IMPORT ANT — READ BEFORE INST ALLING 1. Read and become familiar with these installation in- structions before installing this unit (Fig. 1). Retain these instructions for future maintenance and repair . 2. Be sure the installation conforms to all applicable local and national codes.
UNIT 564A/764A ELECTRICAL CHARACTERISTICS UNIT WEIGHT CENTER OF GRA VITY mm [in.] Lb Kg X Y Z 024 208/230-1-60 222 101 355.6 [14.00] 508.0 [20.00] 241.3 [9.50] 030 208/230-1-60 236 107 355.6 [14.00] 508.0 [20.00] 241.3 [9.50] 036 208/230-1-60, 208/230-3-60 250 1 14 355.
UNIT 564A/764A ELECTRICAL CHARACTERISTICS UNIT WEIGHT CENTER OF GRA VITY mm [in.] Lb Kg X Y Z 042 208/230-1-60, 208/230-3-60 297 135 355.6 [14.00] 508.0 [20.00] 304.8 [12.00] 048 208/230-1-60, 208/230-3-60 310 1 14 355.6 [14.00] 508.0 [20.00] 304.8 [12.
UNIT 564A/764A ELECTRICAL CHARACTERISTICS UNIT WEIGHT CENTER OF GRA VITY mm [in.] Lb Kg X Y Z 060 230-1-60, 208/230-3-60, 460-3-60 350 159 355.6 [14.00] 508.0 [20.00] 355.6 [14.00] LEGEND NEC — National Electrical Code REQUIRED CLEARANCES TO COMBUSTIBLE MA TERIAL, mm [in.
I. LOCA TE THE UNIT A. Clearance Provide suf f icient space for condenser airflow clearance, wir- ing, and servicing unit. See Fig. 2-4. Locate unit where supply- and return-air ducts can be conveniently brought out to unit duct connections.
T able 1 — Physical Data UNIT 564A AND 764A 024 030 036 042 048 060 OPERA TING WEIGHT (lb) 222 236 250 297 310 350 COMPRESSOR TYPE Reciprocating REFRIGERANT R-22 Charge (lb) 2.8 3.9 4.7 4.4 6.1 7.5 REFRIGERANT METERING DEVICE Acutrol™ System CONDENSER COIL Copper T ubes, Aluminum Plate Fins Rows.
Install Flanges for Ductwork Connections (564A/764A060 only) The size 060 units are shipped with flanges which must be field-installed on the unit. T o install unit flanges: 1. Five pieces of flange are shipped on the return air open- ing of the unit.
C. Converting Horizontal Discharge Units to Downflow (V ertical) Discharge W ARNING: Before performing service or mainte- nance operations on system, turn of f main power to unit. T urn off accessory heater power switch if applicable. Elec- trical shock can cause personal injury .
Route thermostat wires through grommet providing a drip loop at the panel. Connect low-voltage leads to the thermo- stat as shown in Fig. 16. The unit transformer supplies 24-v power for complete system including accessory electrical heater . T ransformer is factory wired for 230-v operation.
T able 2 — Electrical Data UNIT 564A/764A NOMINAL VOL T AGE (V -Ph-Hz) VOL T AGE RANGE COMPRESSOR OFM IFM ELECTRIC HEA T POWER SUPPL Y DISCONNECT SIZE Min Max RLA LRA FLA FLA Nominal kW* FLA MCA MOCP FLA LRA 024 208/230-1-60 187 254 10.9 61.0 0.9 2.
Special Procedures for 208-V Operation W ARNING: Make sure that the power supply to the unit is switched OFF before making any wiring changes. Electrical shock can cause personal injury or death. 1. Disconnect the orange transformer-primary lead from the contactor .
Proceed as follows to inspect and prepare the unit for initial start-up: 1. Remove all access panels. 2. Read and follow instructions on all W ARNING, CAU- TION, and INFORMA TION labels attached to, or shipped with, unit. 3. Make the following inspections: a.
C. Unit Controls Compressor High-Pressure Relief V alve — V alve is located in compressor . Relief valve opens at a pressure dif ferential of approximately 450 psi between suction (low side) and discharge (high side) to allow pressure equalization.
CARE AND MAINTENANCE NOTE: The following steps should be performed by a quali- fied service person. W ARNING: Before installing or servicing unit, turn of f main power to system to avoid shock hazard or in- jury from rotating parts. There may be more than one disconnect switch.
SERVICE NOTE: The following steps should be performed by a quali- fied service person. W ARNING: Before installing or servicing unit, turn of f main power to system to avoid shock hazard or in- jury from rotating parts. There may be more than one disconnect switch.
IV . ELECTRICAL CONTROLS AND WIRING Inspect and check the electrical controls and wiring an- nually . Be sure to turn of f all electrical power to the unit. Remove the control, evaporator fan, and compressor compart- ment access panels to locate all the electrical controls and wiring.
Fig. 19 — Cooling Charging Chart — 564A/764A024 Fig. 20 — Cooling Charging Chart 564A/764A030 Fig. 21 — Cooling Charging Chart — 564A/764A036 Fig.
Fig. 23 — Cooling Charging Chart — 564A/764A048 Fig. 24 — Cooling Charging Chart — 564A/764A060 —18—.
COOLING TROUBLESHOOTING CHART SYMPTOM CAUSE REMEDY Compressor and con- denser fan will not start. Power failure Call power company . Fuse blown or circuit breaker tripped Replace fuse or reset circuit breaker . Defective thermostat, contactor , transformer, or control relay Replace component.
.
.
P ACKAGED SERVICE TRAINING Our packaged service training programs provide an excellent way to increase your knowledge of the equipment discussed in this manual. Product programs cover: • Unit Familiarization • Installation Overview • Maintenance • Operating Sequence A large selection of product, theory , and skills programs is available.
.
ST ART -UP CHECKLIST (Remove and Store in Job File) I. PRELIMINARY INFORMA TION MODEL NO.: DA TE: SERIAL NO.: TECHNICIAN: II. PRE-ST ART -UP (insert checkmark in box as each item is completed) M VERIF.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Bryant 764A c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Bryant 764A - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Bryant 764A, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Bryant 764A va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Bryant 764A, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Bryant 764A.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Bryant 764A. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Bryant 764A ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.