HDV100A3 Command & Response Manual-1306cr Cover Page B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Model: HVD100A3 HDV100A3 Command Response Protocol Documentation Number: HDV100A3-4407CR International Headquarters B&B Electronics Mfg.
.
HDV100A3 Command & Response Manual-1306cr Table of Contents i B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Table of Contents INTRODUCTION..........................................
ii HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 WARNING! This Model HDV100A3 Converter Module allows you to connect to active J1708 / J1939 networks.
HDV100A3 Command & Response Manual-1306cr 1 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Introduction The HDV100A3 adapter has t.
2 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Intelligent Mode Command Protocol The HDV100A3 uses a simple protocol to comm unicate to vehicle bus.
HDV100A3 Command & Response Manual-1306cr 3 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Formatting the Control Bytes The 2 nd byte is “Num ber of Control Byt es” to follow and always precedes the control field.
4 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Detailed Description of General Function Codes Command Acknowledgement All comma nds sent to the device will be acknowledged.
HDV100A3 Command & Response Manual-1306cr 5 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 RS-232 Baud Rate Setup To set the baud rate for the RS-232 port, set a general comm and code of 08.
6 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Bits 1 and 0 set the word l ength Bit 0 Bit 1 Word Length 0 0 5 0 1 6 1 0 7 1 1 8 (default) Default value.
HDV100A3 Command & Response Manual-1306cr 7 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Setting Baud 1, Baud 2 Baud Rate Setup .
8 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Baud Rate Example To set the PC baud rate to 57,600 baud, N,8,1, form at the message as follows.
HDV100A3 Command & Response Manual-1306cr 9 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Time Stamp Information The HDV100A3 supports a four-byte rolling time stamp with a resolution of 1.
10 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Byte Number Byte Value Function 1 01 S.
HDV100A3 Command & Response Manual-1306cr 11 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Master Reset Command The master reset com mand all ows the HDV100A3 to be reset from the PC.
12 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 J1708 Commands Receiving Data from the.
HDV100A3 Command & Response Manual-1306cr 13 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Byte number Byte value (hex) Byte Func.
14 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Transmitting Data to the J1708 Bus The HDV100A3 supports standard J1708 comm ands of up to 21 bytes.
HDV100A3 Command & Response Manual-1306cr 15 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 After sending a transmit me ssage to the HDV100A3 you will get the confirmation message if the checksum is correct.
16 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 J1708 Message Filter The J1708 message filter will operate on 4 different MID’s. Only m essages with the same MID as set in the filter will be sent to the PC.
HDV100A3 Command & Response Manual-1306cr 17 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Broadcast Message The HDV100A3 supports one broadcast message.
18 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 To stop broadcast transmi ssion it is not necessary t o send the whole message. The message below will stop broadcast transmission.
HDV100A3 Command & Response Manual-1306cr 19 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 J1939 Commands The J1939 protocol is sim ilar to the J1708 prot ocol. The message starts wi th Start of Frame byt e 01.
20 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 wise to set the receiver off when not in use. Sending the Start Receive clears the mask. This renders the filter function useless.
HDV100A3 Command & Response Manual-1306cr 21 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Data messages received from the HDV 10.
22 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 A message received from the HDV will b.
HDV100A3 Command & Response Manual-1306cr 23 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Transmit Data to J1939 Bus Byte Number.
24 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 The mask can be used to look at a grou.
HDV100A3 Command & Response Manual-1306cr 25 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 2. Set the “Mask” to the desired patt ern (01, 06, 02, 04, XX, XX, XX, XX, 00, CS). 3.
26 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 J1939 Header Worksheet This worksheet will aid in filling ou t/decoding the J1939 arbitration field.
HDV100A3 Command & Response Manual-1306cr 27 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Error Codes Error Code Format: Byte Nu.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté B&B Electronics Command Response Protocol HVD100A3 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du B&B Electronics Command Response Protocol HVD100A3 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation B&B Electronics Command Response Protocol HVD100A3, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le B&B Electronics Command Response Protocol HVD100A3 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le B&B Electronics Command Response Protocol HVD100A3, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du B&B Electronics Command Response Protocol HVD100A3.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le B&B Electronics Command Response Protocol HVD100A3. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei B&B Electronics Command Response Protocol HVD100A3 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.