Manuel d'utilisation / d'entretien du produit 7626-T-110 du fabricant 3M
Aller à la page of 20
3M ™ C old Shrink QT - II I Si licone R ubber Indo or T u bu lar T e rmi na tion K it With Hi gh-K Stress R e l i ef For T ape Shield, Wir e Shield and UniShield ® Cable 7622-T -110, 7623-T -110, 7624-T -110, 7625-T -110, 7626-T -110 Instructions IEEE Std.
2 78-81 13-5099-6 Rev E 1.0 Kit Contents 3 High–K, T racking Resistant, Silicone Rubber T erminations 3 Pre-formed Ground Braids 3 Constant Force Springs 3 3M ™ EMI Copper Foil Shielding T ape 1 1.
78-81 13-5099-6 Rev E 3 2.0 Instructions for T ape Shielded Cable Prepare Cable 2.1 Check to be sure cable size fits within kit range as shown in T able 1. 2.2 Prepare cable using dimensions shown in Figure 1. BE SURE T O ALLOW FOR DEPTH OF TERMINAL LUG.
4 78-81 13-5099-6 Rev E 3.2 Position pre-formed ground braid with short tail over tape shield directly adjacent to cable jacket cut edge. PLEASE NOTE: The ground braid needs to make full contact with the metallic tape shield. Position long tail of ground braid, extending over cable jacket with solder block over mastic strip (Figure 3).
78-81 13-5099-6 Rev E 5 3.5 W rap two highly stretched half-lapped layers of electrical grade vinyl tape around Scotch ® Mastic Strip 2230, constant force spring and exposed tape shield (Figure 5). NOTE: T ake care not to cover exposed semi-con insulation shield.
6 78-81 13-5099-6 Rev E 6.0 Install T ermination 6.1 Slide the termination body onto the cable and remove core. Make sure the termination body (not the core) is butted up to the edge of the vinyl tape marker previously applied (Figure 7). Pull the core while unwinding, counter- clockwise, starting with the loose end (Figure 7).
78-81 13-5099-6 Rev E 7 Instructions for Wire Shielded Cable 7.0 Prepare Cable 7.1 Check to be sure cable size fits within kit range as shown in T able 1. 7.2 Prepare cable using dimensions shown in Figure 8 and Figure 9. BE SURE T O ALLOW FOR DEPTH OF TERMINAL LUG.
8 78-81 13-5099-6 Rev E 8.0 Install Ground Braid 8.1 Select a Scotch ® Mastic Strip 2230 from kit and remove white release liners. Using light tension apply a SINGLE WRAP of mastic around the cable jacket 1/4" (6 mm) from cut edge (Figure 10). Cut off excess.
78-81 13-5099-6 Rev E 9 8.3 W rap ground braid around cable shield wires one complete wrap, trim excess to prevent overlap and secure in place with constant force spring. W rap spring in same direction as ground braid (Figure 12). Cinch (tighten) the spring after wrapping the final winding.
10 78-81 13-5099-6 Rev E 9.0 Install Lug or Connector Important Packaging Notice In order to make sure that you receive an undamaged termination, this 3M™ Cold Shrink QT -III T ermination is packed with a RED SHIPPING CORE inside of the white core. Please remove the red shipping core BEFORE you install the termination.
78-81 13-5099-6 Rev E 11 1 1.2 Connect ground braid to system ground according to standard practice. Semi-Con Insulation Shield Ridge at End of Cable Insulation Shield (Semi-Con) Ridge at End of High-.
12 78-81 13-5099-6 Rev E 12.4 Remove constant force spring. Bend shield wires back upon cable jacket 1-1/2" (38 mm). Cut excess shield wire and discard (Figure 17). 9" (229 mm) 1-1/2" (38 mm) Semi-Conductive Jacket Fold Back Shield Wires Depth Of T erminal Lug + Growth Allowance Figure 17 12.
78-81 13-5099-6 Rev E 13 13.0 Install Ground Braid 13.1 Select a Scotch ® Mastic Strip 2230 from kit and remove white release liners. Using light tension apply a SINGLE WRAP of mastic around the cable semi-conductive jacket 1/4" (6 mm) from shield wires (Figure 19).
14 78-81 13-5099-6 Rev E Shield Wires Constant Force Spring Ground Braid Solder Block Ground Braid Leg T rim Cable Wire Shield 1st Scotch ® Mastic Strip 2230 2nd Scotch ® Mastic Strip 2230 Figure 21 13.
78-81 13-5099-6 Rev E 15 NOTE: Refer to pages 17-19 for 3M ™ connector and lug crimping information. NOTE: For Aluminum Conductors - Thoroughly wire brush conductor strands to remove aluminum oxide layer . Insert conductor into lug or connector and then remove conductor .
16 78-81 13-5099-6 Rev E Semi-Con Ridge at End of Cable Insulation Shield (Semi-Con) Ridge at End of High-K T ube Correct Installation of T ermination on UniShield ® Shielded Cable Cable Insulation C.
78-81 13-5099-6 Rev E 17 T ooling Index Lug and Crimping Information for 3M ™ Scotchlok ™ Copper Lugs 30014 thru 30045 One hole 31036 thru 31068 One hole-long barrel Cable Size AWG/ kcmil Stud Size (in.
18 78-81 13-5099-6 Rev E T ooling Index Lug and Crimping Information for 3M ™ Scotchlok ™ Copper/Aluminum Lugs 40016 thru 40079 One hole 40132 thru 40178 T wo hole Cable Size AWG/ kcmil Stud Size (in.
78-81 13-5099-6 Rev E 19 T ooling Index Crimping Information for 3M ™ Stem Connectors Copper/Aluminum Conductor Size AWG & kcmil 3M ™ Connector Number Crimping T able For 3M ™ Stem T ype Connector Recommended Crimping T ools Stranded Solid Manufacturer Mech.
3M, Scotch and Scotchlok are trademarks of 3M Company . UniShield is a trademark of General Cable T echnologies Corporation. Important Notice All statements, technical information, and recommendations related to 3M's products are based on information believed to be reliable, but the accuracy or completeness is not guaranteed.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté 3M 7626-T-110 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du 3M 7626-T-110 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation 3M 7626-T-110, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le 3M 7626-T-110 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le 3M 7626-T-110, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du 3M 7626-T-110.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le 3M 7626-T-110. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei 3M 7626-T-110 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.