Manuel d'utilisation / d'entretien du produit 561C du fabricant Bryant
Aller à la page of 28
Form No. PDS 561C.18.6 ELECTRIC AIR CONDITIONER 561C (60 Hz) Sizes 018 thru 060 Model 561C Energy-Efficient Air Conditioners incor porate inno- vativ e technology to provide reliab le summer cooling perfor- mance. Built into these units are the f eatures most desired by homeowners toda y including SEER ratings of up to 11.
—2— DIMENSIONS—561C A97017 AIR IN NOTES: 1. Allow 30 in. clearance to service side of unit, 48 in. above unit, 6 in. on one side, 12 in. on remaining side, and 24 in. between units for proper airflow. 2. Minimum outdoor operating ambient in cooling mode is 55 ° F, max.
—3— CHECK-FLO-RA TER® PIST ON CHART * Piston listed is f or any approv ed coil non-capillar y tube combination. Piston is shipped with outdoor unit and must be installed in an appro ved indoor coil. RECOMMENDED TUBE DIAMETERS * For tube sets betw een 50 and 175 ft, consult Residential Split System Long-Line Application Guideline.
—4— SPECIFICA TIONS See notes on page 7. UNIT SIZE-SERIES 561C018-A, D 561C024-A, D 561C030-A, D 561C030-A Operating W eight (Lb) 113/115 115/117 124/133 124 ELECTRICAL Unit V olts—Hertz—Phase 208-230—60—1 208/230—60—3 Operating V oltage Range* 197—253 187—253 Compressor— Rated Load Amps 9.
—5— SPECIFICA TIONS Continued See notes on page 7. UNIT SIZE-SERIES 561C036-A, B, E 561C036-B, D 561C036-B 561C042-A, B 561C042-B, C 561C042-B Operating W eight (Lb) 129/138/138 129/133 133 138/14.
—6— SPECIFICA TIONS Continued See notes on page 7. UNIT SIZE-SERIES 561C048-A, B 561C048-B, C 561C060-A, B 561C060-B, E Operating W eight (Lb) 192/198 233/218 ELECTRICAL Unit V olts—Hertz—Phas.
—7— * P er missible limits of the v oltage range at which unit will operate satisf actor ily . Oper ation outside these limits may result in unit f ailure. † If wire is applied at ambient greater than 30°C (86°F), consult T able 310-16 of the NEC (ANSI/NFP A 70).
—8— A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) Continued 9. High-Pressure Switch Auto reset SPST s witch activated by refrigerant pressure on high side of refrigerant circuit. Cycles compressor off if refrigerant pressure rises to 400 ± 10 psig and resets at 298 ± 20 psig.
—9— COMBINA TION RA TINGS See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST AND ARD RA TING BR Y ANT GAS FURNA CE OR A CCESSOR Y TDR† A CCESSOR Y TXV‡ EERA 018-A, D CC5A/CD5AA018* 17,200 NONE — 10.
—10— COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST AND ARD RA TING BR Y ANT GAS FURNA CE OR A CCESSOR Y TDR† A CCESSOR Y TXV‡ EERA 030-A, D CD5A/CD5AA030* 28,000 NONE 10.
—11— COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST AND ARD RA TING BR Y ANT GAS FURNA CE OR A CCESSOR Y TDR† A CCESSOR Y TXV‡ EERA 036-A, B, D , E CK3BA036 33,800 NONE 10.
—12— COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST AND ARD RA TING BR Y ANT GAS FURNA CE OR A CCESSOR Y TDR† A CCESSOR Y TXV‡ EERA 036-A, B, D , E CK5A/CK5BA042 33,400 TDR 10.
—13— COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST AND ARD RA TING BR Y ANT GAS FURNA CE OR A CCESSOR Y TDR† A CCESSOR Y TXV‡ EERA 042-A, B, C COILS + 355MA V060100 V ARIABLE-SPEED FURNACE CC5A/CD5AA042 40,000 TDR 10.
—14— COMBINA TION RA TINGS Continued * T ested Combination. † In most cases, only 1 method should be used to achie v e TDR function. Using more than 1 method in a system ma y cause degradation in performance. Use either the accessory Time-Dela y Relay KAA TD0101TDR or a furnace equipped with TDR.
—15— DET AILED COOLING CAP A CITIES* See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capacity MBtuh.
—16— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capaci.
—17— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capaci.
—18— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capaci.
—19— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capaci.
—20— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capaci.
—21— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capaci.
—22— DETAILED COOLING CAPACITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capacity .
—23— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capaci.
—24— DET AILED COOLING CAP A CITIES* Continued * Detailed cooling capacities are based on indoor and outdoor unit at the same ele vation per ARI standard 210/240-94. If additional tubing length and/or indoor unit is located abov e outdoor unit, a slight variation in capacity ma y occur .
—25— CONDENSER ONL Y RA TINGS* See notes on page 26. SST °F CONDENSER ENTERING AIR TEMPERA TURES °F 55 65 75 85 95 105 115 125 561C018-A, D 30 TCG 17.6 16.2 14.7 13.4 12.0 10.7 9.52 8.35 KW 1.37 1.49 1.58 1.66 1.73 1.77 1.80 1.82 SDT 75.6 86.1 96.
—26— CONDENSER ONL Y RA TINGS* Continued * ARI listing applies only to systems shown in Ratings and P erformance table . KW — T otal Po wer (Kw) SDT — Saturated T emperature Leaving Compressor.
—27— SYSTEM DESIGN 1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure av ailable is less than 0.01-in. wc. 2. Minimum outdoor operating air temperature without lo w-ambient operation accessor y is 55°F (12.
—2 8— SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels PDS 561C.18.5 © 1999 Bryant Heating & Cooling Systems, 7310 W. Morris St., Indpls., IN 46231 PRINTED IN U.S.A. Catalog No.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Bryant 561C c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Bryant 561C - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Bryant 561C, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Bryant 561C va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Bryant 561C, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Bryant 561C.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Bryant 561C. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Bryant 561C ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.