Manuel d'utilisation / d'entretien du produit DT3 du fabricant Delta
Aller à la page of 21
1 DT3 Series T emperature Controller Instruction Sheet Precaution DANGER! Caution! Electric Shock ! 1. Do not touch the AC terminals while the power is s upplied to the controller to prevent an electric shock. 2. Make sure power is disconnected while checking the unit inside.
2 V : V oltage Pulse Output, 12V ±10% C: DC Current Output 4 ~ 20 m A L: Linear V oltage Ouptut 0 ~ 10 V DC EVENT inputs/ CT function (optional) 1 0: None, 1: Event Input3, 2: RS-485 Communication EV.
3 ALARM1 LOW: Lower limit alarm 1 (display according to the setting in ALARM mode) 4.0 ALARM2 HIGH: Upper limit alarm 2 (display according to the setting in ALARM mode) 4.0 ALARM2 LOW: Lower limit alarm 2 (display according to the setting in ALARM mode) 4.
4 ALARM mode) ALARM3 DELAY: Set up Alarm 3 delay (refer to “Alarm Outputs” ) (display when OUT2 is set to ALARM mode) 0 PV Color Change Function: Select the alarm to change PV display color.
5 SV SLOPE: Set up rising slope (when CRTS = SLOP) ANALOG OUT1 MAX.: Adjust upper limit compensation for analog Output 1 (1scale = 1 μ A; 1scale = 1mV) 0 ANALOG OUT1 MIN.: Adjust lower limit compensation for analog Output 1* (1 scale = 1 μ A; 1scal e = 1mV) 0 ANALOG OUT2 MAX.
6 Initial Start-up Setting 1. When setting up DT3 for the first time, press key for more than 3 seconds till the screen display and select according to your temperature sensor type. Please be aware that a selection of wrong model would cause PV temperature display error .
7 For example: Measure V alue=25.0; Compensation = 1.2. Af ter applying to the Compensation equation PV=26.2. ¾ Linear Compensation Gain (setti ng range = 0~0.999). Linea r Compensation Gain Calcul ation equation: PV = Measure V alue* (1 + Gain/1.000) + Compensation.
8 ¾ T o set Retransmission to positive/negative slopes (a Retransmission board must be installed first): In 【 Initial Setting Mode 】 set the parameter , the last digit (Y) of xxxY indica tes when Y =0 positive slope; when Y=1 negative slope.
9 O u t p u t o f when in PID control mode (Ctrl= PID): When the controller is in PID control and dual loop output mode, sets the P value of the 2nd set of PID. The 1st set of PID is generated when TUNE= AT, but user can also manually sets the PI D value.
10 If the setting control is in running mode, the program will st ar t running from the initial pattern and initial step, and carry out commands one by one. When the setting control is in end mode, the program will stop running and give out an output disable.
11 ¾ Remote compensation adjustment: input corresponding lower limit of analog signal at the Remote end, set Remote compensation adjustment by parameter in 【 Regulation Mode 】 ¾ Remote gain adju.
12 c 、 Coef and DeadB and are added in the PID parameter for double out put (one for heating and one for c ooling). Coef refers to the ratio between the first and second portions of output (P parameter of second group =Coef*P , Coef= 0.01~99.99); DeadBand is the overlapping temperature of the P output of the first group an d the second group.
13 Auto Fine-tune the PID value. During the calculation, A T LED li ghts up in the display panel. When the PV value generates 2 curv es of temperature oscillation based on the SV value, the A T process is completed and the A T LED in the panel goes out.
14 EVENT Function This controller provides a maximum of 3 EVENT s (EV1~EV3) for respectively setting EV functions as shown in the following T able <1>.
15 M103 M203 M303 M104 M204 M304 M105 M205 M305 M106 M206 M306 M107 M207 M307 M108 M208 M308 M109 M209 M309 M110 M210 M310 M111 M211 M311 M112 M212 M312 M113 M213 M313 M114 M214 M314 M115 M215 M315 M1.
16 screen . If the password is incorrect, the screen will return to PV/SV display mode. 3. Enter the new password two times in the screen. The screen w ill return to PV/SV display mode with the ke ys unlocked. If the two entries of password are not the same, the screen will go back to the state of step 2.
17 17 When HOLD status happens to PI D program control, alarm output is ON. 18 When STOP status happens to PID prog ram control, alarm output is ON. 19 When END status happens to PID progra m control, alarm output is ON. ¾ T o set Alarm Mode: Use the parameters , , in 【 Initial Setting Mode 】 to select the alarm mode.
18 1006H Heating/Cooling control selection Refer to Ouputput Mode Selection 1007H 1st group of Heating/Cooling control cycle 1~990, unit is 0.1 second. When the output setting = realy , the minimum control cycle is 5 second 1008H 2nd group of Heating/Cooling control cycle 1~990, unit is 0.
19 1 103H Reverse Out put Bit1: output 2, Bit0: output 1 1 104H Slope of T emperature Increase Unit: 0.1 / ℃ min or 0.1 ℃ /sec (refer to CommunicationAddress 1 124 H) 1 105H Remote Input T ype Sel.
20 selection 0812H Decimal point position selection 0: No decimal place 1: decimal place. (Except for t he thermocouple B,S,R type, all other thermocouple type are valid.
21 Panel Cutout Pattern Panel Cutout ( W * H ) Model Panel Cutout ( W * H ) 4848 (DT320) 45mm * 45mm 7272 (DT330) 68mm * 68mm 4896 (DT340) 44.5mm * 91.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Delta DT3 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Delta DT3 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Delta DT3, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Delta DT3 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Delta DT3, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Delta DT3.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Delta DT3. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Delta DT3 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.