Manuel d'utilisation / d'entretien du produit 1200 cfm du fabricant Venmar
Aller à la page of 24
Light Commer cial Heat Recovery V entilators VB0002 VB0003 VB0001 600 cfm 700 cfm 1200 cfm Installation, Operation and Service Instructions 06/00 04597.
Page 2 Contents 1 Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2 Installation 2.1 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page 3 1 Safety Considerations Hazards may exist within this equipment because it contains electrical and powerful moving components. Only qualified service personnel should install or service this equipment. Untrained personnel can perform basic maintenance such as maintaining filters.
Page 4 The supply and exhaust ducts connected to outside, as well as any ducts passing through an unconditioned space, must have a minimum insulation value of R5.
Page 5 2.8 Electrical Connections Power A terminal block and strain relief bushing or a junction box is provided for line voltage to make the necessary power connections. The electrical requirements are as follows: Control Box Access For Low Speed Setting (600 cfm/1200 cfm only) Disconnect power to the unit.
Page 6 Recirculation Defr ost Module (Optional - Factory Installed) The Recirculation Defrost Module is only available with the 600 cfm and 1200 cfm units. The defrost cycle is electronically controlled in response to the outside temperature 23°F to -22°F (-5°C to -30°C).
Page 7 4.2 Balancing Procedur e Before proceeding with balancing, all windows, overhead doors and walk-in doors should be closed and exhaust systems should be turned off. The connections between the flow stations and the ducts must be sealed with tape.
Page 8 Allow the heat recovery core to soak for three hours in warm water and mild soap. Rinse under a heavy stream of water . Fans Blower wheels and fan housing should be checked for dirt build-up. If they appear dirty , it may be necessary to remove the blower assembly and then vacuum the dust out through the fan mouth.
Page 9 3/8" (10mm) Threaded Rod (Supplied by others) Rubber Vibration Isolater Cabinet Mounted U Channel Wooden Curb (Supplied by others) Bolt to Floor Space must be left to allow connection of d.
Page 10 8.000" [203] 4.000" [102] 8.000" [203] 3.535" [90] 4.000" [102] 28.005" [71 1] 14.000" [356] 5.859" [149] 13.375" [340] 23.500" [597] 2.750" [70] 14.000" [356] 6.500" [165] 8.000" [203] 8.
28.12" [714] 14.00" [356] 4.00" [102] 1.75" [44] 8.00" [203] 2.75" [70] 19.207" [488] 5.125" [130] Access Door Strap Mounting Location Drain Fitting NOTE: For units with the reversed door option, interior components will appear as a mirror image of the above diagram.
Page 12 41.206" [1047] 40.326" [1024] 20.000" [508] 5.715" [145] 20.620" [524] 14.250" [362] 34.000" [864] 5.125" [130] 19.207" [488] 4.028" [102] 1 1.325" [288] 12.000" [305] 15.000" [381] 20.
Page 13 8.00" [203] 1.75" [44] 10.00" [254] 20.00" [508] 2.75" [70] Alimentation électrique Borniers 49.550" [1259] Localisation de la courroie de fixation Aspiration d’air frais Évacuation d’air vicié 5.125" [130] Noyau de récupération de chaleur Option de porte inversée Porte d’accès 15.
Page 14 10.000" [254] Dimensions in [ ] are in millimeters Center of gravity Direction of airflow HRV700i LBS Kg 32.74 14.85 68.46 31.05 35.20 15.97 73.60 33.38 210.00 1.875" [48] EXHAUST AIR OPENING SUPPL Y AIR OPENING 20.750" [527] 8.
Page 15 Flow Measuring Station (FMS) Balancing Damper Canvas Vibration Isolator Min. 12" (305mm) Min. 30" (762mm) Reverse Door Option Exhaust Air From Building Fresh Air From Outside Min. 8" (203mm) (Optional) Canvas Vibration Isolator Min.
Page 16 T o Drain Copper or Plastic Pipe Plastic Drain Fittings Plastic Hose W ater T rap Coupler 3/4"NPT Note: All hose, pipe & couplers to be supplied by others TD i All hose, pipe, and couplers to be supplied by others.
Page 17 WALL CONTROL CLASS 2 VOL T AGE Black OCCUPIED TIMER/ SENSOR F F LOW COMMON HIGH Red Green Y ellow NOTE: Connections are all dry contacts except wall control and 24V AC power supply . Use of 24V AC circuit requires isolating contacts (ex. thermostat) to prevent interconnection of Class 2 outputs.
Page 18 JUMPER (factory installed) OCC. CONTROL (field installed) NSB Timer V enmar PN 1604128 1 M 234 5 JUMPER WALL CONTROL CLASS 2 VOL T AGE Black OCCUPIED TIMER/ SENSOR F F LOW COMMON HIGH Red Green Y ellow NOTE: Connections are all dry contacts except wall control and 24V AC power supply .
Page 19 Control cover plate Control box Remote control access plate Remote wiring terminal block HRV Cabinet VE0001A R ed Low Speed (Red) Remove power before installing or removing JU1-F Extended Defr.
Page 20 Although the 600 cfm, 700 cfm and 1200 cfm models have good efficiencies, the supply air could be colder than the ambient room air . It is possible to eliminate the discomfort associated with this temperature difference by installing an electric duct heater .
Page 21 Appendix H Wiring Diagram Wiring Diagram for 600 cfm unit INTERLOCK (FF) W ALL CONTROL BLACK VE0023A 48445 POWER CONTROL BOARD -t 8 9 10 11 12 13 14 T7 1 2 3 4 5 6 7 T7 BL BL G R Y BK J3 1 J3 2 J3 8 J3 7 J3 6 J3 9 W ALL CONTROL RED OCC./ UNOCC.
Page 22 Appendix H Continued Wiring Diagram Wiring Diagram for 700 cfm unit VE0024A J1 6 J1 9 J1 2 K7 J1 3 LO GND L1 NEUT 120VCA 60Hz COLOR CODE 110 VOL TS LOW VOL T AGE AND FIELD WIRE J1 8 1 2 3 4 5 6 7 T7 INTERLOCK (FF) W ALL CONTROL BLACK 8 9 10 11 12 13 14 T7 W ALL CONTROL RED OCC.
Page 23 Appendix H Continued Wiring Diagram Wiring Diagram for 1200 cfm unit INTERLOCK (FF) W ALL CONTROL BLACK VE0022A . . . . . . JU1 J4 2 1 A B C D E F G 1 2 3 4 5 6 7 8 9 J3 F F I OC OL Y R G B 4 7 6 9 48445 POWER CONTROL BOARD J1 3 2 1 8 1 2 3 J2 COMM.
For technical assistance and warranty information, please call your local supplier . Appendix I T rouble Shooting SYMPTOMS POSSIBLE CAUSES SOLUTIONS Inside air is too dry Over ventilation - speed sett.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Venmar 1200 cfm c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Venmar 1200 cfm - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Venmar 1200 cfm, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Venmar 1200 cfm va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Venmar 1200 cfm, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Venmar 1200 cfm.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Venmar 1200 cfm. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Venmar 1200 cfm ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.