Manuel d'utilisation / d'entretien du produit RuggedVDSL RS900L du fabricant RuggedCom
Aller à la page of 26
RuggedCom Inc. I 30 W hitmore Road, W oodbr idge, Ontario, C anada L4L 7Z4 Tel: (905) 856-528 8 I Fax: (905) 8 56-1995 I Toll Free: (888) 264-0006 Rugg edSwitch Rugg edSwitch Rugg edSwitch Rugg edSwitch RS9 00 RS9 00 RS9 00 RS9 00 L L L L 8-Port Ma naged Ethe rnet Switch with EoVD SL Upli nks Installatio n Guide www.
2 2007 RuggedCom Inc. All rights reserved Rev101 Federal Communications Commission Radio Frequency Interference Statement This equipmen t has been tested and found to comply with the limits for a Class A digital device pursuant to Part 1 5 of the FCC Rules.
3 2007 RuggedCom Inc. All rights reserved Rev101 Table of Contents 1 Product Overview ............................................................................................................................... 5 1.1 Functional Overview .......
4 2007 RuggedCom Inc. All rights reserved Rev101 Table of Figures Figure 1 - Front Panel Descr iption.............................................................................................................. 6 Figure 2 - Bottom Panel Description .
5 2007 RuggedCom Inc. All rights reserved Rev101 1 Product Overview 1.1 Functional Overview The RuggedSwitch RS900L is an 8 port industrially ha rdened, fully managed E thernet swi tch supporting Eth ernet over VDSL allowing up to 2.5 km LAN segments ove r telephone grade cable at up to 35 Mbp s.
6 2007 RuggedCom Inc. All rights reserved Rev101 1.3 Front Panel Description Failsafe Relay Power Port Ports 1-6 10/100Base-TX Ports 7 & 8 10/100Base-TX or 100Base-FX Port 9 Ethernet over VDSL.
7 2007 RuggedCom Inc. All rights reserved Rev101 1.4 Bottom Panel Description Failsafe Relay Console Port Power Port Chassis Ground Optional Din-Ra il Mounting Brack et Figure 2 - Bottom Pan el De.
8 2007 RuggedCom Inc. All rights reserved Rev101 2 Inst allation 2.1 Din Rail Mounting An optional DIN ra il-mounting bracket is available fo r the unit.
9 2007 RuggedCom Inc. All rights reserved Rev101 2.2 Power Supply Wiring and Ground ing 2.2.1 AC Pow er Suppl y Wiring and Gro unding Figure 4 - Power Supply Inp uts The AC powe r supply inputs should be connected as foll ows: 1. +/L should be connected to AC Line/Hot.
10 2007 RuggedCom Inc. All rights reserved Rev101 2.2.2 DC Pow er Suppl y Wiring and Gro unding Figure 5 - DC Power supply wi ring and grounding di agram The low vo ltage DC power supply features reve rse polarity protection and dual indep endent inputs.
11 2007 RuggedCom Inc. All rights reserved Rev101 2.2.3 Failsafe O utput Wiri ng The Failsafe output relay is provided to signal critical error conditions that may occur on the unit. The contact s are energized upon power up of the un it and remain energized until an alarm condition or powe r loss occurs.
12 2007 RuggedCom Inc. All rights reserved Rev101 2.2.4 Dielectric Strength T esting Units which a re to have dielectric strength testing (HIPOT te sting) done in the field must ha ve the braided ground cable disconnected during the test.
13 2007 RuggedCom Inc. All rights reserved Rev101 2.3 RS232 Console Port Wiring The RS232 po rt is used for configuring the unit. A stra ight-through serial cable with a DB-9 connector is re quired. There is no need to crossover the Transmit and Receive signals f rom the PC side since this has been done internally as is shown below.
14 2007 RuggedCom Inc. All rights reserved Rev101 3 Ethernet P ort s 3.1 RJ11 Ethernet over VDSL Port 3.1.1 Overview The Ethernet o ver VDSL (EoVDSL) port on RS900L operates in pairs with one configured as the Master and the other as the Slave.
15 2007 RuggedCom Inc. All rights reserved Rev101 3.1.2 Wiring VDSL typically opera tes over 2-wire CAT-3 wiring; howeve r, other categorized or uncatego rized twisted-pair wiring will work although the pe rformance will vary depending on the d istance and cable characteristics.
16 2007 RuggedCom Inc. All rights reserved Rev101 The unit can auto matically select the best bit-rate ba sed on current line conditions. If the line conditions deg rade (reducing the SNR) but the unit is able to maintain the link, an alarm will be triggered to no tify the user of the reduced SNR.
17 2007 RuggedCom Inc. All rights reserved Rev101 3.2 RJ45 Ethernet Ports The RS900L has se veral 10/100Base-TX ports that a llow connection to standard Category 5 (CAT- 5) unshielded twist ed-pair (UTP) cable with RJ45 male connectors.
18 2007 RuggedCom Inc. All rights reserved Rev101 NOTE: RuggedCo m does not recommend the use of coppe r cabling of any length for critical real- time substation a utomation applications.
19 2007 RuggedCom Inc. All rights reserved Rev101 3.3 Fiber Optic Ethernet Ports Depending on th e order code of the product, the un it can be equipped with several diffe rent fiber optic ports. The Tra nsmit (Tx) and Receive (Rx) connection s of each port must be properly connected and matched for proper link and operation.
20 2007 RuggedCom Inc. All rights reserved Rev101 4 T echnical Speci fications 4.1 Operating Environment Parameter Range Commen ts Ambient Operat ing Temperatu re -40 to 85 ° C Ambient Temp erature as measured f rom a 30 cm r adius surrounding the center of th e enclosure.
21 2007 RuggedCom Inc. All rights reserved Rev101 4.4 RJ11 Ethernet over VDSL Port Speci fications Data Port Media Distance Connect or Type VDSL CAT-3 UTP or ST P 2500m RJ11 Table 11 – RJ1 Ethernet o ver VDSL Port Spec ifications 4.
22 2007 RuggedCom Inc. All rights reserved Rev101 4.6 Fiber Optic Ethernet Port Specifications Speed Standard Mode / Connect or Tx λ λ λ λ (nm) Cable Type 2 ( µ µ µ µ m) Tx Pwr (dBm p eak).
23 2007 RuggedCom Inc. All rights reserved Rev101 4.8 Mechanical Specifications Figure 15 - Mechanica l Specifications Table 15 - Mechanic al Specifications Parameter Value Dimensions 16.8 x 11.7 x 6 .6 cm / 6.6 x 4.6 x 2.6 inches Weight 1.2 kg / 2.
24 2007 RuggedCom Inc. All rights reserved Rev101 5 T ype T es t s 5.1 IEC 61850-3 Type Tests Test Description Test Le vels Severity Levels Enclosure Contact +/- 8kV 4 IEC 61000-4-2 ESD Enclosure A ir +/- 15kV 4 IEC 61000-4-3 Radiated RFI Enclosure po rts 20 V/m x Signal ports +/- 4kV @ 2.
25 2007 RuggedCom Inc. All rights reserved Rev101 5.2 IEEE 1613 Type Tests Test Description Test Le vels Enclosure Contact +/- 8kV IEEE C37.90.3 ESD Enclosure Air +/- 15kV IEEE C37.90.2 Radiated RFI Enclosure ports 35 V/m Signal ports +/- 4kV @ 2.
26 2007 RuggedCom Inc. All rights reserved Rev101 6 W arranty RuggedCom wa rrants this product for a period of five (5) years f rom date of purchase. For warranty details, visit htt p://www.ruggedcom.com or contact your custome r service representative.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté RuggedCom RuggedVDSL RS900L c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du RuggedCom RuggedVDSL RS900L - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation RuggedCom RuggedVDSL RS900L, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le RuggedCom RuggedVDSL RS900L va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le RuggedCom RuggedVDSL RS900L, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du RuggedCom RuggedVDSL RS900L.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le RuggedCom RuggedVDSL RS900L. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei RuggedCom RuggedVDSL RS900L ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.