L i n e a B al a nc e d F lu e C on v ec t or Fi r e I ns t r uc t io n s f or Us e , I ns t a ll a ti o n a nd Se r vi c i ng Fo r use in GB , IE (G rea t Bri ta in and Ei re ) PR0731 Issue 8 (September 2006) IMPORTANT Do not attempt to burn rubbish in this appliance.
2 CONTENTS COVERING THE FOLLOWING MODELS 8651 P8651 PAGE APPLIANCE COMMISSIONING CHECKLIST 3 USER INSTRUCTIONS 4 INSTALLATION INSTRUCTIONS 8 Technical Specifications 8 Site Requirements 9 Installation.
3 FLUE CHECK PASS FAIL 1. Flue is correct for appliance 2. Flue flow test N/A 3. Spillage test N/A GAS CHECK 1. Gas soundness & let by test 2. Standing pressure test mb 3. Appliance working pressure (on High Setting) mb NB All other gas appliances must be operating on full 4.
4 USER INSTRUCTIONS 1.1 A competent person must carry out installation and servicing. 1.2 In all correspondence, please quote the appliance type and serial number, which can be found on the data badge located on a plate under the control valve.
5 2.5 To set the room temperature 2.5.1 Following on from section 2.4, once the room temperature is flashing on the display, it can be set. 2.5.2 Press either the ( ) button (10) or the ( ) button (13) to either increase or decrease the temperature. 2.
4.1 This is a safety feature incorporated on this appliance which automatically switches off the gas supply if the pilot goes out and fails to heat the thermocouple. 5.1 The surface coating on the ceramic panel used in your GAZCO fire will "burn off" during the first few hours of use producing a harmless and temporary odour.
7 USER INSTRUCTION 10.1 If the Linea is fitted with a Designio front, access to the batteries can be achieved by simply dropping the lower front access cover. 10.2 If the Linea is fitted with a Plano or Vetro front, access to the batteries can be achieved through the access hole in the casing below the unit.
8 INSTALLATION INSTRUCTIONS TECHNICAL SPECIFICATION COVERING THE FOLLOWING MODELS 8651 P8651 Efficiency Class I Flue Outlet Size 100 Ø / 152mm Ø Gas Inlet Connection Size 8mm Ø Wall Thickness - Min.
9 INSTALLATION INSTRUCTIONS SITE REQUIREMENTS NOTE: This appliance can only be installed in conjunction with the flue supplied. 1.1 The flue must be sited in accordance with BS5440: Part 1 (latest edition).
10 TIMBER FRAMED BUILDINGS 1.5 It will be necessary to provide additional clearance when the flue passes through a wall containing any combustible materials so as to prevent a fire hazard.
11 INSTALLATION INSTRUCTIONS SITE REQUIREMENTS 4.4 All combustible materials must be removed from behind the appliance. See diagram 6. 4.5 The Linea may be mounted at any height, however, there must be a minimum clearance of 150mm (6") between the bottom edge of the appliance and the floor.
12 IMPORTANT: BEFORE THE APPLIANCE CAN BE OPERATED THE REMOTE HANDSET MUST BE TUNED TO THE CONTROL BOX SITUATED UNDER THE APPLIANCE. IF THIS PROCEDURE IS OMITTED THE APPLIANCE CAN ONLY BE LIT USING THE TOUCH PAD. SEE SECTION 3. ENSURE THAT THE APPLIANCE IS CORRECTLY ADJUSTED FOR THE GAS TYPE AND CATEGORY APPLICABLE IN THE COUNTRY OF USE.
2.7 The flue can now be cut to size. Measure the thickness of the wall, then deduct 12mm. This is the length required when measuring from the line on the flue label. See diagram 3. 2.8 Attach the flue to the appliance and seal using the aluminium tape.
3.1.3 The remote handset must now be programmed. Push the ON / OFF button (11), the ON or OFF display will start flashing. Then press the ON / OFF button (11), and the ( ) (10) and ( ) (13) buttons at the same time. Immediately after press the SET button (12) once.
15 IGNITION FUNCTIONAL CHECK 1 PILOT WILL NOT LIGHT Ensure there is no debris around the pilot assembly, (e.g. soot, etc.) which could short the spark, clean the area. Operate the valve. Is there a spark? Consult User Instructions and retry. Check alignment of pilot burner head, change the ignition lead.
16 PILOT WILL NOT STAY LIT OR FIRE GOES OUT IN USE Ensure there is no debris around the pilot assembly, (e.g. soot etc.) Check for fluff in the pilot aeration hole. See the diagram in Replacing Parts section. Problem is with the pipework or fittings which lead to the fire.
17 2.4 Raise the burner from the slot in the bracket, pull the burner forward and slide to the left to clear the injector. Take care not to lose the spring. 2.5 Replace in reverse order ensuring the spring is located over the stud on the burner and the tab on the bracket.
18 4.7 Reassemble in reverse order and replace the pilot gasket with a new one. 4.8 Check for gas leaks. 5.1 To gain access to the pilot pipe, it is easier if the thermocouple is removed first. To do this follow section 7. 5.2 Undo the pilot pipe from the top of the gas valve and from under side of the pilot burner.
19 7.2 Disconnect the thermocouple from the gas valve. See diagram 8 arrow C. 7.3 Undo the thermocouple nut in the back of the pilot burner by half a turn. This will release the thermocouple. 7.4 Disconnect the two leads noting the orientation. The lead with the red tape on is connected to the thermocouple spade nearest the gas valve.
10.3 Remove the main burner as described in section 2. 10.4 Remove the locknut from the injector. See diagram 15. 10.5 Remove the feed pipe from the gas valve. See diagram 16 arrow C. 10.6 Remove the feed pipe with the injector attached from the appliance.
21 SERVICING INSTRUCTIONS REPLACING PARTS 11.1 Remove the lower cover. See diagram 6. 11.2 Locate the control box and remove all of the wires connected to the box. NOTE THEIR POSITIONS. 11.3 Remove the two screws from the box. See diagram 17, arrow A.
22 SERVICING INSTRUCTIONS REPLACING PARTS In order to change between gas types it will be necessary to change the following items. Main Injector Main Burner Pilot Injector Control Valve Control Box Thermocouple ( NG to LPG only). LPG to NG no change).
23 SERVICING INSTRUCTIONS REPLACING PARTS 15. SHORT SPARES LIST Component NG LPG PROPANE BUTANE BURNER UNIT GC0104 GC0105 GC0106 MAIN INJECTOR IN0053 IN0052 PILOT INJECTOR PI0069 PI0070 THERMOCOUPLE P.
24 SERVICE RECORDS 1ST SERVICE Date of Service:........................................................................... Next Service Due:....................................................................... Signed:................................
Gazco Limited, Osprey Road, Sowton Industrial Estate, Exeter, Devon, England EX2 7JG Tel: (01392) 261999 Fax: (01392) 444148 E-mail: info@gazco.com A member of the Stovax Group.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Stovax GAZCO Linea Balanced Flue Convector Fire c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Stovax GAZCO Linea Balanced Flue Convector Fire - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Stovax GAZCO Linea Balanced Flue Convector Fire, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Stovax GAZCO Linea Balanced Flue Convector Fire va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Stovax GAZCO Linea Balanced Flue Convector Fire, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Stovax GAZCO Linea Balanced Flue Convector Fire.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Stovax GAZCO Linea Balanced Flue Convector Fire. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Stovax GAZCO Linea Balanced Flue Convector Fire ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.