PV500 - 17 05 - 2000 Section 17 1 INSTALLATION & MAINTENANCE MANUAL FOR MAXIM INTEGRATED WATER HEATING SYSTEM TABLE OF CONTENTS Start - up Procedures 2 Maintenance & Safety Inspections 3 - 5 Wiring Diagrams 6,7 Burner 8 Burner Start - up 9 - 12 Burner Troubleshooting 13.
PV500 - 17 05 - 2000 Section 17 2 START - UP PROCEDURES CAUTION: DO NOT RELIGHT PILOT OR START BURNER WITH COMBUSTION CHAMBER FULL OF GAS OR OI L VAPOR, OR WITH VERY HOT COMBUSTION CHAMBER. 1. Study the burner start - up information included in this manual carefully.
PV500 - 17 05 - 2000 Section 17 3 MAXIM MAINTENANCE AND SAFETY INSPECTIONS 1. Establ ish a preventive maintenance program to assure a longer water heater life. 2. The tank should be flushed at two - or three - month intervals depending on water conditions in your location.
PV500 - 17 05 - 2000 Section 17 4 MAXIM MAINTENANCE AND SAFETY INSPECTIONS (continued) Periodic Inspection of Operation Components (continued) CAUTION: THE RELIEF VA LVE IS A PRIMARY SAFETY DEVICE.
PV500 - 17 05 - 2000 Section 17 5 MAINTENANCE & SAFETY INSPECTION REPORT DATE BURNER INSPECTION COMBUSTION ANALYSIS TANK INSPECTION TANK FLUSH & CLEANOUT TANK FITTING INSPECTION VENT INSPECTIO.
PV500 - 17 05 - 2000 Section 17 6 MAXIM AXIAL FLOW GAS BURNER CARBON MONOXIDE WARNING: CAUTION: IMPROPER COMBUSTION MAY CAUSE SERIOUS INJURY. PVI recommends a s easonal or annual combustion check - out be performed by a qualified service agency to ensure safe and efficient operation.
PV500 - 17 05 - 2000 Section 17 7 MAXIM AXIAL FLOW GAS BURNER START - UP (Refer to Figure 17 - 2, page 6 to identify burner parts) 1. Remove the enclosure panel cover on the water heater or boiler to expose the control circuit. A wiring diagram, included in this packet, will show the controls used in our circuitry.
PV500 - 17 05 - 2000 Section 17 8 MAXIM AXIAL FLOW GAS BURNER START - UP (continued) PRESSURE PLATE Set up and Tolerances Figure 17 - 3 13. Connect a test meter to the control for reading the flame response signal. NOTE: Some controls read the flame signal in micro amps and some in volts DC.
PV500 - 17 05 - 2000 Section 17 9 MAXIM AXIAL FLOW GAS BURNER START - UP (continued) This section pertains to MC120 control only. When the blower motor starts, the air proving light on the MC - 120 should be on. This indicates a positive air flow condition.
PV500 - 17 05 - 2000 Section 17 10 MAXIM AXIAL FLOW GAS BURNER START - UP (continued) 17. Check flue gases with a flue analyzer to make final settings of the air shutter. a. The readings need to be taken from a hole in the vent several inches above the heater vent connection, but before draft regulator.
PV500 - 17 05 - 2000 Section 17 11 MAXIM TROUBLESHOOTING SUGGESTIONS AXIAL FLOW GAS BURNER 1. BURNER FAILS TO START Defective On/Off switch. Replace switch. A. Control circuit has an open control contact. Check limits, low water cutoff, proof of closure switch and others as applicable.
PV500 - 17 05 - 2000 Section 17 12 MAXIM TROUBLESHOOTING SUGGESTIONS AXIAL FLOW GAS BURNER (continued) C. Defective automatic main or auxiliary gas shut off valves. Check electrical circuitry to valves. Replace valves or correct circuitry a s required.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.