Manuel d'utilisation / d'entretien du produit R134A du fabricant York
Aller à la page of 140
FORM 201.23-EG1 (1007) Air Cooled Screw Liquid Chillers 150 - 385 T ONS (527 - 1354 kWi) 2 and 3 Compressor 50 and 60 Hz ASHRAE 90.1 Compliant R134a � 140-200 T ons 60Hz.
JOHNSON CONTROLS 2 Introduction ........................................................................................................................................................................................................... 3 Specications .
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 3 YORK has a proud history of innovation in both compressor design and variable-speed-drive (VSD) technology . The Latitude TM air cooled chiller uses the best of modern screw compressor design and manufacturing techniques and combines them with the latest in a long line of chiller variable speed drives.
JOHNSON CONTROLS 4 Specications POWER AND ELECTRICAL • Johnson Controls has over 25 years of experience designing variable speed drives specically for chiller applications.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 5 • Discharge line provided with manual compressor shut of f serv ice valv e (See Option s and Acc ess ori es for suction line valve). Suction line equipped with closed- cell insulation. • Insulated external oil separator s with no moving parts, 450 PSIG (31 bar) design working pressure, and UL listing.
JOHNSON CONTROLS 6 and schedule, (variable) out of range, remote input indication, chilled liquid reset setpoint, and history data for last ten shutdown faults. Compressor suc - tion, discharge, and oil pressures and temperatures, suct ion and dis charg e superhea ts, percen t of full- load, operating hours, starts, and anti-recycle timer status.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 7 Accessories and Options SOUND REDUCTION OPTIONS – The standard chiller has fans that operate at normal speed, no compressor enclosure, and is typically used in non-sensitive sound areas such as industrial areas or locations with loud trafc backg roun d noise.
JOHNSON CONTROLS 8 Accessories and Options (Continued) BUILDING AUT OMA TION SYSTEM INTERF ACE: • Chiller to accept 4 to 20mA or 0 to 10 VDC input to reset the leaving chilled liquid temperature.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 9 NOMENCLA TURE The Model Number denotes the following characteristics of the unit: .
JOHNSON CONTROLS 10 T emperatures and Flows TEMPERA TURE AND FLOWS (English Units) NOTES: 1. For leaving brine temperature below 40°F (4.4°C), contact your nearest Johnson Controls ofce for application requirements. 2. For leaving water temperature higher than 60°F (15.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 1 1 TEMPERA TURE AND FLOWS (SI Units) NOTES: 1. For leaving brine temperature below 4.4°C, contact your nearest Johnson Controls ofce for application requirements. 2. For leaving water temperature higher than 15.
JOHNSON CONTROLS 12 W ater Pressure Drop ENGLISH UNITS COOLER MODEL NUMBER YCIV 60Hz 50Hz A 0157(S/P) 0600(S/P) B 0157(E/V) 0590(E/V) 0177(S/P/E/V) 0630(E/V), 0650(S/P) 0187(S/P/E/V) 0700(E/V), 0720(S.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 13 SI UNITS .
JOHNSON CONTROLS 14 EV AP YCIV MODELS 60Hz 50Hz A 0267EA/V A 1050(E/V) 0287SA/P A 1070(S/P) 0287EA/V A 1 120(E/V) B 0307SA/P A 1 180(S/P) 0327EA/V A 1220(E/V) 0357SA/P A 1340(S/P) 0357EA/V A 1380(E/V).
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 15 .
JOHNSON CONTROLS 16 Standard Efciency Ratings – English - 460V/60Hz NOTES: 1. kWi = Compressor Input Power 2. EER = Chiller EER (includes power from compressors, fans, and control panels 0.8 KWi) 3. LCWT = Leaving Chilled W ater T emperature 4. Ratings based on 2.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 17 NOTES: 1. kWi = Compressor Input Power 2. EER = Chiller EER (includes power from compressors, fans, and control panels 0.8 KWi) 3. LCWT = Leaving Chilled W ater T emperature 4. Ratings based on 2.4 GPM cooler water per ton 5.
JOHNSON CONTROLS 18 Standard Efciency Ratings – English - 460V/60Hz NOTES: 1. kW = Compressor Input Power 2. EER = Chiller EER (includes power from compressors, fans, and control panels 0.8 KWi) 3. LCWT = Leaving Chilled W ater T emperature 4. Ratings based on 2.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 19 NOTES: 1. kW = Compressor Input Power 2. EER = Chiller EER (includes power from compressors, fans, and control panels 0.8 KWi) 3. LCWT = Leaving Chilled W ater T emperature 4. Ratings based on 2.4 GPM cooler water per ton 5.
JOHNSON CONTROLS 20 High Efciency Ratings – English - 460V/60Hz AIR TEMPERA TURE ON - CONDENSER (°F) LCWT 75.0 80.0 85.0 90.0 95.0 100.0 105.0 1 10.0 1 15.0 (°F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 21 AIR TEMPERA TURE ON - CONDENSER (°F) LCWT 75.0 80.0 85.0 90.0 95.0 100.0 105.0 1 10.0 1 15.0 (°F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER 40.
JOHNSON CONTROLS 22 High Efciency Ratings – English - 460V/60Hz NOTES: 1. kW = Compressor Input Power 2. EER = Chiller EER (includes power from compressors, fans, and control panels 0.8 KWi) 3. LCWT = Leaving Chilled W ater T emperature 4. Ratings based on 2.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 23 NOTES: 1. kW = Compressor Input Power 2. EER = Chiller EER (includes power from compressors, fans, and control panels 0.8 KWi) 3. LCWT = Leaving Chilled W ater T emperature 4. Ratings based on 2.4 GPM cooler water per ton 5.
JOHNSON CONTROLS 24 Standard Efciency Ratings – SI - 460V/60Hz MODEL:YCIV0157S/P AIR TEMPERA TURE ON - CONDENSER (°C) LCWT 25.0 30.0 35.0 40.0 45.0 46.0 (°C) KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP 5.0 530.8 136.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 25 MODEL:YCIV0207S/P AIR TEMPERA TURE ON - CONDENSER (°C) LCWT 25.0 30.0 35.0 40.0 45.0 46.0 (°C) KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP 5.0 693.1 174.3 3.7 680.1 201.0 3.2 665.
JOHNSON CONTROLS 26 MODEL:YCIV0267S/P AIR TEMPERA TURE ON - CONDENSER (°C) LCWT 25.0 30.0 35.0 40.0 45.0 46.0 (°C) KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP 5.0 898.1 224.4 3.7 883.4 254.8 3.2 866.4 288.2 2.8 838.4 322.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 27 MODEL:YCIV0357S/P AIR TEMPERA TURE ON - CONDENSER (°C) LCWT 25.0 30.0 35.0 40.0 45.0 46.0 (°C) KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP 5.0 1197.0 297.9 3.7 1 176.3 339.5 3.2 1 152.
JOHNSON CONTROLS 28 MODEL:YCIV0157E/V AIR TEMPERA TURE ON - CONDENSER (°C) LCWT 25.0 30.0 35.0 40.0 45.0 46.0 (°C) KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP 5.0 527.1 125.7 3.8 517.8 142.0 3.3 505.5 159.6 2.9 490.0 180.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 29 MODEL:YCIV0197E/V AIR TEMPERA TURE ON - CONDENSER (°C) LCWT 25.0 30.0 35.0 40.0 45.0 46.0 (°C) KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP 5.0 675.6 158.4 3.9 664.4 182.6 3.3 651.
JOHNSON CONTROLS 30 MODEL:YCIV0247E/V AIR TEMPERA TURE ON - CONDENSER (°C) LCWT 25.0 30.0 35.0 40.0 45.0 46.0 (°C) KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP 5.0 828.3 199.0 3.8 815.0 226.2 3.3 799.5 256.6 2.9 777.0 289.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 31 MODEL:YCIV0327E/V AIR TEMPERA TURE ON - CONDENSER (°C) LCWT 25.0 30.0 35.0 40.0 45.0 46.0 (°C) KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP 5.0 1088.2 253.3 3.9 1070.0 290.7 3.4 1049.
JOHNSON CONTROLS 32 Standard Efciency Ratings – SI - 400V/50Hz MODEL: YCIV0600S/P AIR TEMPERA TURE ON - CONDENSER (°C) LCWT 25.0 30.0 35.0 40.0 45.0 46.0 (°C) KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP 5.0 528.8 133.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 33 MODEL: YCIV0770S/P AIR TEMPERA TURE ON - CONDENSER (°C) LCWT 25.0 30.0 35.0 40.0 45.0 46.0 (°C) KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP 5.0 689.5 170.6 3.7 676.6 196.8 3.2 662.
JOHNSON CONTROLS 34 Standard Efciency Ratings – SI - 400V/50Hz MODEL: YCIV1000S/P AIR TEMPERA TURE ON - CONDENSER (°C) LCWT 25.0 30.0 35.0 40.0 45.0 46.0 (°C) KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP 5.0 894.3 219.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 35 MODEL: YCIV1340S/P AIR TEMPERA TURE ON - CONDENSER (°C) LCWT 25.0 30.0 35.0 40.0 45.0 46.0 (°C) KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP 5.0 1 191.3 291.5 3.7 1 170.8 332.4 3.
JOHNSON CONTROLS 36 High Efciency Ratings – SI - 400V/50Hz MODEL: YCIV0590E/V AIR TEMPERA TURE ON - CONDENSER (°C) LCWT 25.0 30.0 35.0 40.0 45.0 46.0 (°C) KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP 5.0 525.0 123.1 3.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 37 MODEL: YCIV0760E/V AIR TEMPERA TURE ON - CONDENSER (°C) LCWT 25.0 30.0 35.0 40.0 45.0 46.0 (°C) KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP 5.0 672.7 155.1 3.9 661.6 178.9 3.4 648.
JOHNSON CONTROLS 38 High Efciency Ratings – SI - 400V/50Hz MODEL: YCIV0930E/V AIR TEMPERA TURE ON - CONDENSER (°C) LCWT 25.0 30.0 35.0 40.0 45.0 46.0 (°C) KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP 5.0 824.5 194.8 3.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 39 MODEL: YCIV1220E/V AIR TEMPERA TURE ON - CONDENSER (°C) LCWT 25.0 30.0 35.0 40.0 45.0 46.0 (°C) KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP 5.0 1082.7 247.9 3.9 1064.7 284.7 3.4 1044.
JOHNSON CONTROLS 40 Standard Efciency Ratings – English - 380V/60Hz MODEL: YCIV0157S/P S_IPL V = 13.4 P_IPL V = 14.7 AIR TEMPERA TURE ON - CONDENSER (°F) LCWT 75.0 80.0 85.0 90.0 95.0 100.0 105.0 1 10.0 1 15.0 (°F) TONS KW EER T ONS KW EER TONS KW EER T ONS KW EER TONS KW EER TONS KW EER T ONS KW EER TONS KW EER T ONS KW EER 40.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 41 MODEL: YCIV0207S/P S_IPL V = 13.5 P_IPL V = 14.9 AIR TEMPERA TURE ON - CONDENSER (°F) LCWT 75.0 80.0 85.0 90.0 95.0 100.0 105.0 1 10.0 1 15.0 (°F) TONS KW EER T ONS KW EER TONS KW EER T ONS KW EER TONS KW EER TONS KW EER T ONS KW EER TONS KW EER T ONS KW EER 40.
JOHNSON CONTROLS 42 Standard Efciency Ratings – English - 380V/60Hz MODEL: YCIV0267S/P S_IPL V = 12.5 P_IPL V = 15.2 AIR TEMPERA TURE ON - CONDENSER (°F) LCWT 75.0 80.0 85.0 90.0 95.0 100.0 105.0 1 10.0 1 15.0 (°F) TONS KW EER T ONS KW EER TONS KW EER T ONS KW EER TONS KW EER TONS KW EER T ONS KW EER TONS KW EER T ONS KW EER 40.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 43 NOTES: 1. kW = Compressor Input Power 2. EER = Chiller EER (includes power from compressors, fans, and control panels 0.8 KWi) 3. LCWT = Leaving Chilled Water T emperature 4. Ratings based on 2.4 GPM cooler water per ton 5.
JOHNSON CONTROLS 44 High Efciency Ratings – English - 380V/60Hz MODEL: YCIV0157E/V E_IPL V = 13.8 V_IPL V = 14.9 AIR TEMPERA TURE ON - CONDENSER (°F) LCWT 75.0 80.0 85.0 90.0 95.0 100.0 105.0 1 10.0 1 15.0 (°F) TONS KW EER T ONS KW EER TONS KW EER T ONS KW EER TONS KW EER TONS KW EER T ONS KW EER TONS KW EER T ONS KW EER 40.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 45 MODEL: YCIV0197E/V E_IPL V = 13.1 V_IPL V = 15.2 AIR TEMPERA TURE ON - CONDENSER (°F) LCWT 75.0 80.0 85.0 90.0 95.0 100.0 105.0 1 10.0 1 15.0 (°F) TONS KW EER T ONS KW EER TONS KW EER T ONS KW EER TONS KW EER TONS KW EER T ONS KW EER TONS KW EER T ONS KW EER 40.
JOHNSON CONTROLS 46 High Efciency Ratings – English - 380V/60Hz MODEL: YCIV0247E/V E_IPL V = 13.0 V_IPL V = 15.2 AIR TEMPERA TURE ON - CONDENSER (°F) LCWT 75.0 80.0 85.0 90.0 95.0 100.0 105.0 1 10.0 1 15.0 (°F) TONS KW EER T ONS KW EER TONS KW EER T ONS KW EER TONS KW EER TONS KW EER T ONS KW EER TONS KW EER T ONS KW EER 40.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 47 MODEL: YCIV0327E/V E_IPL V = 14.1 V_IPL V = 15.0 AIR TEMPERA TURE ON - CONDENSER (°F) LCWT 75.0 80.0 85.0 90.0 95.0 100.0 105.0 1 10.0 1 15.0 (°F) TONS KW EER T ONS KW EER TONS KW EER T ONS KW EER TONS KW EER TONS KW EER T ONS KW EER TONS KW EER T ONS KW EER 40.
JOHNSON CONTROLS 48 Standard Efciency Ratings – SI - 380V/60Hz MODEL: YCIV0157S/P AIR TEMPERA TURE ON - CONDENSER (°C) LCWT 25.0 30.0 35.0 40.0 45.0 46.0 (°C) KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP 5.0 528.8 133.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 49 MODEL: YCIV0207S/P AIR TEMPERA TURE ON - CONDENSER (°C) LCWT 25.0 30.0 35.0 40.0 45.0 46.0 (°C) KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP 5.0 689.5 170.6 3.7 676.6 196.8 3.2 662.
JOHNSON CONTROLS 50 Standard Efciency Ratings – SI - 380V/60Hz MODEL: YCIV267S/P AIR TEMPERA TURE ON - CONDENSER (°C) LCWT 25.0 30.0 35.0 40.0 45.0 46.0 (°C) KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP 5.0 894.3 219.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 51 MODEL: YCIV357S/P AIR TEMPERA TURE ON - CONDENSER (°C) LCWT 25.0 30.0 35.0 40.0 45.0 46.0 (°C) KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP 5.0 1 191.3 291.5 3.7 1 170.8 332.4 3.3 1 147.
JOHNSON CONTROLS 52 High Efciency Ratings – SI - 380V/60Hz MODEL: YCIV0157E/V AIR TEMPERA TURE ON - CONDENSER (°C) LCWT 25.0 30.0 35.0 40.0 45.0 46.0 (°C) KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP 5.0 525.0 123.1 3.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 53 MODEL: YCIV0197E/V AIR TEMPERA TURE ON - CONDENSER (°C) LCWT 25.0 30.0 35.0 40.0 45.0 46.0 (°C) KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP 5.0 672.7 155.1 3.9 661.6 178.9 3.4 648.
JOHNSON CONTROLS 54 High Efciency Ratings – SI - 380V/60Hz MODEL: YCIV0247E/V AIR TEMPERA TURE ON - CONDENSER (°C) LCWT 25.0 30.0 35.0 40.0 45.0 46.0 (°C) KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP 5.0 824.5 194.8 3.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 55 MODEL: YCIV0327E/V AIR TEMPERA TURE ON - CONDENSER (°C) LCWT 25.0 30.0 35.0 40.0 45.0 46.0 (°C) KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP 5.0 1082.7 247.9 3.9 1064.7 284.7 3.4 1044.
JOHNSON CONTROLS 56 Contact your nearest Johnson Controls Sales Ofce for weight data. Physical Data (English - Standard Efciency) Refrigerant R-134a ST ANDARD EFFICIENCY MODEL NUMBER (YCIV____ S.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 57 Contact your nearest Johnson Controls Sales Ofce for weight data. Refrigerant R-134a ST ANDARD EFFICIENCY MODEL NUMBER (YCIV____ S/P) General Unit Data 60Hz 0287 0307 0357 0397 50Hz 1070 1 180 1340 1500 Number of Independent Refrigerant Circuits 3 3 3 3 Refrigerant Charge, R-134a, Ckt.
JOHNSON CONTROLS 58 Physical Data (English - High Efciency) Refrigerant R-134a HIGH EFFICIENCY MODEL NUMBER (YCIV____ E/V) General Unit Data 60Hz 0157 0177 0187 0197 0207 0227 0247 50Hz 0590 0630 0700 0760 0800 0830 0930 Number of Independent Refrigerant Circuits 222222 2 Refrigerant Charge, R-134a, Ckt.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 59 Refrigerant R-134a HIGH EFFICIENCY MODEL NUMBER (YCIV____ E/V) General Unit Data 60Hz 0267 0287 0327 0357 50Hz 1550 1120 1220 1380 Number of Independent Refrigerant Circuits 3 3 3 3 Refrigerant Charge, R-134a, Ckt.
JOHNSON CONTROLS 60 Physical Data (SI - Standard Efciency) Refrigerant R-134a ST ANDARD EFFICIENCY MODEL NUMBER (YCIV____ S/P) General Unit Data 60Hz 0157 0177 0187 0207 0227 0247 0267 50Hz 0600 0650 0720 0770 0840 0920 1000 Number of Independent Refrigerant Circuits 2222222 Refrigerant Charge, R-134a, Ckt.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 61 Refrigerant R-134a ST ANDARD EFFICIENCY MODEL NUMBER (YCIV____ S/P) General Unit Data 60Hz 0287 0307 0357 0397 50Hz 1070 1 180 1340 1500 Number of Independent Refrigerant Circuits 3 3 3 3 Refrigerant Charge, R-134a, Ckt.
JOHNSON CONTROLS 62 Physical Data (SI - High Efciency) Refrigerant R-134a HIGH EFFICIENCY MODEL NUMBER (YCIV____ E/V) General Unit Data 60Hz 0157 0177 0187 0197 0207 0227 0247 50Hz 0590 0630 0700 0760 0800 0830 0930 Number of Independent Refrigerant Circuits 222222 2 Refrigerant Charge, R-134a, Ckt.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 63 Refrigerant R-134a HIGH EFFICIENCY MODEL NUMBER (YCIV____ E/V) General Unit Data 60Hz 0267 0287 0327 0357 50Hz 1550 1 120 1220 1380 Number of Independent Refrigerant Circuits 3 3 3 3 Refrigerant Charge, R-134a, Ckt.
JOHNSON CONTROLS 64 Dimensions – English Notes: 1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation, and ease of maintenance.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 65 33 5/16" 103 3/8" 80" 230" 101 5/8" 50" 50 5/16" 9 1/8" 93 15/16" 1 5/16" (TYP) X G C Y (3) RIGGING HOLES E.
JOHNSON CONTROLS 66 Dimensions – English - continued Notes: 1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation, and ease of maintenance.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 67 POWER: SINGLE POINT WITH TERMINAL BLOCK X G C Y VIEW D-D B 33 5/16" 103 5/16" A 1 12 13/16" 84 1/2" 93 15/16" D D X G C Z 10" (.
JOHNSON CONTROLS 68 Dimensions – English - continued Models YCIV0197E/V , YCIV0207S/P , and YCIV0227S/P Notes: 1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation, and ease of maintenance.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 69 POWER: SINGLE POINT WITH TERMINAL BLOCK X G C Y VIEW D-D 274" 33 5/16" 103 5/16" 88" D C 93 15/16" D D X Z 10" (WA TER INLET) 1.
JOHNSON CONTROLS 70 Dimensions – English - continued Models YCIV0207E/V and YCIV0227E/V Notes: 1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation, and ease of maintenance.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 71 POWER: SINGLE POINT WITH TERMINAL BLOCK CONTROL P ANEL VIEW D-D 9 1/8" 50 5/16" 37 13/16" 64 3/16" 49 3/16" 60" 318" 33 5/.
JOHNSON CONTROLS 72 Dimensions – English - continued Models YCIV0247S/P , YCIV0247E/V , and YCIV0267S/P Notes: 1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation, and ease of maintenance.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 73 POWER: SINGLE POINT WITH TERMINAL BLOCK CONTROL P ANEL VIEW D-D 9 1/8" 50 5/16" 37 13/16" 64 3/16" 49 3/16" 60" 318" 33 5/.
JOHNSON CONTROLS 74 Dimensions – English - continued Models YCIV0267E/V , and YCIV0287S/P Notes: 1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation, and ease of maintenance.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 75 POWER: SINGLE POINT WITH TERMINAL BLOCK 45 5/16" 29 7/8" 17 5/8" A A X G C Z D D 93 15/16" CONTROL P ANEL 337 3/16" 197 13/16" .
JOHNSON CONTROLS 76 Dimensions – English - continued Models YCIV0287E/V Notes: 1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation, and ease of maintenance.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 77 POWER: SINGLE POINT WITH TERMINAL BLOCK 50 5/16" 50" 76" 99" 19" 53 3/8" 9 1/8" 1 5/16" (TYP) 7 5/8" 17 5/8".
JOHNSON CONTROLS 78 Dimensions – English - continued Models YCIV0307S/P Notes: 1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation, and ease of maintenance.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 79 POWER: SINGLE POINT WITH TERMINAL BLOCK 45 5/16" 26 3/8" 16 3/16" A A X G C Z D D 93 15/16" CONTROL P ANEL 337 3/16" 197 13/16".
JOHNSON CONTROLS 80 Dimensions – English - continued Models YCIV0327E/V and YCIV0357S/P Notes: 1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation, and ease of maintenance.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 81 POWER: SINGLE POINT WITH TERMINAL BLOCK 50 5/16" 50" 76" 99" 74 1/8" 53 3/8" 9 1/8" 1 5/16" (TYP) 6 7/8" 18 3/16.
JOHNSON CONTROLS 82 Dimensions – English - continued Models YCIV0357E/V and YCIV0397S/P Notes: 1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation, and ease of maintenance.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 83 93 15/16" 6 7/8" CONTROL P ANEL ORIGIN 53 3/8" 9 1/8" 50 5/16" 50" 76" 1 12 1 1/16" 19" POWER: SINGLE POINT WITH.
JOHNSON CONTROLS 84 Dimensions – SI Notes: 1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation, and ease of maintenance.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 85 846 2626 2032 D C 5842 2581 1270 1278 231 2387 33 (TYP) X G C Y (3) RIGGING HOLES EACH SIDE (76 X 51) 10" WA TER OUTLET 10" WA TER INLET VIEW D-D X.
JOHNSON CONTROLS 86 Dimensions – SI - continued Notes: 1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation, and ease of maintenance.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 87 DIMENSIONS (mm) UNLESS OTHERWISE NOTED POWER: SINGLE POINT WITH TERMINAL BLOCK X G C Y VIEW D-D B 846 2624 A 2865 2146 2387 D D X Z 10" (WA TER INLET) 1.
JOHNSON CONTROLS 88 Dimensions – SI - continued Notes: 1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation, and ease of maintenance.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 89 POWER: SINGLE POINT WITH TERMINAL BLOCK X G C Y VIEW D-D 6960 846 2624 2235 D C 2387 D D X G C Z 10" (WA TER INLET) 10" (WA TER OUTLET) A A 231 127.
JOHNSON CONTROLS 90 Dimensions – SI - continued Notes: 1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation, and ease of maintenance.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 91 POWER: SINGLE POINT WITH TERMINAL BLOCK CONTROL P ANEL VIEW D-D 231 1278 960 1631 1250 1524 8077 846 2355 4590 7236 2852 2174 10" (WA TER OUTLET) 10&quo.
JOHNSON CONTROLS 92 Dimensions – SI - continued Notes: 1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation, and ease of maintenance.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 93 POWER: SINGLE POINT WITH TERMINAL BLOCK CONTROL P ANEL VIEW D-D 231 1278 960 1631 1250 1524 8077 846 2355 4590 7236 2878 2009 10" (WA TER OUTLET) 10&quo.
JOHNSON CONTROLS 94 Dimensions – SI - continued Notes: 1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation, and ease of maintenance.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 95 POWER: SINGLE POINT WITH TERMINAL BLOCK 1 151 759 447 A A X G C Z D D 2387 CONTROL P ANEL 8565 5024 371 3584 6060 9068 843 10" (WA TER INLET) 10" (.
JOHNSON CONTROLS 96 Dimensions – SI - continued Notes: 1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation, and ease of maintenance.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 97 POWER: SINGLE POINT WITH TERMINAL BLOCK 1278 1270 1930 2515 483 1356 231 33 (TYP) 193 447 759 2387 D D X G C Z X G C Y CONTROL P ANEL ORIGIN A A 10699 3142 5.
JOHNSON CONTROLS 98 Dimensions – SI - continued Notes: 1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation, and ease of maintenance.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 99 POWER: SINGLE POINT WITH TERMINAL BLOCK 1 151 671 41 1 A A X G C Z D D 2387 CONTROL P ANEL 8565 5024 381 3584 6060 9068 843 10" (WA TER INLET) 10" .
JOHNSON CONTROLS 100 Dimensions – SI - continued Notes: 1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation, and ease of maintenance.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 101 POWER: SINGLE POINT WITH TERMINAL BLOCK 1278 1270 1930 2515 1882 1356 231 33 (TYP) 175 462 638 2387 D D X G C Z X G C Y CONTROL P ANEL ORIGIN A A 10700 3066.
JOHNSON CONTROLS 102 Dimensions – SI - continued Notes: 1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable operation, and ease of maintenance.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 103 2387 175 CONTROL P ANEL ORIGIN 1356 231 1278 1270 1930 2863 483 POWER: SINGLE POINT WITH TERMINAL BLOCK VIEW D-D 16 MOUNTING HOLES (TYP) 381 5024 3066 843 5.
JOHNSON CONTROLS 104 Isolator Locations – English CONTROL PANEL L1 L2 R6 R1 L6 L5 L4 L3 R2 R3 R4 R5 R7 L7 x y ST ANDARD EFFICIENCY - ENGLISH MODEL Isolator Locations ( x , y ) - in. and Point Loads - lbs 60 Hz 50 Hz 1 2 3 4 5 6 7 YCIV0157S/P YCIV0600S/P LEFT - L ( 9.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 105 MODEL Isolator Locations ( x , y ) - in. and Point Loads - lbs 60 Hz 50 Hz 1 2 3 4 5 6 7 YCIV0267S/P YCIV1000S/P LEFT - L ( 9.1 , 86.8 ) ( 59.4 , 86.8 ) ( 97.2 , 86.8 ) ( 161.4 , 86.8 ) ( 210.6 , 86.8 ) ( 307.
JOHNSON CONTROLS 106 Isolator Locations – English – continued CONTROL PANEL L1 L2 R6 R1 L6 L5 L4 L3 R2 R3 R4 R5 R7 L7 x y HIGH EFFICIENCY - ENGLISH MODEL Isolator Locations ( x , y ) - in. and Point Loads - lbs 60 Hz 50 Hz 1 2 3 4 5 6 7 YCIV0157E/V YCIV0590E/V LEFT - L ( 9.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 107 MODEL Isolator Locations ( x , y ) - in. and Point Loads - lbs 60 Hz 50 Hz 1 2 3 4 5 6 7 YCIV0227E/V YCIV0830E/V LEFT - L ( 9.1 , 86.8 ) ( 59.4 , 86.8 ) ( 97.2 , 86.8 ) ( 161.4 , 86.8 ) ( 210.6 , 86.8 ) ( 307.
JOHNSON CONTROLS 108 CONTROL PANEL L1 L2 R6 R1 L6 L5 L4 L3 R2 R3 R4 R5 R7 L7 x y Isolator Locations – SI ST ANDARD EFFICIENCY - SI MODEL Isolator Locations ( x , y ) - mm and Point Loads - kg 60 Hz .
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 109 MODEL Isolator Locations ( x , y ) - mm and Point Loads - kg 60 Hz 50 Hz 1 2 3 4 5 6 7 YCIV0247S/P YCIV0920S/P LEFT - L ( 230 , 2204 ) ( 1510 , 2204 ) ( 247.
JOHNSON CONTROLS 1 10 CONTROL PANEL L1 L2 R6 R1 L6 L5 L4 L3 R2 R3 R4 R5 R7 L7 x y Isolator Locations – SI – continued HIGH EFFICIENCY - SI MODEL Isolator Locations ( x , y ) - mm and Point Loads -.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 1 1 1 MODEL Isolator Locations ( x , y ) - mm and Point Loads - kg 60 Hz 50 Hz 1234567 YCIV0227E/V YCIV0830E/V LEFT - L ( 230 , 2204 ) ( 1510 , 2204 ) ( 2470 , .
JOHNSON CONTROLS 1 12 FOR UNITS WITH ALL POINT LOADS LESS THA TN 1404 LBS (637 KG) Weight Range (lbs) Weight Range (kg) Model Number Color 239 to 384 lbs 108 to 174 kg CIP-B- Red 384 to 639 lbs 174 to.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 1 13 Weight Range (lbs) Weight Range (kg) Model Number Color Up to 751 lbs Up to 341 kg ND-C Y ellow 751 to 1651 lbs 341 to 749 kg ND-D Y ellow 1651 to 3226 lbs 749 to 1463 kg ND-DS Y ellow "CS" Cap Screw BC "MBD" Max.
JOHNSON CONTROLS 1 14 Isolator Details (cont'd) ENGLISH SIZE H T D E L HCL W HCW MBD 2-C2 8 1/2 3/8 5/8 1 3/8 14 12 1/4 5 1/4 3 1/ 2 5/8" SI SIZE H T D E L HCL W HCW MBD 2-C2 215.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 1 15 INTENTIONALL Y LEFT BLANK.
JOHNSON CONTROLS 1 16 Electrical Data - 2 Comp Standard Efciency See page 192 for Electrical Data footnotes. Standard Efciency YCIV_ _ _ _ S/P Standard Efciency YCIV_ _ _ _ S/P Model No./Nameplate System 1 System 2 Std. & Ultra Quiet Cond.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 1 17 Standard Efciency YCIV_ _ _ _ S/P Standard Efciency YCIV_ _ _ _ S/P Model No./Nameplate System 1 System 2 Std. & Ultra Quiet Cond. Fans High Head/Static Cond. Fans T wo-Speed Cond. Fans Std. & Ultra Quiet Cond.
JOHNSON CONTROLS 1 18 Electrical Data - 2 Comp High Efciency High Efciency YCIV_ _ _ _ E/V High Efciency YCIV_ _ _ _ E/V Model No./Nameplate System 1 System 2 Std. & Ultra Quiet Cond. Fans High Head/Static Cond. Fans T wo-Speed Cond. Fans Std.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 1 19 High Efciency YCIV_ _ _ _ E/V High Efciency YCIV_ _ _ _ E/V Model No./Nameplate System 1 System 2 Std. & Ultra Quiet Cond. Fans High Head/Static Cond. Fans T wo-Speed Cond. Fans Std. & Ultra Quiet Cond.
JOHNSON CONTROLS 120 Electrical Data - 3 Comp Standard Efciency See page 192 for Electrical Data footnotes. Model No./Nameplate System 1 System 2 System 2 System 3 Std. & Ultra Quiet Cond. Fans High Head/Static Cond. Fans T wo-Speed Cond. Fans Std.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 121 Model No./Nameplate System 1 System 2 System 2 System 3 Std. & Ultra Quiet Cond. Fans High Head/Static Cond. Fans T wo-Speed Cond. Fans Std. & Ultra Quiet Cond. Fans High Head/Static Cond. Fans Two-Speed Cond.
JOHNSON CONTROLS 122 Electrical Data - 3 Comp High Efciency See page 192 for Electrical Data footnotes. Model No./Nameplate System 1 System 2 System 2 System 3 Std. & Ultra Quiet Cond. Fans High Head/Static Cond. Fans T wo-Speed Cond. Fans Std.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 123 Model No./Nameplate System 1 System 2 System 2 System 3 Std. & Ultra Quiet Cond. Fans High Head/Static Cond. Fans T wo-Speed Cond. Fans Std. & Ultra Quiet Cond. Fans High Head/Static Cond. Fans T wo-Speed Cond.
JOHNSON CONTROLS 124 LEGEND C.B. CIRCUIT BREAKER D.E. DUAL ELEMENT FUSE DISC SW DISCONNECT SWITCH F ACT CB F ACT ORY -MOUNTED CIRCUIT BREAKER FLA FULL LOAD AMPS HZ HER TZ MAX MAXIMUM MCA MINIMUM CIRCUIT AMP ACITY MIN MINIMUM MIN NF MINIMUM NON-FUSED RLA RA TED LOAD AMPS S.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 125 FIG. 1 – TWO COMPRESSOR WIRING DIAGRAM WITH CIRCUIT BREAKER 2 COMPRESSOR POWER WIRING CONNECTIONS FIG. 2 – TWO COMPRESSOR WIRING DIAGRAM WITH TERMINAL B.
JOHNSON CONTROLS 126 Power Wiring – continued FIG. 3 – THREE COMPRESSOR WIRING DIAGRAM WITH CIRCUIT BREAKER – SINGLE POINT FIG. 4 – THREE COMPRESSOR WIRING DIAGRAM WITH TERMINAL BLOCK – SING.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 127 INTENTIONALL Y LEFT BLANK.
JOHNSON CONTROLS 128 T ypical Control Wiring - T wo Compressor.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 129 For informational purposes only . Do not attempt to tie into wiring without a proper wiring diagram..
JOHNSON CONTROLS 130 T ypical Control Wiring - Three Compressor.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 131 For informational purposes only . Do not attempt to tie into wiring without a proper wiring diagram..
JOHNSON CONTROLS 132 UNIT LOCA TION The YCIV chillers are designed for outdoor installation. When selecting a site for installation, be guided by the following requirements: 1. Installation sites may be either on a roof or on ground level. (See FOUNDA TION) 2.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 133 Guide Specications P ART 1 — GENERAL 1.01 SCOPE A. The requirements of the General Conditions, Supple - mentary Conditions, and Drawings apply to all work herein.
JOHNSON CONTROLS 134 Guide Specications – continued system, interconnecti ng wiring, safety and operating controls including capacity controller , control center , motor starting components, and special features as specied herein or required for safe, automatic operation.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 135 with full hei ght collars. Subcooling coil an integral part of condenser . Design working pressure shall be 450 PSIG (31 bar).
JOHNSON CONTROLS 136 at ur es , amb ie nt , lea d com pr es so r ide nt i c at io n, cloc k and schedule, (variable) out of range, remote input indication, chilled liquid reset setpoint, and history data for last ten shutdown faults.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 137 components. 4. Louvered/Wire Panels: Louvered steel panels on external condenser coil faces, painted to match unit panels. Heav y gaug e, welded wire- mesh, coated to resist corrosion, around base of machine to restrict unauthorized access.
JOHNSON CONTROLS 138.
JOHNSON CONTROLS FORM 201.23-EG1 (1007) 139.
Form 201.23-EG1 (1007) Supersedes: 201.23-EG1 (607) File in ET2.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté York R134A c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du York R134A - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation York R134A, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le York R134A va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le York R134A, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du York R134A.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le York R134A. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei York R134A ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.