Manuel d'utilisation / d'entretien du produit 38AE012 du fabricant Carrier
Aller à la page of 20
Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERA TIONS ...................1 INST ALLA TION ..............................1 - 8 Step 1 — Complete Pre-Installation Checks ....1 Step 2 — Rig and Mount the Unit ..........
LEGEND A— 1 1 ⁄ 4 -in. (32) diameter knockout for 5 ⁄ 8 -in. (16) ODM liquid line connection B— 1 3 ⁄ 4 -in. (44.5) diameter knockout for suction line connections of 1 1 ⁄ 8 in. (28.6) (38AE012), 1 3 ⁄ 8 in. (35) (38AE014,016), 1 5 ⁄ 8 in.
1 3 2 456 7 8 12 9 10 11 LEGEND 1— Low-V oltage Fuse 5— No. 2 Fan 9— Compressor 2— No. 1 Fan 6— T erminal Block 1 (Unit Power) 1 0— Low-Pressure Switch 3— High-Pressure Switch 7— T erminal Block 2 (Control Power) 11 — Hot Gas Bypass Piping Stub ( 3 ⁄ 8 -in.
T able 1A — Physical Data (English, 60 Hz) UNIT 38AE012 38AE014 38AE016 38AKS024 OPERA TING WEIGHT (lb) 732 779 789 900 REFRIGERANT* R-22 COMPRESSOR Reciprocating, Semi-Hermetic Speed (Rpm) 1750 No. Cylinders 666 4 Model No. 06DD824 06DD328 06DD537 06E4250 Oil (pt) 10 10 10 15.
T able 1C — Physical Data (English, 50 Hz) UNIT 38AE012 38AE014 38AE016 38AKS024 OPERA TING WEIGHT (lb) 732 779 789 900 REFRIGERANT* R-22 COMPRESSOR Reciprocating, Semi-Hermetic Speed (Rpm) 1460 No. Cylinders 666 4 Model No. 06DD824 06DD328 06DD537 06E4250 Oil (pt) 10 10 10 15.
T a b l e2—W eight Distribution UNIT WEIGHT — lb (kg) T otal Operating Support Point AB C D 38AE012 732 (333) 142 (65) 138 (63) 225 (102) 227(103) 38AE014 779 (354) 143 (65) 140 (64) 247 (1 12) 24.
INST ALL FIL TER DRIER(S) AND MOISTURE INDICA- TOR(S) — Every unit should have a filter drier and liquid- moisture indicator (sight glass). In some applications, depending on space and convenience requirements, it may be desirable to install 2 filter driers and sight glasses.
T able 5A — Electrical Data (3 Ph/60 Hz) UNIT UNIT COMPR F AN MOTORS (Single Phase) Model V olts MCA ICF MOCP (Fuse) RLA LRA T otal Fans FLA (ea) Fan No. kW Nameplate Supplied* Min Max 12 38AE012 501 208-230 187 253 62.5 178 100 43.6 170 2 4.3 3.7 1.
PRE-ST ART -UP Evacuate and Dehydrate the entire refrigerant sys- tem by either of the methods described in Carrier Standard Service T echniques Manual, Chapter 1. Leak T est the entire refrigerant system by the pres- sure method described in Carrier Standard Service T ech- niques Manual, Chapter 1.
Fig. 9 — 38AE012 and 38AKS024 Charging Chart 10.
Fig. 10 — 38AE014 Charging Chart 11.
Fig. 1 1 — 38AE016 Charging Chart 12.
Check Operation — V erify operation of all safety con- trols. Replace all service panels. Be sur e that contr ol panel cover is closed tightly . OPERA TING SEQUENCE Cooling — When the first stage (TC1) of the cooling ther- mostat closes, the timer starts.
Outdoor Fans — Each fan is supported by a formed- wire mount bolted to the fan deck and covered with a wire guard. The exposed end of the motor shaft is covered with a rubber boot.
TROUBLESHOOTING PROBLEM SOLUTION COMPRESSOR DOES NOT RUN Contactor Open 1. Power off. 1. Restore power . 2. Fuses blown in field power circuit. 2. After finding cause and correcting, replace with correct size fuse. 3. No control power . 3. Check secondary fuse(s); replace with correct type and size.
TROUBLESHOOTING (cont) PROBLEM SOLUTION COMPRESSOR CYCLES ON LOW-PRESSURE SWITCH (cont) Airflow Restricted 1. Coil iced up. 1. Check refrigerant charge. 2. Coil dirty . 2. Clean coil fins. 3. Air filters dirty . 3. Clean or replace filters. 4. Dampers closed.
.
P ACKAGED SER VICE TRAINING Our packaged service training programs provide an excellent way to increase your knowledge of the equipment discussed in this manual. Product programs cover: • Unit Familiarization • Maintenance • Installation Overview • Operating Sequence A large selection of product, theory , and skills programs is available.
ST ART -UP CHECKLIST A. Preliminary Information OUTDOOR: MODEL NO. SERIAL NO. INDOOR: AIR HANDLER MANUF ACTURER MODEL NO. SERIAL NO. ADDITIONAL ACCESSORIES B. Pre-Start-Up OUTDOOR UNIT IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE: WILL THIS DAMAGE PREVENT UNIT ST ART -UP? (Y/N) CHECK POWER SUPPL Y .
C. Start-Up CHECK EV APORA TOR F AN SPEED AND RECORD. CHECK CONDENSER F AN SPEED AND RECORD. AFTER A T LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS: OIL PRESSURE SUCTION PRESSURE S.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Carrier 38AE012 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Carrier 38AE012 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Carrier 38AE012, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Carrier 38AE012 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Carrier 38AE012, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Carrier 38AE012.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Carrier 38AE012. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Carrier 38AE012 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.