38EYA 12 SEER Split-System Heat Pump with Puron® Installation and Start-Up Instructions NOTE: Read the entire instruction manual before starting the installation.
INSTALLATION IMPORTANT: Specifications for this unit in residential new construction market require using the outdoor unit, indoor unit, refrigerant tubing sets, metering device, and filter drier listed in presale literature. There can be no deviation.
Step 5 — Elevate Unit Accumulation of water and ice in base pan may cause equipment damage. Elevate unit per local climate and code requirements to provide clearance above estimated snowfall level and ensure adequate drainage of unit.
Do not leave system open to atmosphere any longer than minimum required for installation. POE oil in compressor is extremely susceptible to moisture absorption. Always keep ends of tubing sealed during installation. If ANY refrigerant tubing is buried, provide a 6 in.
wrench an additional 1/12 turn (15 ft-lb). DO NOT OVER- TIGHTEN. REFRIGERANT TUBING AND FILTER DRIER Installation of filter drier in liquid line is required. Connect vapor tubing to fittings on outdoor unit vapor service valves. Connect liquid tube to filter drier.
1. Pump system down to 28 in. of mercury and allow pump to continue operating for an additional 15 minutes. 2. Close service valves and shut off vacuum pump. 3. Connect a nitrogen cylinder and regulator to system and open until system pressure is 2 psig.
24 VAC HOT R G W/W1 Y/Y2 O/W2 R W2 W3 E RVS COOLING C B S1 S2 W2 CARRIER PROGRAMMABLE THERMOSTAT MODEL HP FA, FB, FX FAN COIL HEAT PUMP G Y1/W2 L R O INDOOR FAN HEAT STAGE 2 COOL/HEAT STAGE 1 NOT USED.
24 VAC HOT R C W2 Y G R C RVS COOLING C W2 OTHER BRAND HP THERMOSTAT FA, FB, FX FAN COIL HEAT PUMP G O E W2 E W3 R Y 24 VAC COM HEAT STAGE 2 COOL/HEAT STAGE 1 INDOOR FAN EMERGENCY HEAT O * * * IF AVAI.
G R Y/Y2 O/W2 CARRIER DUAL FUEL THERMOSTAT MODEL DF SINGLE-STAGE FURNACE HEAT PUMP G Y W C Y R O W2 Y1/W2 C B L S1 S2 R C FURNACE COMPRESSOR FAN 24 VAC HOT 24 VAC COM N/A RVS HEATING RVS SENSING OUTDO.
24 VAC HOT R G W/W1 Y/Y2 O/W2 RVS COOLING C B S1 S2 CARRIER PROGRAMMABLE THERMOSTAT MODEL HP FA, FB, FX FAN COIL WITH SMART HEAT HEAT PUMP Y1/W2 L R C Y G O W2T W3 W2D Y 0 R C O W2 Y INDOOR FAN HEAT S.
24 VAC HOT R C Y G O RVS COOLING W2 OTHER BRAND HP THERMOSTAT FA, FB, FX FAN COIL WITH SMART HEAT HEAT PUMP E R C Y G O W2T W3 W2D Y 0 R C O W2 Y INDOOR FAN EMERGENCY HEAT COOL/HEAT STAGE 1 24 VAC COM.
Back seating service valves are not equipped with Schrader valves. Fully back seat (counter clockwise) valve stem before removing gage port cap. Do not vent refrigerant to atmosphere. Recover during system repair or final unit disposal. Follow these steps to properly start up the system.
• 3 – phase scroll compressors are rotation sensitive. • A flashing LED on phase monitor indicates reverse rotation. (See Fig. 18 and Table 3.) • This will not allow contactor to be energized. • Disconnect power to unit and interchange 2 field wiring leads on unit contactor.
Step 14 — Check Charge UNIT CHARGE Factory charge is shown on unit rating plate. To check charge in cooling mode, refer to Cooling Only Procedure. To check charge in heating mode, refer to Heating Check Chart Procedure.
Step 15 — Final Checks IMPORTANT: Before leaving job, be sure to do the following: 1. Securely fasten all panels and covers. 2. Tighten service valve stem caps to 1/12-turn past finger tight. 3. Leave User ’ s Manual with owner. Explain system operation and periodic maintenance requirements outlined in manual.
PURON ® (R-410A) QUICK REFERENCE GUIDE • Puron ® refrigerant operates at 50-70 percent higher pressures than R-22. Be sure that servicing equipment and replacement components are designed to operate with Puron ® . • Puron ® refrigerant cylinders are rose colored.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Carrier 38EYA c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Carrier 38EYA - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Carrier 38EYA, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Carrier 38EYA va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Carrier 38EYA, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Carrier 38EYA.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Carrier 38EYA. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Carrier 38EYA ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.