Manuel d'utilisation / d'entretien du produit U2TW65T*FRN du fabricant Bradford-White Corp
Aller à la page of 52
Save this manual for future reference Manual 238-48385-00A SERVICE MANUAL Troubleshooting Guide and Instructions for Service (To be performed ONLY by qua lified servi ce providers) Models Covered by T.
Page 2 Table of Contents Section Page Introduction ______________________________________________5 How to Use this Manual _____________________________________6 Tools Required for Service ____________.
WARNING If the information in these instructions is not followed exactly, a fire or ex- plosion may result causing property damage, personal injury, or death.
Page 4 WARNING Water heaters are heat producing appliances. To avoid damage or injury, do not store materials against the water heater or any of its components. Use proper care to avoid unnecessary contact, especially by children, with the water heater and its components.
Page 5 The Bradford White ECO-DEFENDER Safety System ® The Bradford White ECO-DEFENDER Safety System was designed to resist the ignition of flammable vapors that can occur outside of the water heater and produce Ultra Low NOx emissions.
Page 6 diagnostic LED will flash a code to positively identify an operational issue. This service manual is designed to facilitate problem diagnosis and enhance service efficiency. To further promote quicker service tim es the new gas valve can be removed and replaced with- out draining the water heater.
Page 7 Contact the Bradford White technical support group immediately if diagnosis cannot be m ade using the methods described in this service manual. T ools Requir ed for Service Manometer: A liquid “U” tube type or a digital (magna-helic) typ e can be used.
Page 8 P ower Supply Dedicated 115VAC, 60 Hz, 15A. G as Supply Pipe Minimum 1/2” NPT (schedule 40 bl ack iron pipe recommended). A pproved Gas Type Natural Gas. G as Pressure 6.0” W.C. minimum, 11.0” W.C. maximum. Venting System Power vent through the wall or vertical through the roof.
Page 9 Vent Tables Venting Specificat ions for: 40 Gallon—40,000 BTU/hr. 50 Gallon—40,000 BTU/hr. 6 0 Gallon—42,000 BTU/hr. 2” Diameter (5.1 cm) PVC Vent Connector Lengths Terminating # of Elbows Maximum Straight L ength ft (m) Minimum Straight L ength ft (m) T hrough the Wall 1 45 (13.
Page 10 Vent Tables Venting Specificat ions for: 48 Gallon—60,000 BTU/hr. 65 Gallon—60,000 BTU/hr. 3” Diameter (7.6 cm) PVC Vent Connector Lengths Terminating # of Elbows Maximum Straight Length ft (m) Minimum Straight Length ft (m) Through the Wall 1 55 (16.
Page 11 Specifications Wiring Diagram Control Timings Ignition State Timing Pre-purge 15 s econds Trial for Ignition 90 seconds Flame Stabilization Period 3 seconds Inter-purge 15 s econds F lame Failure Response Time 1.
Page 12 Power Up Sequence 1. Start-up: Upon power up, the gas control runs a safe start check with a typical delay of 5 seconds. 2. Flammable Vapor Verification: The gas control verifies that the Flamma- ble Vapor Sensor is in the proper operating range prior to energizing any components.
Page 13 Normal Heating Sequence (cont’d) 7. Main Burner Ignition: After pilot flame is sensed, the gas control acti- vates the main valve for main burner ignition. The gas control will ig- nore flame and pressure switch signals for 3 seconds to allow for the main burner to stabilize.
Page 14 Abnormal Operation (cont’d) B) If the resistance is below 3000 ohms: The gas control immediately turns off all outputs and proceeds to flash 8 times then 1 time with a three second pause. The error self clears if the resistance returns to nor- mal range for at least 15 seconds.
Page 15 Abnormal Operation (cont’d) B) Pressure switch or blower temperature switch failed to close: The gas control runs the blower for 30 seconds waiting for the pressure switch and/or the blower temperature switch to close.
Page 16 Abnormal Operation (cont’d) 5. Flame Sensing Fault: A) Flame Lost During Run: The gas control turns off the pilot and main valves and runs the blower for 15 seconds (inter-purge) The gas control increments the recycle count, if the recycle count has not reached its limit (4), another trial for ignition begins.
Page 17 L ED S ta tus C ontr ol S ta tus P r oba bl e C a us e S e rv ic e P ro c e d ur e No ne ( L E D not on or fla s h in g) N o e le ct rica l p o w e r C o n t r o l p o w e r s w it ch in " O F F " posi t i on. Su pp l y vo l t a g e int e rru p te d .
Page 18 L ED S ta tus C ontr o l S ta tus P r oba bl e C a use S er v i c e P ro c e d ur e Six fla s h e s , one f l a s h, thr e e s e c o nd paus e ( S o f t Lo c kou t) Fa ile d t o lig h t p ilo t , sy stem r eset s af t er (5 ) m i n u t e s 1. Unstabl e pi l ot 2.
Page 19 L ED Status Control Status Probable Cause Service Procedure Eight flashes, t hree flashes, three second pause Thermal well sensor damaged or un- plugged or gas con- t rol electronics fault detected 1. Damage to thermal well wires 2. Thermal well sensor resistance out of range 3.
Page 20 Burner Inspection At periodic intervals (every 6 months), a visual inspection should be made of the pilot and main burner for proper operation and to assure no debris is accumulating. The pilot flame should be stable. Some causes for an unsta- ble pilot flame are: a) Gas pressure is out of specification.
Page 21 Burner Cleaning Procedure (cont’d) Step 5. Remove the (4) 1/4” hex dri ve screws holding the right side inner door in place. Step 6. Remove the (3) 1/4” hex drive screws holding the left side burner door in place.
Page 22 Burner Cleaning Procedure (cont’d) Step 1 1. Thoroughly inspect burner screen and burner venturi and remove any loose debris accumu- lation. Inspect burner screen for any openings larger than the normal screen openings.
Page 23 Pilot Inspection, Testing and Replacement (cont’d) Step 2. Unplug the water heater from the wall outlet. Step 3. Turn off the gas supply to the water heater. Step 4. Remove the outer door. Step 5. Remove the (4) 1/4” hex drive screws holding the right side inner door in place.
Page 24 Pilot Inspection, Testing and Replacement (cont’d) Step 8. Remove the burner assembly from the com- bustion chamber. Step 9. Remove the pilot assembly from the main feedline using a 1/4" nut driver. Step 10. Visually inspect the spark igniter/flame sense wire for damage.
Page 25 Pilot Inspection, Testing and Replacement (cont’d) Step 15. Inspect the pilot tubing and pilot orifice for blockages: a) Remove ferrule nut from the bottom of the pilot assembly using a 7/16" wrench. b) Remove the pilot tube and pilot orifice.
Page 26 Pressure Switch Testing (cont’d) Pressure Switch Testing Pressure switch wire leads W ith steps 1,2 & 3 complete, discon- nect wire leads from pressure switch. Use a multi-meter set to the ohms setting. With blower off, check across the pres- sure switch termi- nals.
Page 27 Pressure Switch Replacement Step 1. Move the gas control power switch to the “OFF” p osition. Step 2 . Remove the three screws (Phillips screw driver) from the control access cover on the blower as- sembly and remove cover. Step 3 . Carefully remove pressure switch from blower housing.
Page 28 Step 5 . Disconnect yellow wires from the pr es- sure switch. Step 6. Reconnect wires from step 5 to new pressure switch. Step 7. Reconnect tubing to new pressure switch. Step 8. Carefully position pressure switch into blower housing. Step 9. Position gas control power switch to the “ON” postion and verify proper heater operation.
Page 29 Blower Testing (cont’d) Does blower energize within 2 minutes? Disconnect pr es- sure switch t ub- ing from blower (see photo 3). Connect manome- ter to pressure tap of blower (see photo 3). Disconnect v ent system from top of blower and remove vent adapter (see photo 5).
Page 30 Blower Removal Step 1. Move the gas control power switch to the “OFF” position. Step 2. Unplug the water heater from the wall out- let. S t e p 3 . Disconnect vent system from exhaust adapter on top of blower. Step 4. Remove exhaust adapter from blower (blade screw driver) and retain for use on new blower.
Page 31 Blower Installation (cont’d) Step 11. Secure blower in place using mounting screws from step 7. Step 12. Reinstall exhaust adapter from step 4. Step 13. Reinstall dilution air clip from step 5. Step 14. Reconnect vent system to exhaust adapter.
Page 32 Blower Temperature Switch Testing (cont’d) S witch Setting Opens on rise @ approximately 165 o F A uto resets on fall @ approximately 160 o F Cool switch to below 160 o F Reconnect wire leads and ob- serve heater operation. Do exhaust gas temperatures rise to or above 170 o F with vent connected? Replace switch (see page 33).
Page 33 Blower Temperature Switch Replacement Step 1. Move the gas control power switch to the “OFF” p osition. Step 2 . Remove the three screws (Phillips screw driver) from the control access cover on the blower as- sembly and remove cover. Step 3.
Page 34 Thermal Well Testing Follow the procedure, below, if the water heater gas control has gone into a ECO lock- out (4 flash, 3 second pause). Reset the gas control by rotating the setpoint knob to the minimum setting for at least 6 seconds before returning to the desired water tem- perature setting.
Page 35 Thermal Well Testing (cont’d) Determine the correct resistance values using the Determine the Water Temperature Inside the Tank procedure on page 23.
Page 36 Sensor Resistance at Various Temperatures Gas Control & Thermal Well Removal From Water Heater Step 1. Move the gas control power switch to the “OFF” po- sition. Step 2. Unplug the water heater from the wall outlet. Step 3. Drain the water heater to a point below the gas control level.
Page 37 Gas Control & Thermal Well Removal From Water Heater (cont’d) Step 4 . Disconnect the pilot tube using a 7/16” wrench and the main burner feedline with a 3/4” wrench from the gas control. Step 5. Disconnect the wire harnesses and spark igniter/ flame sense wire from the gas control.
Page 38 Gas Control Removal From Thermal Well (cont’d) Step 3. Turn off the gas supply to the water heater and disconnect the gas piping from the gas control. Step 4 . Disconnect the pilot tube using a 7/16” wrench and the main burner feedline with a 3/4” wrench from the gas control.
Page 39 Gas Control Assembly to the Thermal Well (cont’d) Step 2. Route the wire leads back into relief opening. Step 3. Align the slots located on the thermal well flange with the tabs located on the back of the gas control. Step 4. Carefully push the gas control back onto the thermal well flange as far as possible towards the water heater.
Page 40 Gas Control Assembly to the Thermal Well (cont’d) Step 8. To resume operation, follow the instructions located on the water heater lighting instruction label. Or, use the lighting instructions located in the water heater installation and operating manual.
Page 41 115 VAC Circuit Trace WARNING 115 volt potential exposure. Use caution making voltage checks to avoid personal injury. LED status: N one, control LED not on or flashing. LED status: S hort flash once every four seconds. LED status: “ Heartbeat”, alternates bright/dim.
Page 42 Safety Circuit Voltage Trace Note: This procedure assumes a cold tank. Step 1. Remove three screws (Phillips screw driver) from control access cover on blower and remove cover. Safety Circuit Voltage Trace WARNING 115 volt potential exposure. Use caution making voltage checks to avoid personal injury.
Page 43 Remove the Blower to Gain Access to the Flue Baffle Step 1 . Move the gas control p o w e r switch to the “OFF” position. S t e p 2 . Unplug the water h e a t e r from the wall outlet. Step 3 . Disconnect the vent system from the exhaust adapter on top of blower.
Page 44 water heater. Remove the Blower to Gain Access to the Flue Baffle (cont’d) Step 8. Inspect the baffle for deterioration and missing restrictors. Clean any scale or debris build-up. Replace with a new baffle, as necessary. Step 9. Reinstall the baffle into the flue.
Page 45 be free of cracks and any blockage. Hydro-jet slots should be open and free of any blockage. Any damage, such as cracks, restriction due to deformation, or uninten- tional holes are not field repairable and the inlet nipple/diptube must be replaced.
Page 46 Step 8. To resume operation, follow the instructions located on the water heater lighting instruction label. Or, use the lighting instructions located in the water heater installation and operating manual. Inner Door Removal Procedure Step 1. Move the gas control power switch to the “OFF” po- sition.
Page 47 Step 6 . Remove the connectors attached to the re- settable thermal switch on the manifold mount. Inner Door Removal Procedure (cont’d) Step 7. Remove the flammable vapor sensor from the clip by pushing down on the tab to open the clip. Step 8.
Page 48 inner door gasket to the inner door sections. Refer to the illustration for proper applica- tion. Note the overlap configuration in the flange area of the inner door. Set the flange section first, and this will help to achieve the proper overlap position.
Page 49 screws. Verify that both the left and right side inner doors are properly positioned and sealed against the combustion chamber. Step 8. Re-install the outer door. Step 9. To resume operation, follow the instructions located on the water heater lighting instruction label.
Page 50 Common Terms BTU British Thermal Units ECO Energy Cut Off GPM Gallons per Minute Hz Hertz KWh Kilowatts per hour LED Light Emitting Diode NPT National Pipe Thread Ohms Ohms of resistance PSI Pounds per Square Inch RPM Revolutions per Minute VAC Volts Alternating Current W.
Page 51 Parts List 3 3 32 3 0 39 34 3 5 36 29 18 3 1 2 1 20 1 2 3 4 5 12 1 3 9 10 1 1 1 4 1 5 1 9 2 2 2 3 2 7 28 7 25 24 6 26 16 1 7 29 1 8 1 8 18 18 40 37 38 Part Name and Description 1. Blower Complete 15. T&P Valve 29. Burner Assembly 2. Air Mixing Inlet 16.
Email parts@bradfordwhite.com techserv@bradfordwhite.com www .bradfordwhite.com.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Bradford-White Corp U2TW65T*FRN c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Bradford-White Corp U2TW65T*FRN - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Bradford-White Corp U2TW65T*FRN, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Bradford-White Corp U2TW65T*FRN va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Bradford-White Corp U2TW65T*FRN, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Bradford-White Corp U2TW65T*FRN.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Bradford-White Corp U2TW65T*FRN. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Bradford-White Corp U2TW65T*FRN ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.