P/N 240499 CATALOG NO.: 6200.50 M Effective: 04-15-05 Replaces: 06-01-00 INST ALLA TION AND OPERA TING INSTRUCTIONS COMMERCIAL SWIMMING POOL HEA TERS Raytherm Models 514-824 This manual should be maintained in legible condition and kept adjacent to the heater or kept in a safe place for future reference.
WATER CHEMISTRY (Corrosive water voids all warranties) For your health and the protection of your pool equipment it is essential that your water chemically balanced.
4 PART ONE - OWNER’S OPERATING INSTRUCTIONS 4 SECTION 1/START-UP PROCEDURES 4 Before Start-Up 5 Operating Instructions 6 After Start-up 6 SECTION 2/CAUTION 6 SECTION 3/MAINTENANCE AND CARE PROCEDURE.
P ART ONE - OWNER’S OPERA TING INSTRUCTIONS FOR YOUR SAFETY - READ BEFORE OPERATING WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY RESULT, CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. SECTION 1/START-UP PROCEDURES BEFORE START-UP BURNERS Clean main burners and air louvers of dust, lint and debris.
5 1. STOP! Read the safety information above. 2. Set the thermostat on the lowest setting. 3. Turn off all electric power to the appliance. 4. Remove heater door panel. 5. This appliance is equipped with an ignition device which automatically light the pilot.
AFTER START-UP Feel the inlet and outlet pipes. Outlet pipe should be only slightly warmer than the inlet. It should not be hot. WARNING: Should overheating occur or the gas supply fail to shut off, turn off the manual gas control to the appliance.
5 . On indoor heater, clean room intake openings to assure adequate flow of combustion and ventilation air. CAUTION: Combustion air must not be contaminated by corrosive chemical fumes which can damage the heater and void the warranty.
4 foot Minimum 4 foot Minimum 1 foot Minimum 4 foot Minimum 3 foot Minimum 10 foot Minimum Forced Air Inlet 12" Minimu m 12" M inimum 4" Minimum HEA TER Sheet Metal 24 Gauge 8 HIGH WIND.
INDOOR HEATER The design is also certified for indoor installation when equipped with the approved draft hood. Locate heater as close as practical to a chimney or gas vent. Heater must always be vented to the outside. See Vent Piping Section for venting details.
As much as possible avoid long horizontal runs of vent pipe and too many elbows. If installation requires horizontal non-vertical runs, the vent pipe must have a minimum of 1/4 inch per foot rise and should be supported at not less than five foot intervals.
GAS SUPPLY CONNECTIONS Gas piping must have a sediment trap ahead of the heater gas controls, and a manual shut off valve located outside the heater jacket. All gas piping should be tested after installation in accordance with local codes. MANUAL SHUT OFF VALVE GAS INLET HEATER JACKET SEDIMENT GA S TRAP UNION VALVE Fig.
PIPE SIZING FOR GAS CONNECTIONS MAXIMUM EQUIVALENT PIPE LENGTH Natural gas 1000 BTU/Ft .60 Specific Gravity @ 0.5” W.C. Pressure Drop Propane Gas 2500 BTU/Ft 1.
AUTOMATIC CHLORINATORS AND CHEMICAL FEED- ERS All chemicals must be introduced and completely diluted into the pool or spa water before being circulated through the heater. Do not place chlorine tablets or bromine sticks in the skimmer. High chemical concen- trations will result when the pump is not running (i.
To avoid water damage or scalding due to valve operation, drain pipe must be connected to valve outlet and run to a safe place of discharge. Drain pipe must be the same size as the valve discharge connection through- out its entire length and must pitch downward from the valve.
15.
16 151965 824 825,000 BTUH.
17 152141 514-724 512,000 THRU 726,000 BTUH 5.
18 152142 824 825,000 BTUH 6.
CONTROLS/ADJUSTMENTS/REPLACEMENTS THERMOSTAT The heater is built with a single mechanical thermo- stat, located in the front panel above the door. The thermostat maybe set for any desired pool or spa temperature TEMPERATURE SENSOR MECHANICAL THERMOSTAT Fig.
PRESSURE SWITCH The pressure switch, or heater actuator, insures that the heater operates only when the filter pump is in operation. It is factory set at 1.75 PSI for deck level installations. When the heater is located below the level of the spa or pool it may be necessary to reset the pressure switch to compensate for the no-flow static head.
GAS VALVE REMOVAL 1. Shut off gas supply to the heater. Remove gas piping to gas valve inlet. 2. Disconnect wires, pilot tubing and bleed line, if required. 3. Turn vertical gas pipe from manifold slightly and unscrew gas valve. 4. Reverse above procedure to re-install.
22 Shut gas and power off to the unit, close the system off and drain the heater. Remove the draft diverter. Remove the access panel and jacket top. Lift flue collector off.
23 SECTION 5/TROUBLESHOOTING GUIDE IMPORTANT NOTICE These instructions are primarily intended for the use of qualified personnel specifically trained and experienced in the installation of this type of heating equipment and related system components. Installation and service personnel may be required by some states to be licensed.
Inspect bypass for movement, if no movement, replace. Replace if no movement when heated. Replace well and maintain water chemistry properly. Replace heat exchanger and maintain chemistry properly. See pressure switch adjustment. Replace refractory. Determine cause of sooting and correct.
WARNING HIGH VOLTAGE For qualified Technicians ONLY NOTE: Some heaters may be equipped with an ignition module that shuts off pilot gas if pilot fails to light. To reset, interrupt power to heater. Intermittent Pilot System TROUBLESHOOTING HONEYWELL S8600 NOTE:Before troubleshooting, familiarize yourself with the startup and checkout procedure.
26 SECTION 6/REPLACEMENT PARTS LIST NOTE: To supply the correct part it is important that you state the model number, serial number and type of gas when applicable.
this page is empty.
28 PILOT ASSEMBLY- ELECTRONIC IGNITION PILOT ASSEMBLY- STANDING PILOT Fig # 9293 Fig # 9294.
29.
30.
.
RAYPAK, INC., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 FAX (800) 872-9725 Litho in U.S.A. ww w .raypak.com.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Raypak 514-824 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Raypak 514-824 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Raypak 514-824, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Raypak 514-824 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Raypak 514-824, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Raypak 514-824.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Raypak 514-824. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Raypak 514-824 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.