/ Mar le y Sigma F Ser ies Cooling T ower / Engineer ing Data & Specifications.
Mar ley / Sigma F Ser ies Cooling T ower / T able of Contents Engineer ing Data Sc hematic 4 Support 5 Piping 7 T emperature Control 1 0 Environmental 1 1 Specifications / Base Base 12 Thermal P erfor.
Mar ley / Sigma F Ser ies Cooling T ower / 3 T he Sigma F Series is a field-erected, crossflow , fiberglass-str ucture cooling to wer designed to ser ve normal air conditioning and refrigeration systems as w ell as medium sized industrial loads.
Mar ley / Sigma F Ser ies Cooling T ower / Engineer ing D ata : Schematic 4 H B T OP OF F AN CYLINDER BASE OF T OWER COLUMNS F AN DECK 13'-6" N O T E 1 U se this bulletin for preliminary layouts only . Obtain current drawings from y our Marley representative.
Mar ley / Sigma F Ser ies Cooling T ower / Engineer ing D ata : Support 5 A SP ACES A T 4'-0" = L W OVERALL OF BASIN SUMP OVERFLOW MAKEUP V AL VE INTERMEDIA TE BEAM AIR INLET F ACE AIR INLET.
Mar ley / Sigma F Ser ies Cooling T ower / Engineer ing D ata : Support 6 A SP ACES AT 4'-0" = L 6 " MIN TYP SUMP SEE NOTE 7 OPTIONAL PA RTITION W ALL FOR INDIVIDU AL CELL OPERA TION B .
Mar ley / Sigma F Ser ies Cooling T ower / Engineer ing D ata : Piping Plan 2 7 C MOTOR C F COLUMN AND ANCHOR BOLT TYP. SINGLE CELL D TYP. MULTICELL C L COLUMN AND ANCHOR BOLT C L INLET C L TOWER AND .
Mar ley / Sigma F Ser ies Cooling T ower / Engineer ing D ata : Piping Plan 3 8 C H MO TO R C F COLUMN AND ANCHOR BOL T TY P. SINGLE CELL D TY P. MUL TICELL C L COLUMN AND ANCHOR BOL T C L RISER C L T.
Mar ley / Sigma F Ser ies Cooling T ower / Engineer ing D ata : Piping Plan 4 9 C H MO TO R C F COLUMN AND ANCHOR BOL T TY P. SINGLE CELL D TY P. MUL TICELL C L COLUMN AND ANCHOR BOL T C L RISER AND HEADER C L T OWER AND F AN C L FA N C L FA N C L RISER C L H E G F AN FLANGE IS 3 / 4 " THICK.
Mar ley / Sigma F Ser ies Cooling T ower / Engineer ing D ata: Energ y Management 10 CAUTION The cooling tower must be located at suc h distance and direction to avoid the possibility of contaminated tower disc harge air being drawn into building fresh air intake ducts.
Mar ley / Sigma F Ser ies Cooling T ower / Engineer ing D ata: Envir onmental 11 Sound Control Sound produced by a Sigma to wer operating in an unobstructed environment will meet all but the most restrictiv e noise limit a- tions—and will react fa vorably to natural at tenuation.
Specifications Specification V alue Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Base 12 1.0 Base: 1.1 Furnish and inst all an induced-draft, crossflow-type, field-erected, structural fiberglass-framed, P VC film-fill, industrial- duty cooling tower of _____ cell(s), as shown on Plans.
Specifications Specification V alue Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Base 13 2.0 Ther mal P erfor mance: 2.1 The tow er shall be capable of cooling _____ GPM of water from ____ °F to _____ °F at a design entering air wet- bulb temperature of _____ °F .
Specifications Specification V alue Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Base 14 3.0 Constr uction: 3.1 The tow er shall be capable of with- standing water having a pH of 6.
Specifications Specification V alue Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Base 15 4.0 F an Deck and F an Cylinder: 4.1 The fan dec k shall act as a working platform for maintenance personnel.
Specifications Specification V alue Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Base 16 5.4 A st ainless steel oil fill and drain line shall extend from the gear reducer to the vicinit y of the motor , and shall be equipped with a bronze-bodied oil lev el sight-glass gauge.
Specifications Specification V alue Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Base 17 7.0 Hot W ater Distribution Syst em: 7.1 The mechanical equipment support/ crossover pipe for each cell shall be equipped with a flange for the attachment of customer supply piping.
Specifications Specification V alue Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Base 18 9.0 Access and Saf ety: 9.1 Single cell towers shall include a 33" (838 mm) wide by 61" (1 .55 m) high molded FRP access door in one endwall casing for access to the inte- rior of the tow er .
Specifications Specification V alue Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Base 19 11.0 Scope of Wor k : 11.1 The cooling tow er manufact urer shall be responsible for the design, fabrica- tion, and deliver y of materials to the project site, and for the erection of the tower over supports pro vided by others.
Specifications Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Options 20 Specification V alue Cold W ater Basin Options Stainless Steel Cold W ater Basin : 10.
Specifications Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Options 21 Specification V alue and a solid state circuit board for tem- perature control and low water cutof f . A control probe shall be located in the basin to monitor water lev el and tem- perature.
Specifications Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Options 22 Specification V alue Plenum W alkwa y: 9.1 Add the following to the end of this paragraph: Pro vide a 30" (7 62 mm) minimum wide walkwa y extending from one endwall access door to the other through the length of the tow er .
Specifications Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Options 23 Specification V alue Air Inlet Screens: 6.3 Add the following paragraph in the Fill, Louver s and Drift Eliminator s section: The air inlet faces of the tow er shall be covered by 1" mesh stainless steel w elded wire screens.
Specifications Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Options 24 Specification V alue Control Options Control Syst em: 5.7 Add the following paragraphs in the Mechanical Equipment .
Specifications Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Options 25 Specification V alue F an Motor V ariable Speed Dr ive: Marle y All W eather ACH550 System 6.
Specifications Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Options 26 Specification V alue and cooling is no longer required. The fluid cooler manufact urer shall supply VFD st art-up assistance.
Specifications Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Options 27 Specification V alue ■ Unless specified otherwise, a Robertshaw or Metrix switch will be provided. Double-pole, double-throw models are also avail- able. If purc hased in conjunction with the Control System, it is also factory- wired.
Specifications Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Options 28 Specification V alue Fiberglass Ladder: 9.3 Change paragraph 9.3 to read as follows: One endwall of the tow er shal.
Specifications Mar ley / Sigma F Ser ies Cooling T ower / Specifications: Options 29 Specification V alue.
7 4 01 WEST 1 29 STRE ET OVER LAN D P AR K, KANSAS 6 621 3 U N ITE D ST A TES 913 6 64 7 400 spxcooling@ct.spx.com spxcooling.com In the interest of techno logical progr ess, all products are subject to design and/or material change without notice. ©2008 SPX Cooling T ech nologies , Inc.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté SPX Cooling Technologies FSIG-TS-08A c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du SPX Cooling Technologies FSIG-TS-08A - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation SPX Cooling Technologies FSIG-TS-08A, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le SPX Cooling Technologies FSIG-TS-08A va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le SPX Cooling Technologies FSIG-TS-08A, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du SPX Cooling Technologies FSIG-TS-08A.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le SPX Cooling Technologies FSIG-TS-08A. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei SPX Cooling Technologies FSIG-TS-08A ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.