Manual 2100-467K Page 1 of 24 SINGLE P ACKAGE AIR CONDITIONERS MODELS P A13242-A P A13302-A P A13362-A P A13362-B P A13422-A P A13422-B P A13422-C P A13482-A P A13482-B P A13482-C P A13602-A P A13602-.
Manual 2100-467K Page 2 of 24 CONTENTS Getting Other Informations and Publications ......... 3 General Instructions Important ................................................................. 4 Shipping Damage .........................................
Manual 2100-467K Page 3 of 24 Getting Other Information and Publications These publications can help you install the air conditioner or heat pump. Y ou can usually nd these at your local library or purchase them directly from the publisher . Be sure to consult current edition of each standard.
Manual 2100-467K Page 4 of 24 General InstructIOns ImPOrt ant The equipment covered in this manual is to be installed by trained, experienced service and installation technicians. All duct work, supply and return ducts, must be properly sized for the design airow requirement of the equipment.
Manual 2100-467K Page 5 of 24 t able 2 electrIcal sPecIFIca tIOns model P a13242-a P a13302-a P a13362-a P a13362-b P a13422-a P a13422-b P a13422-c P a13482-a P a13482-b P a13482-c P a13602-a P a1360.
Manual 2100-467K Page 6 of 24 t able 3 OPtIOnal FIelD Inst alleD hea ter P acKaGes Onl Y t O be useD WIth the mODels InDIca teD heater Package model V olts & Phase P a13242-a P a13302-a P a13362-a.
Manual 2100-467K Page 7 of 24 t able 4 OPtIOnal FIelD Inst alleD electrIc hea ter t able IMPORT ANT : While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance with the National Electrical Code and all existing local codes.
Manual 2100-467K Page 8 of 24 FIGure 1a DImensIOns OF unIts Return open i ng Dr ain a cc e ss S upp ly open i ng Hi gh volt age k no ck out Lo w volt age k no ck out a cc e ss door C on trol pane l do.
Manual 2100-467K Page 9 of 24 FIGure 1b DImensIOns OF unIts A B C D F E D A H G UN IT A B C D E F GH PA /PH1324, 1330, 1336 7 3/16" 38 13/16" 36 3/4" 1 3/8" 33 5/8" 35 1/2&quo.
Manual 2100-467K Page 10 of 24 Inst alla tIOn lOca tIOn General The unit must be located outside, or in a well ventilated area. It must not be in the space being heated or cooled.
Manual 2100-467K Page 1 1 of 24 36 " mi n. 24 " mi n. 24 " mi n. T he dist an ce be tw een 1 inch cl ea r an ce A cc e ss Air I nl et Com p- N ea res t Structu re Air I nl et S upp ly a.
Manual 2100-467K Page 12 of 24 FIGure 4 eleV a teD mOuntInG Pla tFOrm Bot h l eg s mus t re st on su rface o f pla tf o rm 32 °F or l owe r c lim a te 12" mi n .
Manual 2100-467K Page 13 of 24 FIGure 5 cOnDensa te DraIn traP 5. Other Inst alla tIOns – Many other installations are possible with the packaged air conditioner . No matter what the installation, always consider the following facts: A. Insure that the discharge air is not obstructed in any way so as to cause operation difculties.
Manual 2100-467K Page 14 of 24 t able 6 thermOst a t WIre sIze transFOrmer t aPs 230/208V , 1 phase and 3 phase equipment employ dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap.
Manual 2100-467K Page 15 of 24 E Y 1120 - 445 TH 5220 D 1151 Lo w Voltage Wiring L 2 C O 1 Unit Contr ol Panel Blo ck Y C G R W1 W2 E F Y1 C G R W1 O Y2 W2 D A E L A UX R G E B RC 3 L B Thermostat S u.
Manual 2100-467K Page 16 of 24 st art uP These units require R-410A refrigerant and Polyol Ester oil. General: 1. Use separate service equipment to avoid cross contamination of oil and refrigerants. 2. Use recovery equipment rated for R-410A refrigerant.
Manual 2100-467K Page 17 of 24 three Phase scrOll cOmPressOr st art uP InFOrma tIOn (Models P A13362-B; P A13422-B, -C; P A13482-B, -C; P A13602-B, -C) All units with three phase scroll compressors are equipped with a three phase line monitor to prevent compressor damage due to phase reversal.
Manual 2100-467K Page 18 of 24 lOW Pressure sWItch, bYP ass, anD lOcKOut sequence (standard Feature) If the low pressure switch opens for more that 120 seconds, the compressor contactor will de-energize and go into a soft lockout.
Manual 2100-467K Page 19 of 24 F an blaDe settInGs Shown in Figure 8 are the correct fan blade setting dimensions for proper air delivery across the outdoor coil.
Manual 2100-467K Page 20 of 24 (continued on Page 20 in t able 1 1) t able 9 Pressure t able cOOlInG Air T emperature Entering Outdoor Coil Degree F LOW SIDE PRESSURE +4 PSIG HIGH SIDE PRESSURE +10 PSIG T ablesbaseduponratedCFM(airow)acrosstheevaporatorcoil.
Manual 2100-467K Page 21 of 24 t able 10 Pressure t able LOW SIDE PRESSURE +4 PSIG HIGH SIDE PRESSURE +10 PSIG T ablesbaseduponratedCFM(airow)acrosstheevaporatorcoil.
Manual 2100-467K Page 22 of 24 suctIOn anD DIscharGe tube brazInG Compliant Scroll compressors have copper plated steel suction and discharge tubes. These tubes are far more rugged and less prone to leaks than copper tubes used on other compressors.
Manual 2100-467K Page 23 of 24 FIGure 10 NOTE: Bard Models PA13242; PA13302; PA13362-A, -B; PA13422-A, -B, -C; PA13482-A, -B, -C; PA13602-A, -B, -C contain the X13-Series Motors. trOubleshOOtInG Ge x13-serIes ecm2.3 ™ mOt Ors If the Motor is Running 1.
Manual 2100-467K Page 24 of 24 FIGure 1 1 trOubleshOOtInG Ge x13-serIes ecm2.3 ™ mOt Ors cOnt’D. Model X13 Communication Diagnostics The X13 motor is communicated through 24 V AC low voltage (Thermostat Control Circuit W iring). 1. Start with unit wiring diagram to conrm proper connections and voltage (see Figure 11).
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Bard PA13422-C c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Bard PA13422-C - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Bard PA13422-C, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Bard PA13422-C va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Bard PA13422-C, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Bard PA13422-C.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Bard PA13422-C. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Bard PA13422-C ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.