Ser vi ce & P ar ts Manu al 200 7 Compact Programmable Models CP14N10 CP18N30 CP24N30 CP-14-18-24-Svc-Prts-07 (3-07).
2 T ab le o f Co n t en ts Per formanc e Data .............................................................................................................. .......................................................... 3 Outer Comp onent Identi fi cation .
3 Model CP14N10 CP18N30 CP24N30 Function COOLING COOLING COOLING Rated V oltage 1 15V ~ 230/208V~ 230/208V~ Rated Frequency 60Hz 60Hz 60Hz T otal Capacity (Btu/h) 14000 18000/17600 23500/23100 Power Input (W) 1430 1850/1810 2740/2710 Rated Input (W) 1540 2478 3538 Rated Current (A) 15 12.
4 Out er Compo ne nt Ide n ti fi ca ti on Models : CP1 4N 1 0 , CP 1 8N3 0, CP2 4N30 Cabinet Air inlet louver F ront grille Pow e r co r d Control panel co ver F ront intake grille Air filter (behind.
5 Installat ion D imensions Models : CP1 4N 1 0 , CP 1 8N30, CP24 N30 (Top View) Fence / obstruction Over 2' Over 1' Over 1' Wall Or window (Front View) (Side View) Ceiling Over 1' Over 1' 25.
6 CP24N30 CP18N30 / CP14N10 Wirin g Dia gram s.
7 F unct ional C omponent De fi niti ons MEC HANIC AL C OMPONEN TS Ve nt d o o r A l l o w s i n t r o d u c t i o n o f f r esh air into the ro om and/or exhausts stale r oom air outsi de ( on select mo dels. ) Plenum assembly D i f f u s e r w i t h d i r e c t i o n a l l o u v e r s u s e d t o d i r e c t the c onditione d air fl ow .
8 In the c ase of the c apillar y tube thi s is acc omplished (by design ) throug h size ( and length ) of device, and th e pressure di f ference present ac ross t he device.
9 EQUIP MENT RE QUIRED 1. Vo l t m e t e r 2. Ammeter 3. Ohmmeter 4. E.P . A . A pproved Ref riger ant Rec overy S ystem. 5. V acuum Pump (capable of 20 0 mic rons or le ss vacuum. ) 6. Acetylene Welder 7 . Elec troni c Halo gen Leak Detec tor (G.E . T yp e H - 6 or equivalen t.
10 NOTE : I n o r d e r t o a c c e s s t h e s e a l e d sy s t e m i t w i l l b e n e c e s s a r y t o i n s t a l l S c h r a d e r t y p e fi t tings to the proce ss tubes on the discharge and suct ion of the c ompress or . Proper refr igerant recovery proc edures need to be adhered t o as outlined in EP A R egulations.
11 A n u n d e r c h a r g e d s y s t e m w i l l r e s u l t i n p o o r p e r f o r m a n c e ( l o w pres sures, etc. ) in both the heatin g and co oling cycl e. Whenever you ser vice a unit wit h an under charge of refrigera nt, always suspect a le ak.
12 RESTRICTED REFRIGERANT SYSTEM A quick c he c k for either c ondit ion begins at t he evaporator . W ith a par tial re stric tion, t here may be gurgling soun ds at the meterin g device entr ance to the evapor ator .
13 Problem Possible Cause Action Compressor does not run Low voltage Check voltage at compressor . 1 15V & 230V units will operate at 10% voltage variance T -stat not set cold enough or inoperative Set t-stat to coldest position. T est t-stat & replace if inoperative Compressor hums but cuts off on B10 overload Hard start compressor .
14 Problem Possible Cause Action Unit does not run Fuse blown or circuit tripped Replace fuse, reset breaker . If repeats, check fuse or breaker size. Check for shorts in unit wiring & components .
15 Problem Possible Cause Action Compressor runs for short periods only . Cycles on overload Overload inoperative. Opens too soon Check operation of unit.
16 Problem Possible Cause Action W ater "spitting" into room Sublimation: When unconditioned saturated, outside air mixes with conditioned air , condensation forms on the cooler surfaces Ensure that foam gaskets are installed in between window panes & in between the unit & the sleeve.
17 Problem Possible Cause Action Room temperature uneven (Heating cycle) Heat anticipator (resistor) shorted (on applicable models) Disconnect power to unit. Remove resistor from t- stat bulb block. Plus in unit & allow to operate. Feel resistor for heat.
18 Problem Possible Cause Action Unit cools when heat is called for Incorrect wiring Refer to applicable wiring diagram Defective solenoid coil Check for continuity of coil Reversing valve fails to shift Block condenser coil & switch unit to cooling.
19 Com pon en ts Model CP 1 4N 1 0.
20 No Description Qty Friedrich Part# Code 1 Supporter Assy 1 67700200 2 Screw ST4.2X13 7 67700154 3 Window locking bracket 2 677001 13 4 Screw 4X20 6 67700151 5 Seal strip 1 1 67700128 6 Seal strip 2 1 67700129 7 Curtain Assemby Left and Right 1 67700201 8 Right Curtain 1 67700202 9 Left Curtain 1 67700203 10 Cabinet Assy 1 67700204 1 1 Screw ST4.
21 No Description Qty Friedrich Part# Code 37 Clapboard of Snail Shell 1 67700108 38 Base Plate of Air Flue 1 67700106 39 Evaporator Assy 1 67700103 40 Sensor Holder 1 67700213 41 Compressor 44B124HXC.
22 No Description Qty Friedrich Part# Code 1 Supporter Assy 1 67700132 2 Self-threading Screw ST4.2x22 7 67700154 3 Window Locking Bracket 2 677001 13 4 Screw 4X20 6 67700151 5 Seal Strip 1 1 67700128.
23 No Description Qty Friedrich Part# Code 36 Blower Wheel 1 677001 16 37 Front Clapboard of Snail Shell 1 67700108 38 Base Plate of Air Flue 1 67700106 39 Evaporator Assy 1 67700103 40 Insert Block 2.
24 Com pon en ts Model CP2 4N30.
25 No Description Qty Friedrich Part# Code 1 Supporter Assy 1 67700200 2 Screw ST4.2X13 7 67700154 3 Window locking bracket 2 677001 13 4 Screw 4X20 6 67700151 5 Seal strip 1 1 67700128 6 Seal strip 2 1 67700129 7 L T & R T Curtain Assembly 1 67700201 8 Right Curtain 1 67700202 9 Left Curtain 1 67700203 10 Cabinet Assy 1 67700238 1 1 Screw ST4.
26 No Description Qty Friedrich Part# Code 38 Base Plate of Air Flue 1 67700106 39 Evaporator Assy 1 67700103 40 Sensor Holder 1 67700213 41 Compressor 44B124HXCEF 1 67700244 42 Overload Protector 1 6.
Friedrich Air Conditioning Company P.O. Box 1540 San Antonio, TX 78295 210.357.4400 www.friedrich.com ROOM AIR CONDITIONERS LIMITED WARRANTY FIRST YEAR A NY PART: If any part supplied by FRIEDRICH fai.
CP-14-18-24-Svc-Prts-07 (3-07) F r iedrich Air Condition ing Co. Post Of f ice Box 15 4 0 • San Ant onio , T exa s 782 9 5 - 15 4 0 420 0 N. Pan A m Expr es sw ay • San Anto ni o, T exa s 7821 8 -5212 (210) 357 - 4 4 0 0 • F A X (210) 357 - 4 4 8 0 w w w.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Friedrich CP14-18-24 CP14N10 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Friedrich CP14-18-24 CP14N10 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Friedrich CP14-18-24 CP14N10, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Friedrich CP14-18-24 CP14N10 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Friedrich CP14-18-24 CP14N10, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Friedrich CP14-18-24 CP14N10.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Friedrich CP14-18-24 CP14N10. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Friedrich CP14-18-24 CP14N10 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.