R T -DS-10 April 1999 Packaged Rooftop Air Conditioners 23 to 42 T on (81-148 kW) V oyager Commercial 50 HZ.
2 ©American Standard Inc. 1999 Features and Benefits Over the years the V oyager product line has developed into the most complete line of commercial packaged units available. W e were first with the Micro when we developed micro- electronic unit controls and we move ahead again with V oyager Commercial products.
3 Contents Contents Optional Features Electric heat Natural gas heat LP gas heat (kit only) Power exhaust Barometric relief High efficiency 2 (51 mm) throwaway filters H.
4 One of two matched scroll plates the distinguishing feature of the scroll compressor . Chart illustrates low torque variation of 3-D Scroll compressors reciprocating compressor .
5 Features and Benefits Micro Controls For over 10 years T rane has been working with microprocessor controls in the applied equipment markets. These designs have provided the technology that has been applied to the V oyager units.
6 Features and Benefits Excellent Part-Load Efficiency The Scroll compressor s unique design allows it to be applied in a passive parallel manifolded piping scheme, something that a recip just doesn t do very well.
7 Features and Benefits Serviceability T oday s owners are more conscious of the cost of service and maintenance. V oyager was designed with input from service contractors. Their information helped us design a unit that would get the serviceman off the job quicker and save the owner money .
8 V ariT rac T rane s changeover V A V System for light commercial applications is also available. Coupled with V oyager Commercial, it provides the latest in technological advances for comfort management systems and can allow thermostat control in every zone served by V ariT rac .
9 Model Number Description TC D 400 A C 0 A 1 A 4 F D .
10 T able 10-1 General Data 23-25 T ons TC*275 (23 T ons) TC*305 (25 T ons) Cooling Performance 1 Nominal Gross Capacity(Btuh) 279,000 (81.8 kW) 304,000 (89.1 kW) System Power kW 26.1 30.2 kW Compressor Number/T ype 2/Scroll 2/Scroll Nominal Motor HP (ea) 8.
11 T able 11-1 General Data 29-33 T ons TC*350 (29 T ons) TC*400 (33 T ons) Cooling Performance 1 Nominal Gross Capacity(Btuh) 375,000 (105 kW) 409,000 (120 kW) System Power kW 34.0 42.5 Compressor Number/T ype 2/Scroll 3/Scroll Nominal Motor HP (ea) 12.
12 General Data T able 12-1 General Data 43 T ons TC*500 (42T ons) Cooling Performance 1 Nominal Gross Capacity(Btuh) 505,000 (148 kW) System Power kW 52.9 Compressor Number/T ype 3/Scroll Nominal Motor HP (ea) 12.5 Motor RPM 2875 Natural Gas Heat 2 Low High Heating Input(Btuh) 335,000 (98.
13 Application Considerations Exhaust Air Options When is it necessary to provide building exhaust? Whenever an outdoor air economizer is used, a building generally requires an exhaust system. The purpose of the exhaust system is to exhaust the proper amount of air to prevent over or under -pressurization of the building.
14 Application Considerations Acoustical Considerations Proper placement of rooftops is critical to reducing transmitted sound levels to the building. The ideal time to make provisions to reduce sound transmissions is during the design phase.
15 Selection Procedure Selection of T rane commercial air conditioners is divided into five basic areas: 1 Cooling capacity 2 Heating capacity 3 Air delivery 4 Unit electrical requirements 5 Unit designation Factors Used In Unit Cooling Selection: 1 Summer design conditions 95 DB/ 76 WB (35/24.
16 Selection Procedure 1 Winter outdoor design conditions 0°F (17.7°C). 2 T otal return air temperature 72°F (22.2°C). 3 Winter outside air minimum ventilation load and cfm 1,000 cfm and 87.2 MBh. 4 Peak heating load 150 MBh. Utilizing unit selection in the cooling capacity procedure.
17 Performance Adjustment Factors T able 17-2 Cooling Capacity Altitude Correction Factors Altitude ft. (m) Sea Level 1000 (304.8) 2000 (609.6) 3000 (914.4) 4000 (1219.2) 5000 (1524.0) 6000 (1828.8) 7000 (2133.6) Cooling Capacity Multiplier 1.00 0.
18 Performance Data T able 18-1 23 T on Gross Cooling Capacities (MBh) English Ambient T emperature Deg F 85 95 105 115 Ent Entering Wet Bulb T emperature Deg F DB 61 67 73 61 67 73 61 67 .
19 Performance Data T able 19-1 25 T on Gross Cooling Capacities (MBh) English Ambient T emperature Deg F 85 95 105 115 Ent Entering Wet Bulb T emperature Deg F DB 61 67 73 61 67 73 61 67 .
20 Performance Data T able 20-1 29 T on Gross Cooling Capacities (MBh) English Ambient T emperature Deg F 85 95 105 115 Ent Entering Wet Bulb T emperature Deg F DB 61 67 73 61 67 73 61 67 .
21 Performance Data T able 21-1 33 T on Gross Cooling Capacities (MBh) English Ambient T emperature Deg F 85 95 105 115 Ent Entering Wet Bulb T emperature Deg F DB 61 67 73 61 67 73 61 67 .
22 T able 22-1 42 T on Gross Cooling Capacities (MBh) English Ambient T emperature Deg F 85 95 105 115 Ent Entering Wet Bulb T emperature Deg F DB 61 67 73 61 67 73 61 67 73 61 67 73 CFM (.
23 Performance Data T able 23-1 Electric Heat Air T emperature Rise (Degrees F) English Heater T otal CFM Input (kW) MB h 7000 8000 9000 10000 11000 12000 13000 14000 15000 16000 17000 26.9 92 12.1 10.6 9 .4 8. 5 7.7 7.1 40.4 138 18.
24 T able 24-1 Supply Fan Per formance 23-29 T on English Static Pressure (in. wg) 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 SCFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 6670. 307. 0.92 371. 1.30 431. 1.75 490.
25 Figure 25-1 Performance Data.
26 T able 26-1 Supply Fan Performance 33 and 42 T on English Static Pressure (in. wg) 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50 SCFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 9996. 309. 1.80 360.
27 Figure 27-1 Performance Data.
28 Performance Data T able 28-1 Component Static Pressure Drops (in wg) 50 Hz English Heating System Filters Nominal CF M Gas Heat Electric Heat ID Coil High Eff. Filters Inlet Guide Std.T ons (kW) Std Air Low High 1 Element 2 Element Adder 2 4 V anes Economizer 6670 0.
29 Performance Data T able 29-2 Power Exhaust Fan Performance - 50 Hz English External Static Pressure Inches of Water Exhaust High Med Low Airflow Speed Speed Speed (Cfm) ESP ESP ESP 1000 0.800 1500 0.780 2000 0.750 0.400 2500 0.
30 Electrical Data Electrical Service Sizing T o correctly size electrical service wiring for your unit, find the appropriate calculations listed below . Each type of unit has its own set of calculations for MCA (Minimum Circuit Ampacity), MOP (Maximum Overcurrent Protection), and RDE (Recommended Dual Element fuse size).
31 Electrical Data T able 31-1 Electrical Service Sizing Data Fan Motors Compressor Supply Condenser Electrical 2 Qty./ R L A L R A F L A Max. Model Characteristics Nominal HP ( E a. ) Ea.) H P F L A No . H P (Ea. ) MCA* Fuse Size TC/TE/YC*275 380-415/50/3 2/10,15 18.
32 Controls V A V Units Only Sequence of Operation 1 Supply Air Pressure Control Inlet Guide V ane Control Inlet guide vanes are driven by a modulating 2-10 vdc signal from the V A V Module.
33 Controls CV Units Only V A V Units Only Morning Warm-up (MWU) Morning warm-up control (MWU) is activated whenever the unit switches from unoccupied to occupied and the zone temperature is at least 1.
34 Controls Both V A V and CV Units Control Sequences of Operation That are Common to Both V A V and CV Units V entilation Override (VOM) V entilation override allows an external system to assume control of the unit for the purpose of exhaust or pressurization.
35 Dimensional Data Figure 35-1 23-29 T ons (TC, TE, YC Low Heat) Note: Dimensions in ( ) are mm 1 = 25.4 mm.
36 Figure 36-1 23-29 T ons (YC High Heat) Dimensional Data Note: Dimensions in ( ) are mm 1 = 25.4 mm.
37 Figure 37-1 33-42 T ons (TC, TE, YC Low & High Heat) Dimensional Data Note: Dimensions in ( ) are mm 1 = 25.4 mm.
38 T able 38-2 Approximate Operating Weights Kgs. Basic Unit Weights 1 W eight of Optional Components Non- Fact. Hi-Stat/ 0-25% Inlet Thru-the Fused GFI with Unit YC YC TC TE Baro. Power Hi Eff. Sup Man Guide Serv base Discon. Discon. Model Low Heat High Heat Relief Exhaust Fan Motor 2 Damper Econ.
39 Field Installed Sensors V ariable Air V olume SINGLE SETPOINT SENSOR WITH SYSTEM FUNCTION LIGHTS (BA YSENS021*) NOTE: Remote sensors are available for use with all zone sensors to provide remote sensing capabilities. PROGRAMMABLE NIGHT -SETBACK SENSOR (BA YSENS020*) Note: Dimensions in ( ) are mm 1 = 25.
40 Field Installed Sensors Constant V olume DUAL SETPOINT , MANUAL/AUTOMA TIC CHANGEOVER SENSOR WITH SYSTEM FUNCTION LIGHTS (BA YSENS010*) WITHOUT LED ST A TUS INDICA TORS (BA YSENS008*) SINGLE SETPOINT WITHOUT LED ST A TUS INDICA TORS (BA YSENS006*) PROGRAMMABLE NIGHT -SETBACK SENSOR (BA YSENS019*) Note: Dimensions in ( ) are mm 1 = 25.
41 Field Installed Sensors Constant and V ariable Air V olume NOTE: Remote sensors are available for use with all zone sensors to provide remote sensing capabilities.
42 Mechanical Specifications General The units shall be dedicated downflow or horizontal airflow . The operating range shall be between 115°F and 0°F (46.1°C and -17.8°C) in cooling as standard from the factory for all units. 60 HZ cooling performance shall be rated in accordance with ARI testing procedures.
43 Mechanical Specifications V ariable Frequency Drives (VFDs) shall be factory installed and tested to provide supply fan motor speed modulation. The VFD shall receive a 2-10 VDC signal from the unit.
Library Product Literature Product Section Unitary Product Rooftop Model 000 Literature T ype Data Sales Catalog Sequence 10 Date April 1999 File No. PL-UN-R T -000-DS-10-499 Supersedes RT -DS-10 12/94 Ordering No. R T -DS-10 The T rane Company International Unitary Systems Group 3600 Pammel Creek Road La Crosse, WI 54601-7599 www .
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Trane RT-DS-10 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Trane RT-DS-10 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Trane RT-DS-10, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Trane RT-DS-10 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Trane RT-DS-10, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Trane RT-DS-10.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Trane RT-DS-10. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Trane RT-DS-10 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.