Manuel d'utilisation / d'entretien du produit GT-PX du fabricant Carrier
Aller à la page of 56
Carr ier works continually to improve its products. As a result, the design and speci fi cations of each product at the time for order may be changed without notice and may not be as described herein.
.
Indoor & Outdoor Split Geother mal Comfor t Systems Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 1 T able of Contents Geothermal Advantages .............................................................................
Car r ier Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 2 Geother mal Advantages Geothe rmal s ys tems tr ansfer heat fr om a build ing to the ear t h in the cooling mode, or fr om the ear t h to the building in the heating mode .
Indoor & Outdoor Split Geother mal Comfor t Systems Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 3 V er tical Loops ar e the ideal choice when available land ar ea is limited. Dr illing equipm ent is used to bore small - diameter ver tical holes .
GT -PX 4 Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 Rounding Out the Product Line Building upon the ov erwhelming mar ket success of the GT -PX packaged unit, the split system uses the same components in a more fl exible con fi guration.
T wo-Stage Indoor Split Puron ® Systems 5 Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 Other Ne w Features • Stylish two-tone look with textured b lack powder coat paint and stainless steel front access panel. • Liftout handle for front access panel.
GT -PX 6 Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 - Automatically performs special leak tests on all joints. - Conducts pressure tests. - P erforms highly detailed r un test unpar alleled in the HV A C industr y . - Automatically disables packaging f or a “failed” unit.
T wo-Stage Indoor Split Puron ® Systems 7 Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 Three Easy , Lift-out Ser vice Access Panels with Stainless Steel Front Panel Over.
GT -GS 8 Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 Application Fle xibility • Eight Capacities 018, 024, 030, 036, 042, 048, and 060. • V oltage availability in 208-230/60/1. • Stackable cabinets. • Extended r ange operation (20-120°F EWT) and fl ow rates as low as 1.
Single-Stage Indoor Split R22 Systems 9 Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 Options & Accessor ies • Optional hot water gener ator with internally mounted pump. • Optional cupronickel coaxial heat exchanger .
GT -S 10 Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 What is the GT -S? Car rier introduced the industr y to the fi r st ever “outdoor” geothermal split system with inter nal pumping for residential applications.
Single-Stage Outdoor Split R22 Systems 11 Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 The GT -S does not need to be located outside . It can be placed in gar ages, car por ts, basements, cr a wl spaces, etc . This may be impor tant to some homeowner s who ma y be ver y concer ned about outdoor aesthetics.
GT -S 12 Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 Application Fle xibility • Eight Capacities 018, 024, 030, 036, 042, 048, and 060. • V oltage availability in 208-230/60/1. • Stackable cabinets. • Extended r ange operation (20-120°F EWT) and fl ow rates as low as 2.
Single-Stage Outdoor Split R22 Systems 13 Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 Options & Accessor ies • Optional remote-mounted hot water gener ator with inter nally mounted pump . • Optional cupronickel coaxial heat exchanger .
Car r ier Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 14 ARI/ISO/ASHRAE 13256-1 GT -PX (50YDS) Performance Data - English (IP) Units GT -PX (50YDS) Performance Data - Me.
Indoor & Outdoor Split Geother mal Comfor t Systems Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 15 ARI/ISO/ASHRAE 13256-1 GT -GS (50YCS) & GT -S (38WQS) Performance Data - English (IP) Units GT -GS (50YCS) & GT -S (38WQS) Performance Data - Metric (SI) Units Cooling capacities based upon 80.
Car r ier Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 16 GT -PX Nomenclature GT -GS Nomenclature 38WQS Nomenclature Model Nomenclature SS = ST ANDARD SIZE: 4 042 048 060.
Indoor & Outdoor Split Geother mal Comfor t Systems Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 17 CFM = air fl ow , cubic feet/minute EWT = entering water temperat.
GT -PX 18 Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 P erfor mance Cor rection F actor s Full Load Heating Corrections Full Load Cooling Corrections Sens Clg Cap Multipliers- Entering DB ° F Ent Air DB ° F Htg Cap Power Heat of Ext Ent Air WB ° F T otal Clg Cap 60 65 70 75 80 80.
T wo-Stage Indoor Split Puron ® Systems 19 Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 50YDS026 P ar t Load W ith FV4003 20 7.00 4.5 10.4 450 0 0 0 0 0 0 10.9 1.17 7.2 92.4 2.73 1.9 20 7.00 4.5 10.4 530 0 0 0 0 0 0 1 1.
GT -PX 20 Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 50YDS026 Full Load W ith FV4003 20 8.00 5.6 12.9 750 0 0 0 0 0 0 14.9 1.54 9.8 88.4 2.84 2.4 20 8.00 5.6 12.9 880 0 0 0 0 0 0 15.1 1.49 10.1 85.9 2.97 2.1 30 4.00 1.5 3.
T wo-Stage Indoor Split Puron ® Systems 21 Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 50YDS038 P ar t Load W ith FV4005 20 8.00 4.7 10.9 600 0 0 0 0 0 0 16.5 1.64 1 1.1 95.5 2.95 2.4 20 8.00 4.7 10.9 700 0 0 0 0 0 0 16.
GT -PX 22 Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 20 9.00 5.9 13.6 1000 0 0 0 0 0 0 23.3 2.25 15.9 91.6 3.04 2.9 20 9.00 5.9 13.6 1200 0 0 0 0 0 0 23.6 2.18 16.3 88.2 3.17 2.5 30 4.50 1.7 3.9 1000 41.8 21.7 1.66 46.7 25.
T wo-Stage Indoor Split Puron ® Systems 23 Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 50YDS049 P ar t Load W ith FV4006 20 1 1.00 4.0 9.2 850 0 0 0 0 0 0 22.3 2.16 15.3 94.3 3.03 3.3 20 1 1.00 4.0 9.2 1000 0 0 0 0 0 0 22.
GT -PX 24 Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 50YDS049 Full Load W ith FV4006 20 12.00 4.8 1 1.1 1400 0 0 0 0 0 0 31.8 2.89 22.2 91.0 3.22 3.8 20 12.00 4.8 1 1.1 1650 0 0 0 0 0 0 32.3 2.80 22.8 88.1 3.38 3.3 30 6.
T wo-Stage Indoor Split Puron ® Systems 25 Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 50YDS064 P ar t Load W ith FV4006 20 14.00 4.1 9.5 1000 0 0 0 0 0 0 28.6 2.93 19.0 96.5 2.86 3.4 20 14.00 4.1 9.5 1200 0 0 0 0 0 0 29.
GT -PX 26 Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 20 15.00 5.0 1 1.6 1575 0 0 0 0 0 0 39.4 3.90 26.5 93.2 2.96 4.0 20 15.00 5.0 1 1.6 1850 0 0 0 0 0 0 40.0 3.78 27.2 90.0 3.10 3.5 30 7.50 0.6 1.4 1575 61.7 37.7 3.19 71.
Indoor & Outdoor Split Geother mal Comfor t Systems Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 27 50YCS018 / 38WQS018 W ith GAH018 Performance capacities shown in thousands of Btuh. WPD HEA TING - EA T 70 ° F COOLING - EA T 80/67 ° F EWT ° FG P M PSI FT CFM HC KW HE LA T COP HWC TC SC KW HR EER HWC 2.
Car r ier Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 28 50YCS024 / 38WQS024 W ith GAH024 Performance capacities shown in thousands of Btuh. WPD HEA TING - EA T 70 ° F COOLING - EA T 80/67 ° F EWT ° F GPM PSI FT CFM HC KW HE LA T COP HWC TC SC KW HR EER HWC 3.
Indoor & Outdoor Split Geother mal Comfor t Systems Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 29 50YCS030 / 38WQS030 W ith GAH030 Performance capacities shown in thousands of Btuh. WPD HEA TING - EA T 70 ° F COOLING - EA T 80/67 ° F EWT ° F GPM PSI FT CFM HC KW HE LA T COP HWC TC SC KW HR EER HWC 3.
Car r ier Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 30 50YCS036 / 38WQS036 W ith GAH036 Performance capacities shown in thousands of Btuh. WPD HEA TING - EA T 70 ° F COOLING - EA T 80/67 ° F EWT ° FG P M PSI FT CFM HC KW HE LA T COP HWC TC SC KW HR EER HWC 4.
Indoor & Outdoor Split Geother mal Comfor t Systems Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 31 50YCS042 / 38WQS042 W ith GAH042 Performance capacities shown in thousands of Btuh. WPD HEA TING - EA T 70 ° F COOLING - EA T 80/67 ° F EWT ° FG P M PSI FT CFM HC KW HE LA T COP HWC TC SC KW HR EER HWC 5.
Car r ier Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 32 50YCS048 / 38WQS048 W ith GAH048 Performance capacities shown in thousands of Btuh. WPD HEA TING - EA T 70 ° F COOLING - EA T 80/67 ° F EWT ° F GPM PSI FT CFM HC KW HE LA T COP HWC TC SC KW HR EER HWC 6.
Indoor & Outdoor Split Geother mal Comfor t Systems Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 33 50YCS060 / 38WQS060 W ith GAH060 Performance capacities shown in thousands of Btuh. WPD HEA TING - EA T 70 ° F COOLING - EA T 80/67 ° F EWT ° F GPM PSI FT CFM HC KW HE LA T COP HWC TC SC KW HR EER HWC 7.
Car r ier Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 34 Physical Data GT -S (38WQS) Physical Data GT -GS (50YCS) Physical Data GT -PX (50YDS) Physical Data Model 026 038 049 064 Compressor [1 Each) Copeland UltraT ech T wo-Stage Scroll Factory Charge R410A (oz) [kg] 90 [2.
Indoor & Outdoor Split Geother mal Comfor t Systems Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 35 GT -PX Dimensional Data GT -PX (50YDS) Dimensional Data Model Over.
Car r ier Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 36 GT -GS Dimensional Data Overall Cabinet Water Connections Refrigerant Connections Electrical Knockouts Model A B.
Indoor & Outdoor Split Geother mal Comfor t Systems Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 37 33 [83.8cm] 22 [55.
Car r ier Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 38 Electr ical Data Model Compressor HWG Pump FLA External Pump FLA T otal Unit FLA Min Circuit Amps Max Fuse/ HACR Min AW G Max Wire Ft. (m) RLA LRA Qty 026 10.3 52 1 0.
Indoor & Outdoor Split Geother mal Comfor t Systems Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 39 Ther mostat W ir ing Thermostat Installation The thermostat should be located on an interior wall in a larger room, away from supply duct drafts.
Car r ier Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 40 CXM Control For detailed control information, see CXM/DXM Application, Operation and Maintenance (AOM) manual (part #97B0003N08).
Indoor & Outdoor Split Geother mal Comfor t Systems Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 41 CXM Controls Safety Features – CXM Control The safety features b.
Car r ier Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 42 Unit Operation T -stat signal TTS GSS/PDW GSS/PDW V ariable Speed Air Handler V ariable Speed Air Handler PSC Ai.
Indoor & Outdoor Split Geother mal Comfor t Systems Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 43 GT -PX Split W ir ing Diagr am.
Car r ier Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 44 GT -GS Split W ir ing Diagr am.
Indoor & Outdoor Split Geother mal Comfor t Systems Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 45 GT -S Split W ir ing Diagr am.
Car r ier Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 46 Equipment Selection The installation of geothermal heat pump units and all associated components, parts, and acc.
Indoor & Outdoor Split Geother mal Comfor t Systems Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 47 Equipment Selection T able 1b: Selection of Coils other than Above.
Car r ier Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 48 Air Handler Selection Example Figure 1 shows a typical peformance table for a heat pump air handler . Suppose the evaporator temperature required is 50ºF , the capacity required is 35,000 Btuh and the air fl ow required is 1,200 CFM.
T wo-Stage Indoor Split Puron ® Systems 49 Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 GT -PX Split (50YDS) Ser ies General The liquid source heating/cooling split cond.
GT -GS 50 Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 GT -GS Indoor Split (50YCS) Ser ies General The liquid source heating/cooling split con dens ing units shall be ARI.
Single-Stage Outdoor Split R22 Systems 51 Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 GT -S Outdoor Split (38WQS) Ser ies General The liquid source heating/cooling split.
Car r ier Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev .: 08/10/05 52 Accessories & Options Hot W ater Generator (internal) - GT -PX & GT -GS units only An optional heat reclaiming desuperheater coil of vented double-wall copper construction suitable for potable water shall be provided.
.
Carr ier works continually to improve its products. As a result, the design and speci fi cations of each product at the time for order may be changed without notice and may not be as described herein.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Carrier GT-PX c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Carrier GT-PX - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Carrier GT-PX, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Carrier GT-PX va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Carrier GT-PX, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Carrier GT-PX.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Carrier GT-PX. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Carrier GT-PX ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.