Sierra Monitor Corporation 1991 Tarob Court, Milpitas, CA 95035 (408) 262-6611 Applicability & Effectivity MODEL 5000 S E N T R Y GAS MONITORING SYSTEM Version 6 Sensors Service APPLICABILITY & EFFECTIVITY Effective for all Sentry systems manufactured after September 1, 1995.
SMC sierra monitor corporation Sentry Instruction Manual - Version 6 SERVICE Page: 69 7.5 COMBUSTIBLE GAS SENSOR MODULE (5100-02) 7.5.1 DESCRIPTION The Combustible Gas M odule includes the sensor and electronic assembl y installed in an explosion proof housing.
SMC sierra monitor corporation Sentry Instruction Manual - Version 6 SERVICE Page: 70 3. Using a Sierra Monitor M odel 1200-26 Gas Calibrator with a Si erra Monitor M odel 5358- 00 calibration adapter, or M odel 5360 Gas Delivery Fitting. Apply the calibratio n gas at a flow rate of 100 cc/min.
SMC sierra monitor corporation Sentry Instruction Manual - Version 6 SERVICE Page: 71 7.5.5 COMBUSTIBLE GAS SCALING FACTORS For combustible gas monitoring, a calibration standard of Me thane or Propan.
SMC sierra monitor corporation Sentry Instruction Manual - Version 6 SERVICE Page: 72 7.6 OXYGEN MODULE (5100-03) 7.6.1 DESCRIPTION The Oxygen Module includes the electronic assembly i nstalled in an explosion proof housi ng and the electrochemical sensor connected to one hub of the enclosure.
SMC sierra monitor corporation Sentry Instruction Manual - Version 6 SERVICE Page: 73 Unscrew the old sensor from the conduit hub, screw in the new sensor and connect the wiring harness to the transmitter electronics. Repl ace the transm itter into the enclosure, make signal adjustm ents as described above, and replace the enclosure cover.
SMC sierra monitor corporation Sentry Instruction Manual - Version 6 SERVICE Page: 74 7.7 CARBON MONOXIDE MODULE (5100-04) 7.7.1 DESCRIPTION The Carbon Monoxide Module includes t he sensor and electronic assembly installed i n an explosion proof housing.
SMC sierra monitor corporation Sentry Instruction Manual - Version 6 SERVICE Page: 75 If sensor replacement is necessa ry remove the electronics from the housing and unplug the old sensor from the bottom board, rem ove it from the enclosure hub and reverse the procedure to install the new sensor.
SMC sierra monitor corporation Sentry Instruction Manual - Version 6 SERVICE Page: 76 7.8 HYDROGEN SULFIDE MODULE (5100-05) 7.8.1 DESCRIPTION Model 5100-05 Hydrogen Sulfide Sensor Module includes a sensor assembly and elect ronic assembly i nstalled in an explosion proof housi ng.
SMC sierra monitor corporation Sentry Instruction Manual - Version 6 SERVICE Page: 77 1. Confirm that sy stem power has been removed. 2. Remove the transmitter electronics board from the ma in housing and unplug the sensor harness from the transmitter electronics.
SMC sierra monitor corporation Sentry Instruction Manual - Version 6 SERVICE Page: 78 7.9 TOXIC GAS SENSOR MODULE 7.9.1 DESCRIPTION Toxic Gas Sensor Modules include t he following models and default r.
SMC sierra monitor corporation Sentry Instruction Manual - Version 6 SERVICE Page: 79 The SENSOR FAILURE message for toxic gas sensors does not indicate a specific fail ure of the sensor but indicates that the sensor is not correctl y connected to the electronics.
SMC sierra monitor corporation Sentry Instruction Manual - Version 6 SERVICE Page: 80 7. Apply span gas. Adjust the gain potenti ometer until TP10 = correct value as described above. To increase voltage at TP10 turn the gain potentiome ter counter clockwise.
SMC sierra monitor corporation Sentry Instruction Manual - Version 6 SERVICE Page: 81 7.10 AMMONIA SENSOR MODULE (5100-25) 7.10.1 DESCRIPTION The Amm onia Sensor Module includes a sensor assembly and electronic assembly installed in an explosion proof housing.
SMC sierra monitor corporation Sentry Instruction Manual - Version 6 SERVICE Page: 82 The SENSOR FAILURE message for am monia sensors does not indicate a specific failure of the sensor but indicates that the sensor is not co rrectly connected to the electronics.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Sierra Monitor Corporation 5000 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Sierra Monitor Corporation 5000 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Sierra Monitor Corporation 5000, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Sierra Monitor Corporation 5000 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Sierra Monitor Corporation 5000, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Sierra Monitor Corporation 5000.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Sierra Monitor Corporation 5000. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Sierra Monitor Corporation 5000 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.