www .rosemount-tg.com Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 Graphical Field Display.
.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 www .rosemount-tg.com Rosemount 2230 Graphical Field Display Cover Photo: 2230_coverphoto_2.
.
Reference Manual 00809-0100-2230, Rev BB August 2014 TOC-1 Rosemount 2230 Table of Contents T able of Contents SECTION 1 Introduction 1.1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 1.2 Symbols . . . . .
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 TOC-2 Table of Contents SECTION 4 Configuration and Operation 4.1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1 4.2 Introduction . . . . .
Reference Manual 00809-0100-2230, Rev BB August 2014 TOC-3 Rosemount 2230 Table of Contents SECTION 5 Service and Troubleshooting 5.1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1 5.2 Service . . . . . . .
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 TOC-4 Table of Contents.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 www .rosemount-tg.com Section 1 Introduction 1.1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1- 1 1.2 Symbols . . . . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 1-2 Section 1. Introduction 1.2 SYMBOLS The CE marking symbolizes the conformity of the product with the applicable European Community Directives.
Reference Manual 00809-0100-2230, Rev BB August 2014 1-3 Rosemount 2230 Section 1. Introduction 1.3 MANUAL OVERVIEW Section 1:Introduction • Manual overview • Product recycling/disposal • Packin.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 1-4 Section 1. Introduction 1.4 T ECHNICAL DOCUMENTATION The Rosemount T ank Gauging System includes the following documents: Docume.
Reference Manual 00809-0100-2230, Rev BB August 2014 1-5 Rosemount 2230 Section 1. Introduction 1.5 PRODUCT RECYCLING/ DISPOSAL Recycling of equipment and packaging should be taken into consideration and disposed of in accordance with local and national legislation/regulations.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 1-6 Section 1. Introduction.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 www .rosemount-tg.com Section 2 Overview 2.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1 2.2 2230 Components . . . . . . . . . . . . . . . . .
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 2-2 Section 2. Overview 2.2 2230 COMPONENTS Figure 2-2. Rosemount 2230 components 1. Weather protection lid (1) 2. Display 3. Menu 4. Soft keys 5. Activity indicator 6. Cover screw 7.
Reference Manual 00809-0100-2230, Rev BB August 2014 2-3 Rosemount 2230 Section 2. Overview 2.3 SYSTEM OVERVIEW The Rosemount T ank Gauging state-of-the art inventory and custody transfer radar tank l.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 2-4 Section 2. Overview Figure 2-3. Rosemount T ank Gauging System architecture 2230 Display 2240S T emperature T ransmitter 5900S R.
Reference Manual 00809-0100-2230, Rev BB August 2014 2-5 Rosemount 2230 Section 2. Overview Figure 2-4. Rosemount T ank Gauging system architecture for wireless systems 2230 Display 2240S T emperature.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 2-6 Section 2. Overview Figure 2-5. Rosemount T ank Gauging system architecture in a Foundation fieldbus network 2230 Display 2240S .
Reference Manual 00809-0100-2230, Rev BB August 2014 2-7 Rosemount 2230 Section 2. Overview T ankMaster HMI Software T ankMaster is a powerful Windows-based Human Machine Interface (HMI) for complete tank inventory management.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 2-8 Section 2. Overview The Rosemount 5900S sends microwaves towards the surface of the product in the tank.
Reference Manual 00809-0100-2230, Rev BB August 2014 2-9 Rosemount 2230 Section 2. Overview Rosemount Smart Wireless Gateway and Rosemount Smart Wireless THUM Adapter A THUM Adapter allows wireless communication between a 2410 T ank Hub and a Smart Wireless Gateway .
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 2-10 Section 2. Overview 2.3.1 System Start-up The standard start-up procedure of a Rosemount T ank Gauging system that includes dev.
Reference Manual 00809-0100-2230, Rev BB August 2014 2-1 1 Rosemount 2230 Section 2. Overview 2.4 INSTALLATION PROCEDURE Follow these steps for proper installation of the Rosemount 2230 Graphical Field Display: 1. Review installation considerations (“Installation Considerations” on page 3-2) 4.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 2-12 Section 2. Overview.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 www .rosemount-tg.com Section 3 Installation 3.1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1 3.2 Mechanical Installation . . . . . . . . . . . . .
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 3-2 Section 3. Installation 3.2 MECHANICAL INSTALLATION 3.2.1 Installation Considerations The Rosemount 2230 Graphical Field Display can be installed either on the tank roof or at the foot of the tank for a flexible and convenient read-out of tank data.
Reference Manual 00809-0100-2230, Rev BB August 2014 3-3 Rosemount 2230 Section 3. Installation 3.2.2 Mounting the Graphical Display The Rosemount 2230 Graphical Field Display is designed for mounting on a plate, wall, or pipe. Mounting on a Plate The 2230 display can be mounted on a plate by attaching four M4 screws to the back of the display .
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 3-4 Section 3. Installation W all Mounting with Bracket The Rosemount 2230 Graphical Field Display can be mounted on a wall by using the optional mounting kit supplied by Rosemount T ank Gauging.
Reference Manual 00809-0100-2230, Rev BB August 2014 3-5 Rosemount 2230 Section 3. Installation Pipe Mounting The 2230 can be mounted on pipes ranging from a diameter of 33 to 60 mm by using an optional mounting kit supplied by Rosemount T ank Gauging.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 3-6 Section 3. Installation 3.3 ELECTRICAL INSTALLATION 3.3.1 Cable/Conduit Entries The electronics housing has three entries, two M20×1.5 and one M25×1.5 (Optional: adapters for two ½ - 14 NPT and one ¾- NPT).
Reference Manual 00809-0100-2230, Rev BB August 2014 3-7 Rosemount 2230 Section 3. Installation Grounding - F OUNDATION ™ Fieldbus Signal wiring of the fieldbus segment must not be grounded. Grounding one of the signal wires will shut down the entire fieldbus segment.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 3-8 Section 3. Installation 3.3.6 The T ankbus The Rosemount T ank Gauging system is easy to install and wire. Devices can be “daisy-chained” thus reducing the number of segment couplers.
Reference Manual 00809-0100-2230, Rev BB August 2014 3-9 Rosemount 2230 Section 3. Installation 3.3.7 T ypical installations The example below in Figure 3-4 illustrates a system with terminators at both ends of the fieldbus segment as required in a F OUNDATION fieldbus system.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 3-10 Section 3. Installation 3.3.8 2230 in F OUNDATION fieldbus systems The Rosemount 2230 Display supports the F OUNDATION fieldbus (FF) technology and lets you integrate a 2230 into an existing FF network.
Reference Manual 00809-0100-2230, Rev BB August 2014 3-1 1 Rosemount 2230 Section 3. Installation 3.3.9 Wiring Use the following wiring procedure for the Rosemount 2230: 1. Unscrew and remove all screws at the front of the display . 2. Remove the cover carefully .
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 3-12 Section 3. Installation Figure 3-7. 2230 cable connections X2: T ankbus FB+ input X3: T ankbus FB- input Jumper for built-in te.
Reference Manual 00809-0100-2230, Rev BB August 2014 3-13 Rosemount 2230 Section 3. Installation Daisy-Chain Connection Y ou may use the daisy-chain option in order to connect the Rosemount 2230 to other field devices on the T ankbus: 1. Unscrew and remove all six screws on the front of the Rosemount 2230.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 3-14 Section 3. Installation 3.4 LED SIGNALS AND RESET BUTTON The Rosemount 2230 has three LED signals that show communication and status. Figure 3-10. LED Signals Status LED Using different blinking sequences, the status LED indicates error codes.
Reference Manual 00809-0100-2230, Rev BB August 2014 3-15 Rosemount 2230 Section 3. Installation 3.5 SWITCHES 3.5.1 DIP Switches The Rosemount 2230 is equipped with four DIP switches as illustrated in Figure 3-1 1. Figure 3-1 1. DIP Switches The switches control the following settings: T able 3-2.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 3-16 Section 3. Installation 3.6 AMBIENT T EMPERATURE The Rosemount 2230 is equipped with a temperature sensor for measuring ambient temperature. The temperature can be displayed on the field display and in the T ankMaster software.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 www .rosemount-tg.com Section 4 Configuration and Operation 4.1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1 4.2 Introduction . . . . . . . . . . .
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 4-2 Section 4. Configuration and Operation Explosions could result in death or serious injury: V erify that the operating environment of the display is consistent with the appropriate hazardous locations certifications.
Reference Manual 00809-0100-2230, Rev BB August 2014 4-3 Rosemount 2230 Section 4. Configuration and Operation 4.2 INTRODUCTION This chapter provides information about configuration and operation of the Rosemount 2230 Graphical Field Display .
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 4-4 Section 4. Configuration and Operation Adjusting the display contrast The 2230 automatically adjusts display contrast to optimize for changes of ambient temperature. The contrast can be manually adjusted when further fine-tuning is desired.
Reference Manual 00809-0100-2230, Rev BB August 2014 4-5 Rosemount 2230 Section 4. Configuration and Operation 4.2.3 Activity and Alarm Indication The Rosemount 2230 display shows a warning symbol for simulated or manual measurement values as illustrated in Figure 4-2 and Figure 4-3.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 4-6 Section 4. Configuration and Operation 4.2.4 Start-Up Procedure When the Rosemount 2230 display is powered on, a test of the LCD screen is performed. Figure 4-5. T est screen After the LCD test is done the start-up screen will appear .
Reference Manual 00809-0100-2230, Rev BB August 2014 4-7 Rosemount 2230 Section 4. Configuration and Operation 4.3 MENU T REE The Rosemount 2230 lets you navigate in a menu structure as illustrated in Figure 4-8: Figure 4-8.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 4-8 Section 4. Configuration and Operation 4.4 THE MAIN MENU In normal operation the Rosemount 2230 display is in View Mode and shows the current measurement values for the selected tanks.
Reference Manual 00809-0100-2230, Rev BB August 2014 4-9 Rosemount 2230 Section 4. Configuration and Operation 4.5 THE SELECT VIEW MENU In the Select View menu, you can specify the number of measurement values to be displayed in View Mode. T o configure the Select View menu: 1.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 4-10 Section 4. Configuration and Operation 4.6 THE OPTIONS MENU In the Options Menu, the following items are available for a Rosemo.
Reference Manual 00809-0100-2230, Rev BB August 2014 4-1 1 Rosemount 2230 Section 4. Configuration and Operation 4.6.1 V ariables In the Select V ariables menu (1) , you can choose which variables to present in View Mode.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 4-12 Section 4. Configuration and Operation T able 4-1. Selectable variables Select V ariables in T ankMaster WinSetup V ariables to present in the View Mode can also be configured by using the T ankMaster WinSetup configuration program.
Reference Manual 00809-0100-2230, Rev BB August 2014 4-13 Rosemount 2230 Section 4. Configuration and Operation 4.6.2 Select T anks In the Select T anks menu (1) , you can specify which tanks to show in View Mode.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 4-14 Section 4. Configuration and Operation 4.6.3 Units for Display In the Units for Display menu, you can see which measurement units that are used for the displayed variables. The available measurement units are listed in T able 4-2 on page 4-15.
Reference Manual 00809-0100-2230, Rev BB August 2014 4-15 Rosemount 2230 Section 4. Configuration and Operation T able 4-2. Available measurement units for the Rosemount 2230 V ariable A vailable Measurement Units Auto When Auto is selected the unit that will appear on the display is controlled by the Multiple Analog Output Block configuration.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 4-16 Section 4. Configuration and Operation 4.6.4 T oggle Time The T oggle T ime parameter specifies the time period that each value, or set of values, is presented on the display . T o set the T oggle T ime: 1.
Reference Manual 00809-0100-2230, Rev BB August 2014 4-17 Rosemount 2230 Section 4. Configuration and Operation 4.7 THE SERVICE MENU In the Service Menu, the following items are available: • Status • Custody T ransfer V iew (1) • LCD T est • LCD Contrast • Restart • Factory Settings (1) • About T o choose a Service menu item: 1.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 4-18 Section 4. Configuration and Operation 4.7.1 Status The Status screen shows the current status of the 2230. V arious error messages and warnings can be displayed in case of software or hardware malfunctions.
Reference Manual 00809-0100-2230, Rev BB August 2014 4-19 Rosemount 2230 Section 4. Configuration and Operation 4.7.3 LCD T est In the LCD test two checkered patterns will be displayed testing the whole display area. T o open the LCD T est view: 1. In View Mode, press <Menu><Service><LCD T est>: Figure 4-29.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 4-20 Section 4. Configuration and Operation 4.7.5 Restart T o restart the 2230: 1. In View Mode, press <Menu><Service>: Figure 4-31. The Restart option 2. Choose the Restart option and press the softkey .
Reference Manual 00809-0100-2230, Rev BB August 2014 4-21 Rosemount 2230 Section 4. Configuration and Operation 4.7.7 About T o view the About information: 1. In View Mode, press <Menu><Service>. 2. Choose the About option and press the softkey .
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 4-22 Section 4. Configuration and Operation 4.8 F OUNDATION FIELDBUS OVERVIEW This section provides a brief overview of F OUNDATION Fieldbus block operation with the Rosemount 2230 Graphical Field Display .
Reference Manual 00809-0100-2230, Rev BB August 2014 4-23 Rosemount 2230 Section 4. Configuration and Operation 4.9 DEVICE CAPABILITIES 4.9.1 Link Active Scheduler The Rosemount 2230 can be designated to act as the backup Link Active Scheduler (LAS) in the event that the LAS is disconnected from the segment.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 4-24 Section 4. Configuration and Operation 4.10 GENERAL BLOCK INFORMATION 4.10.1 Modes Changing Modes T o change the operating mode, set the MODE_BLK.T ARGET to the desired mode. After a short delay , the parameter MODE_BLOCK.
Reference Manual 00809-0100-2230, Rev BB August 2014 4-25 Rosemount 2230 Section 4. Configuration and Operation 4.10.2 Factory Configuration The following fixed configuration of function blocks is provided: T able 4-5. Available function blocks for the 2230 4.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 4-26 Section 4. Configuration and Operation 4.1 1.2 Application Example A 2230 Graphical Field Display configured for receiving level and temperature measurement data from devices such as the Rosemount 5900S Radar Level Gauge and the Rosemount 2240S T emperature T ransmitter .
Reference Manual 00809-0100-2230, Rev BB August 2014 4-27 Rosemount 2230 Section 4. Configuration and Operation 4.12 RESOURCE BLOCK 4.12.1 FEA TURES and FEA TURES_SEL The FEA TURES parameter is read only and defines which features are supported by the 2230.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 4-28 Section 4. Configuration and Operation The following table displays all possible configurations of the WRITE_LOCK parameter . T able 4-6. Possible configuration of the WRITE_LOCK parameter .
Reference Manual 00809-0100-2230, Rev BB August 2014 4-29 Rosemount 2230 Section 4. Configuration and Operation 4.12.3 Field Diagnostic Alerts The Resource Block acts as a coordinator for Field Diagnostic alerts.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 4-30 Section 4. Configuration and Operation Out of Specification Alarms An Out of Specification alarm indicates that the device operates out of the specified measurement range. If the condition is ignored, the device will eventually fail.
Reference Manual 00809-0100-2230, Rev BB August 2014 4-31 Rosemount 2230 Section 4. Configuration and Operation Maintenance Alarms A Maintenance alarm indicates that the device or some part of the device needs maintenance soon. If the condition is ignored, the device will eventually fail.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 4-32 Section 4. Configuration and Operation Function Check Alarms A Function Check alarm indicates that the device is temporary non-valid due to some activities, for example maintenance, on the device.
Reference Manual 00809-0100-2230, Rev BB August 2014 4-33 Rosemount 2230 Section 4. Configuration and Operation 4.13 475 FIELD COMMUNICATOR MENU T REE The 2230 can be configured by using a 475 Field Communicator . The menu tree below shows the available options for configuration and service.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 4-34 Section 4. Configuration and Operation 4.14 CONFIGURATION USING AMS DEVICE MANAGER The Rosemount 2230 Graphical Field Display supports DD Methods to facilitate device configuration.
Reference Manual 00809-0100-2230, Rev BB August 2014 4-35 Rosemount 2230 Section 4. Configuration and Operation 5. The Overview window shows information about the current device status; Good or Bad . It also gives you access to more detailed information by pressing the Device Information button.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 4-36 Section 4. Configuration and Operation 7. Set the Display T ransducer Block to Out Of Service (OOS) mode by clicking the Change button.
Reference Manual 00809-0100-2230, Rev BB August 2014 4-37 Rosemount 2230 Section 4. Configuration and Operation 10. Configure all the MAO Blocks that are used. Ensure that unused MAO block inputs are unconfigured, i.e. that there are no tank numbers or tank parameters configured for these inputs.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 4-38 Section 4. Configuration and Operation 16. In the Custom Units window specify units for the various custom parameters. The unit label can be specified anyway you like. It does not need to be a standard unit such as metric or imperial units.
Reference Manual 00809-0100-2230, Rev BB August 2014 4-39 Rosemount 2230 Section 4. Configuration and Operation 4.14.2 Manual Setup In case you wish to configure device options not available in the Guided Setup window , for example specifying tank names, you may use the Manual Setup option.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 4-40 Section 4. Configuration and Operation 4.15 ALERT SETUP The Alert Setup window allows you to configure and enable/disable Alerts. For details on how to view active alerts see “Viewing Active Alerts in AMS” on page 5-14.
Reference Manual 00809-0100-2230, Rev BB August 2014 4-41 Rosemount 2230 Section 4. Configuration and Operation 6. Select the desired tab ( FF I/O Board or 2230 Graphical Field Display ).
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 4-42 Section 4. Configuration and Operation 4.15.1 Alert Default Settings The following default settings are used for the FF I/O Board and the 2230 Graphical Field Display . Y ou may configure error types in a different way if you like.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 www .rosemount-tg.com Section 5 Service and T roubleshooting 5.1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-1 5.2 Service . . . . . . . . . . . . .
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 5-2 Section 5. Service and Troubleshooting 5.2 SERVICE 5.2.1 Status Information The Status screen lets you view the current status of the Rosemount 2230 . T o open the status information screen: 1.
Reference Manual 00809-0100-2230, Rev BB August 2014 5-3 Rosemount 2230 Section 5. Service and Troubleshooting 5.2.2 Viewing Input and Holding Registers Measured data is continuously stored in the Rosemount 2230 Input Registers. They can be used for verifying that the Rosemount 2230 works properly and for advanced troubleshooting.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 5-4 Section 5. Service and Troubleshooting 4. The Predefined option lists a basic selection of useful registers. 5. Choose the desired Start Register and enter the Number of Registers to read.
Reference Manual 00809-0100-2230, Rev BB August 2014 5-5 Rosemount 2230 Section 5. Service and Troubleshooting 5.2.3 Restarting the 2230 Display T o restart the Rosemount 2230 choose one of the follow.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 5-6 Section 5. Service and Troubleshooting 5.2.4 Device Error Signals A Light Emitting Diode (LED) inside the 2230 cover is used for presentation of device status using different blinking sequences.
Reference Manual 00809-0100-2230, Rev BB August 2014 5-7 Rosemount 2230 Section 5. Service and Troubleshooting 5 . 3 T ROUBLESHOOTING T able 5-3 provides summarized maintenance and troubleshooting suggestions for the most common operating problems. 5.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 5-8 Section 5. Service and Troubleshooting 5.3.2 T ankbus System This section covers systems with field devices connected to a Rosemount 2410 T ank Hub.
Reference Manual 00809-0100-2230, Rev BB August 2014 5-9 Rosemount 2230 Section 5. Service and Troubleshooting 5.3.3 Foundation Fieldbus System This section covers Rosemount T ank Gauging systems in F OUNDATION fieldbus networks.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 5-10 Section 5. Service and Troubleshooting 5.3.4 Device Errors T able 5-6 shows a list of error messages for the Rosemount 2230 . Detailed information about the different error types can be found in Input registers 1 100 - 1 134 as shown in T able 5-6.
Reference Manual 00809-0100-2230, Rev BB August 2014 5-1 1 Rosemount 2230 Section 5. Service and Troubleshooting 5.3.5 Device W arnings Device warnings are signaled in the Input Register Device Warnings. W arnings are less serious than errors. Detailed information about the different warning types can be found in Input registers 1050 - 1070.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 5-12 Section 5. Service and Troubleshooting 5.3.6 Status Information Status information is available for each measurement variable via the Status button in the View menu. T able 5-8. Status Information Status button Status Description Action Invalid_TV_V alue Invalid source value.
Reference Manual 00809-0100-2230, Rev BB August 2014 5-13 Rosemount 2230 Section 5. Service and Troubleshooting 5.4 RESOURCE BLOCK T able 5-9. Resource Block BLOCK_ERR messages 5.5 T RANSDUCER BLOCK Error conditions that may appear in the T ransducer block.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 5-14 Section 5. Service and Troubleshooting 5.6 ALERTS The AMS Device Manager lets you view active alerts. The alarm parameters FD_F AIL_ALM, FD_OFFSPEC_ALM, FD_MAINT_ALM, and FD_CHECK_ALM contain information regarding some of the device errors.
Reference Manual 00809-0100-2230, Rev BB August 2014 5-15 Rosemount 2230 Section 5. Service and Troubleshooting 6. The Active Alerts tab shows the alerts that are currently active. All types of alerts can be shown; Failed, Maintenance, Out of Specification, and Check Function.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 5-16 Section 5. Service and Troubleshooting 5.6.2 Recommended Actions The FD_RECOMMEN_ACT and RECOMMENDED_ACTION parameters display text strings that will give a recommended course of action to take based on which type and which specific event of the alert that is active.
Reference Manual 00809-0100-2230, Rev BB August 2014 5-17 Rosemount 2230 Section 5. Service and Troubleshooting 5.7 SERVICE T OOLS IN AMS 5.7.1 Service T ools Window AMS Device Manager supports a number of service functions for the 2230 display . T o access the service tools: 1.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 5-18 Section 5. Service and Troubleshooting 4. In the Navigation Pane select the desired Service T ools option.
Reference Manual 00809-0100-2230, Rev BB August 2014 5-19 Rosemount 2230 Section 5. Service and Troubleshooting 5.7.2 Device Status T o view the current device status: 1. In AMS Device Manager open Service T ools window as shown in section “Service T ools Window” on page 5-17.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 5-20 Section 5. Service and Troubleshooting 5.7.3 Viewing Input/Holding Registers Measurement data is continuously updated in the Rosemount 2230 Input Registers. They can be used for verifying that the Rosemount 2230 works properly and for advanced troubleshooting.
Reference Manual 00809-0100-2230, Rev BB August 2014 5-21 Rosemount 2230 Section 5. Service and Troubleshooting 5. Select one of the tabs Holding Registers or Input Registers , depending on what type of register you are interested in.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 5-22 Section 5. Service and Troubleshooting 5.7.4 Reset/Restore The Service T ools/Maintenance option lets you restart the Rosemount 2230 Display if needed. Y ou may also reset the 2230 to factory configuration: 1.
Reference Manual 00809-0100-2230, Rev BB August 2014 5-23 Rosemount 2230 Section 5. Service and Troubleshooting 5.7.5 V ariables The Service T ools/V ariables option lets you view the current values of the Multiple Analog Output Block inputs as well as the Internal T emperature of the 2230 Display .
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 5-24 Section 5. Service and Troubleshooting 5.7.6 Simulation The Service T ools/Maintenance option lets you simulate Field Diagnostics alerts. T o start simulation: 1. Ensure that the Simulation switch is set to “ON” (see “Write Protection” on page 5-25).
Reference Manual 00809-0100-2230, Rev BB August 2014 5-25 Rosemount 2230 Section 5. Service and Troubleshooting 5.8 WRITE PROTECTION There are two write protection options available for the 2230 Display; hardware switch and software protection.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 5-26 Section 5. Service and Troubleshooting Software Write Protection in AMS When the Rosemount 2230 Display is used in F OUNDATION fieldbus systems it can be software write protected in order to prevent changes of the configuration database and F IELDBUS parameters.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 www .rosemount-tg.com Appendix A Reference Data A.1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-1 A.2 Dimensional drawings . . . . . . . . . . . .
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 A-2 Appendix A. Reference Data F OUNDATION ™ fieldbus characteristics Polarity sensitive No Quiescent current draw 30 mA Lift-off minimum voltage 9.
Reference Manual 00809-0100-2230, Rev BB August 2014 A-3 Rosemount 2230 Appendix A. Reference Data A.2 DIMENSIONAL DRAWINGS Figure A-1. Dimensional drawings 150 mm (5.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 A-4 Appendix A. Reference Data A.3 ORDERING INFORMATION Model (Pos 1) Product Description Note 2230 Graphical Field Display Code (Po.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 www .rosemount-tg.com Appendix B Product Certifications B.1 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . page B-1 B.2 EU Conformity . . . . . . . . . . . . . .
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 B-2 Appendix B. Product Certifications B.2 EU CONFORMITY The EC declaration of conformity for all applicable European directives for this product can be found on the Rosemount T ank Gauging web site at www .
Reference Manual 00809-0100-2230, Rev BB August 2014 B-3 Rosemount 2230 Appendix B. Product Certifications B.3 HAZARDOUS LOCATIONS CERTIFICATIONS The Rosemount 2230 Graphical Field Displays that have the following labels attached have been certified to comply with the requirements of the approval agencies noted.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 B-4 Appendix B. Product Certifications B.3.2 Factory Mutual Canadian Approvals Certificate of Compliance: 3037177C.
Reference Manual 00809-0100-2230, Rev BB August 2014 B-5 Rosemount 2230 Appendix B. Product Certifications B.3.3 European A TEX Directive Information The Rosemount 2230 Graphical Field Displays that h.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 B-6 Appendix B. Product Certifications Specific Conditions of Certification (X) 1. The non-metallic parts incorporated in the enclosure of this equipment may generate an ignition-capable level of electrostatic charge.
Reference Manual 00809-0100-2230, Rev BB August 2014 B-7 Rosemount 2230 Appendix B. Product Certifications B.3.4 IECEx Approval Figure B-4. IECEx Intrinsic Safety Approval Label I7 The following infor.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 B-8 Appendix B. Product Certifications B.4 APPROVAL DRAWINGS Follow the installation guidelines presented in Factory Mutual system control drawings in order to maintain certified ratings for installed devices.
Reference Manual 00809-0100-2230, Rev BB August 2014 C-1 Rosemount 2230 Appendix C. F OUNDATION fieldbus Block Information Appendix C F OUNDATION fieldbus Block Information C.1 Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . page C-2 C.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 C-2 Appendix C. F OUNDATION fieldbus Block Information C.1 RESOURCE BLOCK This section contains information on the Resource Block of the Rosemount 2230S Graphical Field Display . The resource block defines the physical resources of the device.
Reference Manual 00809-0100-2230, Rev BB August 2014 C-3 Rosemount 2230 Appendix C. F OUNDATION fieldbus Block Information 17 FEA TURES Used to show supported resource block options.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 C-4 Appendix C. F OUNDATION fieldbus Block Information 42 FD_VER A parameter equal to the value of the major version of the Field Diagnostics specification that this device was designed to.
Reference Manual 00809-0100-2230, Rev BB August 2014 C-5 Rosemount 2230 Appendix C. F OUNDATION fieldbus Block Information T able C-2. FD_SIMULA TE elements 77 F AILED_PRI Designates the alarming priority of the F AILED_ALM and also used as switch b/w FD and legacy PW A.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 C-6 Appendix C. F OUNDATION fieldbus Block Information C.2 REGISTER T RANSDUCER BLOCK The Register T ransducer Block (TB 1200) allows access to Database registers and Input registers of the Rosemount 2230 Graphical Field Display .
Reference Manual 00809-0100-2230, Rev BB August 2014 C-7 Rosemount 2230 Appendix C. F OUNDATION fieldbus Block Information 12 COLLECTION_DIRECTORY A directory that specifies the number , starting indices, and DD Item ID’s of the data collections in each transducer within a transducer block.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 C-8 Appendix C. F OUNDATION fieldbus Block Information C.3 MAIN T RANSDUCER BLOCK The Main T ransducer (TB1 100) block contains parameters for configuration of the Rosemount 2230 Graphical Field Display .
Reference Manual 00809-0100-2230, Rev BB August 2014 C-9 Rosemount 2230 Appendix C. F OUNDATION fieldbus Block Information C.3.1 Diagnostic Device Alerts T able C-5 lists conditions reported in the DIAGN_DEVICE_ALERT parameter .
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 C-10 Appendix C. F OUNDATION fieldbus Block Information C.4 DISPLAY T RANSDUCER BLOCK The Display T ransducer block (TB 1300) includes parameters for setup of the 2230 Graphical Field Display for use in a F OUNDATION Fieldbus system.
Reference Manual 00809-0100-2230, Rev BB August 2014 C-1 1 Rosemount 2230 Appendix C. F OUNDATION fieldbus Block Information 25 MAO_2_INPUT_4 26 MAO_2_INPUT_5 27 MAO_2_INPUT_6 28 MAO_2_INPUT_7 29 MAO_.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 C-12 Appendix C. F OUNDATION fieldbus Block Information 67 CUSTOM_UNIT_2 Set the preferred text to show on the display for custom unit 2. 68 CUSTOM_UNIT_3 Set the preferred text to show on the display for custom unit 3.
Reference Manual 00809-0100-2230, Rev BB August 2014 C-13 Rosemount 2230 Appendix C. F OUNDATION fieldbus Block Information C.5 MULTIPLE ANALOG OUTPUT BLOCK The Multiple Analog Output Block (MAO_1400 to MAO_1700) accepts output values from field devices and assigns them to specified I/O channels in order to make them available for the display .
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 C-14 Appendix C. F OUNDATION fieldbus Block Information 19 FST A TE_V AL2 The preset analog value to use when failure occurs in IN_2. Ignored if the “Fault state to value 2” in the MO_OPTS parameter is false.
Reference Manual 00809-0100-2230, Rev BB August 2014 C-15 Rosemount 2230 Appendix C. F OUNDATION fieldbus Block Information C.6 SUPPORTED UNITS The 2230 Graphical Field Display supports the following units: T able C-8. T emperature T able C-9. Length T able C-10.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 C-16 Appendix C. F OUNDATION fieldbus Block Information T able C-13. Pressure ID Display Description 1 130 Pa Pascal 1 133 kPa Kilo .
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 www .rosemount-tg.com Index Symbols . . . . . . . . . . . . . . . . . . . . . . . . . 4-26 Numerics 2160 Field Communication Unit . 2-7 2230 Foundation fieldbus . . . . . . . 2-1 2410 .
Rosemount 2230 Index-2 Reference Manual 00809-0100-2230, Rev BB August 2014 I IECEx Approval . . . . . . . . . . . . . . B-7 Input mapping . . . . . . . . . . . . . . 4-36 Input Registers . . . . . . . . . 5-3 , 5-20 Installation Electrical . . . . . .
Index-3 Rosemount 2230 Reference Manual 00809-0100-2230, Rev BB August 2014 Write Protect switch . . . . 3-15 , 5-25 Write Protection . . . . . . . . . . . . 5-25 WRITE_LOCK parameter . . . . . 4-27 X X1 terminal . . . . . . . . . . . . . . . . 3-1 1 X2 and X3 terminals .
Rosemount 2230 Index-4 Reference Manual 00809-0100-2230, Rev BB August 2014.
.
Reference Manual 00809-0100-2230, Rev BB August 2014 Rosemount 2230 Emerson Process Management © 2014 Rosemount T ank Radar AB. All rights reserved. Rosemount and the Rosemount logotype are trademarks of Rosemount Inc. HART is a trademark of the HAR T Communication Foundation.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Emerson 2230 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Emerson 2230 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Emerson 2230, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Emerson 2230 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Emerson 2230, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Emerson 2230.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Emerson 2230. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Emerson 2230 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.