Manuel d'utilisation / d'entretien du produit 575A du fabricant Bryant
Aller à la page of 16
IMPORT ANT — READ BEFORE INST ALLING 1. Read and become familiar with these installation in- structions before installing this unit. 2. Be sure the installation conforms to all applicable local and national codes. 3. These instructions contain important information for the proper maintenance and repair of this equipment.
UNIT 575A UNIT W/ ALUMINUM-FIN COIL UNIT W/ COPPER-FIN COIL WEIGHT (WITH ALUMINUM-FIN COIL) WEIGHT (WITH COPPER-FIN COIL) Std Unit Corner W Corner X Corner Y Corner Z Std Unit Corner W Corner X Corner Y Corner Z Dim. A Dim. B Dim. A Dim. B Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg 090 1 8 -8 9 [508.
T able 1 — Physical Data UNIT 575A 090 OPERA TING WEIGHT (lb) Aluminum Coils (Standard) 540 Copper Coils (Optional) 608 RIGGING WEIGHT (lb) Aluminum Coils (Standard) 590 Copper Coils (Optional) 658 REFRIGERANT* R-22 COMPRESSOR Reciprocating, Semi-Hermetic Quantity .
III. COMPLETE REFRIGERANT PIPING CONNECTIONS Suction connection is sweat with plastic cap; liquid connec- tion is sweat with plastic cap. Refer to T able 2 for the proper line sizes. Follow standard piping practices. T able 2 — Refrigerant Piping Sizes LINEAR LENGTH OF PIPING — ft UNIT 575A 0-25 25-50 50-75 75-100 Line Size (in.
LEGEND NEC — National Electrical Code TXV — Thermostatic Expansion V alve *Accessory item. †Field supplied. NOTES: 1. All piping must follow standard refrigerant piping techniques. 2. All wiring must comply with the applicable local and national codes.
IV . MAKE ELECTRICAL CONNECTIONS W ARNING: Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur .
T able 4 — Electrical Data UNIT 575A NOMINAL VOL T AGE (V -Ph-Hz) VOL T AGE RANGE COMPRESSOR OFM POWER SUPPL Y MINIMUM DISCONNECT Min Max RLA LRA FLA MCA MAX FUSE OR HACR BRKR AMPS FLA LRA 090 208/230-3-60 187 254 31.5 160 3.1 42.5 50 45 177 460-3-60 414 508 15.
C. Field Control Wiring Install an approved accessory thermostat assembly accord- ing to installation instructions included with the accessory . Locate thermostat assembly on a solid wall in the condi- tioned space to sense average temperature in accordance with thermostat installation instructions.
B. Oil Charging Allow unit to run for about 20 minutes. Stop unit and check compressor oil level. Add oil only if necessary to bring oil into view in sight glass. See T able 1 for oil charge. Use only ap- proved compressor oil as follows: Suniso 3GS and WF32-150 Do not reuse drained oil or use any oil that has been exposed to atmosphere.
C. Defrost Defrost board (DB) is a time and temperature control, which includes a field-selectable time period between checks for frost (30, 50, and 90 minutes). Electronic timer and defrost cycle start only when contactor is energized and defrost thermo- stat (DFT) is closed (below 28 F).
SERVICE CAUTION: When servicing unit, shut of f all electri- cal power to unit to avoid shock hazard or injury from rotating parts. I. CLEANING Inspect unit interior at the beginning of each cooling season and as operating conditions require. A. Outdoor Coil Inspect coil monthly .
II. LUBRICA TION A. Compressors Compressor has its own oil supply . Loss of oil due to a leak in the system should be the only reason for adding oil after the system has been in operation. See Start-Up, Oil Charging section. B. Fan Motor Bearings Fan motor bearings are permanently lubricated.
TROUBLESHOOTING CHART , HEA TING CYCLE LEGEND N.C. — Normally Closed —13—.
TROUBLESHOOTING CHART , COOLING CYCLE LEGEND TXV — Thermostatic Expansion V alve Copyright 1995 Carrier Corporation CA TALOG NO. BDP-3357-502.
ST ART -UP CHECKLIST I. PRELIMINAR Y INFORMA TION OUTDOOR: MODEL NO. INDOOR: MODEL NO. SERIAL NO. SERIAL NO. ADDITIONAL ACCESSORIES B. Pre-Start-Up OUTDOOR UNIT IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE: WILL THIS DAMAGE PREVENT UNIT ST ART -UP? (Y/N) CHECK POWER SUPPL Y .
C. Start-Up CHECK INDOOR-F AN SPEED AND RECORD. CHECK OUTDOOR-F AN SPEED AND RECORD. AFTER A T LEAST 15 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS: COOLING HEA TING OIL PRESSURE SUCTION P.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Bryant 575A c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Bryant 575A - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Bryant 575A, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Bryant 575A va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Bryant 575A, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Bryant 575A.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Bryant 575A. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Bryant 575A ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.