Manuel d'utilisation / d'entretien du produit DH500ACDC du fabricant System Sensor
Aller à la page of 12
D500-0 7-00 1 I56-432-1 1R DH500ACDC Intelligent Air Duct Smoke Detector Housing INST ALLA TION AND MAINTENANCE INSTRUCTIONS 3825 Ohio A venue , St. Charles, Illinois 60 174 1-800-SENSOR2, F AX: 63 0-377-6495 www .
D500-0 7-00 2 I56-432-1 1R The DH500A CDCs ar e built to operate on 120/240 V A C or 24 V A C/DC. T wo form-C (SPD T) relay contacts are av ail- able for control purposes. T wo LEDs on each detector latch on to pro vide a local alarm indication. R emote alarm indi- cation is made possible b y using the auxiliary alarm output (see Figur e 5).
D500-0 7-00 3 I56-432-1 1R Exception: Where it is physically impossible to locate the detector accordingly , the detector can be positioned closer than six duct widths , but as far as possible from the open- ing, bend, or deflection plates. Step 3. Mount Duct Housing R emov e the duct housing cover .
A. Installation for Ducts Less Than 8 Feet Wide 1. If the inlet tube is longer than the width of the air duct, drill a 3/4-inch hole in the duct directly opposite the hole alr eady cut for the inlet tube. If the inlet tube is shorter than the width of the air duct, install the end cap into the inlet tube as shown in Figure 3.
av ailable at most plumbing supply houses, may be used. This flange/connector mounting technique makes the initial installation easier because a 1- inch to 1-1/4-inch hole may be drilled where the flange/connector will be used. It is easier to push the inlet tube through the lar ger hole .
ALARM SIGNAL (+) AUX POWER (–) 2 6 (+) (–) DUCT DETECTOR DH500ACDC PA400 (OPTIONAL) AUDIBLE ALERT ALARM SIGNAL (+) AUX POWER (–) 2 6 (+) (–) DUCT DETECTOR DH500ACDC RA400Z (OPTIONAL) REMOTE (L.
Step 7. Per form Detector Check 7.1 Air Flow 1. T o verify sufficient sampling of ducted air , use a manom- eter to measure the differential pr essure created from air flo w acr oss the sampling tubes. The pr essure should measure no less than 0.0 1 inches of w ater and no greater than 1.
Step 8. Install the Cover Install the cover using the four scre ws . Be certain filters are installed as specified in Step 6. Make sure that the cover fits into the base gr oove and that all gaskets ar e in their proper positions. Tighten the four cov er scre ws to 1 0 in-lbs .
1. T urn off power to the system. 2. R emove and inspect sampling tube filter s. 3. If filters ar e heavily coated with dirt, r eplace them with new filter s. If they ar e not heavily coated, use a vacuum cleaner or compressed air nozzle to remo ve dust, then install the filters .
A ccessories P art No. R emote LED RA400ZA Piezo Alert Sounder P A400 R eplacement Filter s F36-05-00 Magnet M02-04-00 End Plug F or Sampling T ube P48-2 1-00 Installation Kit (P arts bag) A2650-0 1 I.
Sy stem Sensor warrants its enclosed air duct smoke detector to be free from defects in materials and workmanship under normal use and ser- vice for a period of three y ears fr om date of manufactur e. S ystem Sensor makes no other e xpress warr anty for this air duct smok e detector .
D500-0 7-00 12 I56-432-1 1R © 200 1 S ystem Sensor DETECTOR TEST LOG Detector Identification Infor mation Manufacturer and Serial Date Detector Model:______________________ Number: __________________.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté System Sensor DH500ACDC c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du System Sensor DH500ACDC - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation System Sensor DH500ACDC, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le System Sensor DH500ACDC va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le System Sensor DH500ACDC, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du System Sensor DH500ACDC.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le System Sensor DH500ACDC. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei System Sensor DH500ACDC ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.