IMPORT ANT —READ BEFORE INST ALLING 1. Read and become familiar with these installation instructions before installing this unit (Fig. 1). 2. Be sure the installation conforms to all applicable local and national codes. 3. These instructions contain important information for the proper maintenance and repair of this equipment.
NOTE: If vibration isolators are required for a particular in- stallation, use corner weight information in Fig. 2 to make proper selection. I. LOCA TE THE UNIT A. Clearance Maintain clearance around and above unit to provide mini- mum distance from combustible materials, proper airflow , and service access.
T able 1A — Specifications (English) UNIT 569C072 569C090 569C120 576B090 576B102 576B120 NOMINAL CAP ACITY (T ons) 67 1 ⁄ 2 10 7 1 ⁄ 2 8 1 ⁄ 2 10 OPERA TING WEIGHT (lb) Aluminum Coils (Stand.
T able 1B — Specifications (SI) UNIT 569C072 569C090 569C120 576B090 576B102 576B120 NOMINAL CAP ACITY (kW) 21 26 35 26 29.9 35 OPERA TING WEIGHT (kg) Aluminum Coils (Standard) 154 168 179 231 256 .
UNIT DIM. A DIM. B DIM. C DIM. D DIM. E DIM. F 569C072 1 8 -6 1 ⁄ 2 9 1 8 -2 3 ⁄ 4 9 —1 8 -2 1 ⁄ 4 9 1 8 -4 5 ⁄ 16 9 2 8 -9 5 ⁄ 16 9 [470.0] [375.0] — [362] [415] [846.5] 569C090 1 8 -8 9 1 8 -6 1 ⁄ 2 9 —1 8 -3 9 2 8 - 5 ⁄ 16 9 3 8 -5 7 ⁄ 16 9 [508.
B. Filter Drier and Moisture Indicator The filter drier is factory installed. Moisture indicator is a field-installed accessory and should be installed just after liq- uid line shutof f valve. Do not use a receiver . A receiver is not supplied with the unit and should not be used.
All units except 208/230-v units are factory wired for the volt- age shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power supply , the transformer must be rewired by moving the black wire from the 230-v orange wire on the transformer and connecting it to the 200-v red wire from the transformer .
T able 4 — Electrical Data UNIT NOMINAL VOL T AGE (V -Ph-Hz) VOL T AGE RANGE COMPRESSOR OFM POWER SUPPL Y Min Max RLA LRA FLA MCA MOCP 569C072 208/230-3-60 187 254 21.8 142 1.9 25.6 35 460-3-60 414 508 9.6 72 1.0 12.9 15 575-3-60 518 632 7.6 58 1.9 1 1.
T able 5 — American/European Wire Conversions AMERICAN EUROPEAN Industry Standard Size American Conversion (mm 2 ) Industry Standard Size (mm 2 ) 18 A WG 0.82 1.0 16 A WG 1.30 1.5 14 A WG 2.08 2.5 12 A WG 3.30 4.0 10 A WG 5.25 6.0 8A W G 6.36 10.0 6A W G 13.
ST ART -UP I. ST ART -UP AND ADJUSTMENTS CAUTION: Complete the required procedures given in the Pre-Start-Up section before starting the unit. Do not jumper any safety devices when operating the unit. Do not operate the compressor when the outdoor tem- perature is below 25 F ( 2 4 C) (unless accessory low am- bient kit is installed).
SERVICE W ARNING: When servicing unit, shut of f all electri- cal power to unit to avoid shock hazard or injury from rotating parts. I. CLEANING Inspect unit interior at the beginning of each cooling season and as operating conditions require. A. Condenser Coil Inspect coil monthly .
IV . CAP ACITY CONTROL (576B120 Only) A suction pressure-actuated unloader controls 2 cylinders and provides capacity control. Unloaders are factory set (see T able 1A or 1B), but may be field adjusted: A. Control Set Point The control set point (cylinder load point) is adjustable from 0 to 85 psig (586 kPa).
Fig. 14 — Cooling Charging Chart — 569C072 Fig. 15 — Cooling Charging Chart — 569C090,120 and 576B090,102,120 —13—.
TROUBLESHOOTING GUIDE SYMPTOM CAUSE REMEDY Compressor does not run — Contactor open Power off. Restore power . Fuses blown. Replace with correct fuses after finding cause and correcting. T ransformer open/shorted. Replace transformer if primary windings are receiving power and no output.
LEGEND FOR FIG. 16 AND 17 C— Contactor , Compressor CAP — Capacitor CB — Circuit Breaker CH — Crankcase Heater CLO — Compressor Lockout COMP — Compressor Motor COTP — Compressor T empera.
.
.
Copyright 1999 Bryant Heating & Cooling Systems CA TALOG NO. 5356-902.
ST ART -UP CHECKLIST I. PRELIMINAR Y INFORMA TION OUTDOOR: MODEL NO. SERIAL NO. INDOOR: AIR HANDLER MANUF ACTURER MODEL NO. SERIAL NO. ADDITIONAL ACCESSORIES II. PRE-ST ART -UP OUTDOOR UNIT IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE: WILL THIS DAMAGE PREVENT UNIT ST ART -UP? (Y/N) CHECK POWER SUPPL Y .
III. ST ART -UP CHECK EV APORA TOR-F AN SPEED AND RECORD. CHECK CONDENSER-F AN SPEED AND RECORD. AFTER A T LEAST 15 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS: OIL PRESSURE (576B only) SU.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Bryant 569C c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Bryant 569C - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Bryant 569C, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Bryant 569C va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Bryant 569C, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Bryant 569C.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Bryant 569C. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Bryant 569C ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.