1 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. INST ALLA TION INSTRUCTIONS VENTED GAS FIREPLACE HEATERS - DIRECT VENT MODELS P/N 700,020M REV. M 11/2004 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors or liquids in the vicin- ity of this or any other appliance.
2 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. Figure 1 Installation must conform to local codes. In the absence of local codes, installation must com- ply with the current National Fuel Gas Code, ANSI Z223.1. (In Canada, the current CAN-1 B149 installation code.
3 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. h t i w s l e d o M t l o v i l l i M e v l a V s a G d e t a l u d o M - y l l a u n a M s a G e n a p o r P d n a l a r u t a N s r e b m u N l e d o M) H / U T B ( e t a r t u p n I 0 0 4 - T D 0 0 4 - R D 0 0 5 , 7 1 o t 0 0 5 , 3 1 .
4 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. Figure 2 Figure 3 APPLIANCE AND VENT CLEARANCES The appliance is approved with zero clearance to combustible materials on all sides (as de- tailed in.
5 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. h c t i P f o o R H ) t e e f ( 2 1 / 6 o t t a l F0 . 1 2 1 / 7 o t 2 1 / 6 r e v O5 2 . 1 2 1 / 8 o t 2 1 / 7 r e v O5 . 1 2 1 / 9 o t 2 1 / 8 r e v O0 . 2 2 1 / 0 1 o t 2 1 / 9 r e v O5 . 2 2 1 / 1 1 o t 2 1 / 0 1 r e v O5 2 .
6 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. Figure 8 EXTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS * n o i t a l l a t s n I n a i d a n a C* * n o i t a l l a t s n I S U , h c r o p , a d n a r e v , e d a r g e v o b a e c n a r a e l C = A .
7 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. *34 ⁵⁄₁₆ (872) Back wall of chase/enclosure (including any finishing materials) a 8 ³⁄₁₆ (208) b Note- Venting requirements for rear vent applications in corner installations - - the round termination (SV4.
8 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 21 ¹⁄₂ (546) 13 (330) ¹⁄₂ (13) 1 ⁵⁄₈ (42) 8 ¹¹⁄₃₂ (212) 3 (76) T op View NOTE - Eyebrow hood shown as positioned in louvered front model.
9 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. T R A H C H T G N E L N O I T C E S T N E V l a n i m o N h t g n e L n o i t c e S ) s e h c n i ( 62 14 26 38 4 T O T A L Q T Y n o i t c e S t e N.
10 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 10 ¹⁄₂ ” Min. (267 mm) 10 ¹⁄₂ ” Min. (267 mm) First Vent Component Align the dimple (four places) with the opening of the locking incline channel on appliance collar . T wist vent component clockwise to engage and seal.
11 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. Framing Dimensions for Roof Pitch C D 0/12 10 ¹⁄₂ in. 10 ¹⁄₂ in. (267 mm) (267 mm) 6/12 10 ¹⁄₂ in. 12 in. (267 mm) (305 mm) 12/12 10 ¹⁄₂ in. 17 ³⁄₄ in. (267 mm) (451 mm) SV4.
12 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. Figure 24 - Rear Vent - ONE 90 DEGREE ELBOW Figure 23 - Top Vent - STRAIGHT Figure 25 - Top Vent - TWO 90 DEGREE ELBOWS VERTICAL VENT FIGURES/TABLES Note: Secure Vent (rigid vent pipe) is shown in the figures; Secure Flex (flexible vent pipe) may also be used.
13 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. Figure 26 - Rear Vent - THREE ELBOWS Figure 27 - Top Vent - THREE ELBOWS VERTICAL VENT FIGURES/TABLES (continued) E E L B A T VM M U M I N I HH + 1 m u m i x a M t e e f) m (t e e f) m ( 1) 5 0 3 . 0 (5 ) 2 5 .
14 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. Vertical Rise SV4.5E90 Elbow Horizontal / Inclined Run SV4.5HTSSL T ermination Shown *Ceiling Firestop/Spacer (SV4.5BF) SV4.5L6/12/24/36/48 Vent Sections Support Bracket Spacing Every 5 ft (1.52 m) See Figure 17 on page 10 for vertical vent section support.
15 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. *Firestop/Spacer (SV4.5HF) shown on the exterior side of the wall. It may also be installed on the interior side.
16 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. SFHRK Snorkel Cap – The snorkel cap is de- signed to be fitted into a basement window box. The SFHRK cap is for use with flex vent The vertical distance between the inlet and outlet of the cap is 28 in.
17 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. Figure 37 - Top Vent - ONE 90 DEGREE ELBOW - ELBOW CONNECTION NOT DIRECTLY AT APPLIANCE Figure 38 - Rear Vent - TWO 90 DEGREE ELBOWS Figure 36 - Top.
18 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. Refer to Table 3 on page 16 for an aid in venting component selection for a particular range of exterior wall thicknesses when using the square (SV4.5HTS), small square (SV4.5HTSS) or the round (SV4.
19 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. D. Install Firestop/Spacers at ceilings and walls - When Secure Flex penetrates a wall or ceiling, a firestop/spacer is required: use the SF4.5 BF firestop/spacer for ceilings and the SF4.5 HF firestop/spacer for walls.
20 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 1. If any of the original wire as supplied must be replaced, 1. it must be replaced with T ype AWM 105 ° C – 18 GA.
21 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. FBK-250 Blower Kit (See Figure 46 ) An electrical outlet box is provided for the instal- lation of the FBK-250 forced air blower kit. Electrical power must be provided to this box to operate these blowers.
22 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. Figure 52 Electronic Appliance Checkout To light the burner, turn ‘ ON ’ the optional remote wall switch and turn the gas control switch to the “ ON ” position. Ensure the ignitor lights the pilot.
23 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. Adjustment Rod Up (Fully Open Position) Air Shutter Burner T ube Adjusting Set Screw Adjustment Rod Down (minimum air opening position) Combustible .
24 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. * All compressed flex vents can be expanded up to two times. d e t s i L x e l F e r u c e S s t n e n o p m o C ™ .
25 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. * All compressed flex vents can be expanded up to two times. INSTALLATION ACCESSORIES (Continued) d e t s i L x e l F e r u c e S s t n e n o p m o C ™ . t a C . o N . o N l e d o Mn o i t p i r c s e D .
26 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. SIT Millivolt Gas Valve Pressure Regulator Remove These Components Figure 59 Step 4. Millivolt Appliances - SIT Systems a. See Figure 59 and the instructions provided with the kit. Using a Torx T20, remove and discard the three pressure regulator mounting screws.
27 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. Pilot for SIT Millivolt Gas Valve Orifice Strip T ab Pilot Hood Position After Loosening Hex Fitting 1/4 T urn Push T ab to Set Gas T ype Usage Note - Orifice Strip T ab May Be Randomly Located On Any Side Of The Hex Fitting Hood Alignment Hood 7/16 in.
28 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. Step 8. Reassemble all removed components by reversing the procedures outlined in the preceding steps.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Superior DR-400CMN c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Superior DR-400CMN - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Superior DR-400CMN, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Superior DR-400CMN va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Superior DR-400CMN, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Superior DR-400CMN.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Superior DR-400CMN. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Superior DR-400CMN ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.