Manuel d'utilisation / d'entretien du produit DRN-PS-750 du fabricant Omega Engineering
Aller à la page of 18
.
Servicing North America: USA: One Omega Drive, P.O. Box 4047 ISO 9001 Certified Stamford, CT 06907-0047 TEL: (203) 359-1660 FAX: (203) 359-7700 e-mail: info@omega.com Canada: 976 Bergar Laval (Quebec) H7L 5A1 TEL: (514) 856-6928 FAX: (514) 856-6886 e-mail: info@omega.
1. General Information and Features 2 2. Applicable Standards 3 3. Installation and Removal 4 4. Input and Output Connections 8 5. Specifications 9 5.1 PS T ype Labeling 5.2 Size & W eight 5.3 Mounting 5.4 T emperature Ranges 5.5 Input Range 5.6 Input Current Surge Protection 5.
The compact DRN power supplies are designed to supply well-regulated 21.5 volt DC power to sensors, signal conditioners, data acquisition systems and high level logic equipment.
2.1 Input Voltage Tolerances Exceeds IEC 38 range 2.2 Input / Output Isolation 4KV rms 60Hz 1 minute test 630V conductor spacing, IEC 348 Exceeds VDE551 / IEC 742 separation spacing Exceeds VDE106 protective separation Exceeds VDE 160 clearance distances Exceeds VDE160 creepage distances 2.
The DRN power supplies are heavy enough to cause damage and or injury if dropped during installation. Assure firm rail mounting before releasing grip on the unit. If a rail assembly is to be transported, then disconnection, dismounting and separate packing of the power supply is recommended.
T o change voltage jumpers: 1. Remove cover from case by carefully prying up two side tabs using a screwdriver . Remove two screws from bottom of case. Slide unit out of case. 2. Locate the main board assembly and position it in front of you the same way as shown in Figure 3.
Figure 3.1 Ñ Main Board Power Jumpers MAIN BOARD T1 115VAC WIRING SHOWN WITH W1 W3 TRANSFORMER MOUNTING PLATE W2 115VAC JUMPER WIRING W1 W3 W2 230VAC JUMPER WIRING W2 W3 W1 I NST ALLA TION AND R EMOV.
Figure 3.2 Ñ 35mm "Top Hat" Installation: Hook in the module with the mounting rail guide on the top edge of the mounting rail and lower it to lock it into position. Removal: Release the spring catch with a screwdriver while raising the module to disengage it.
Figure 4.1 Ñ Front Panel Connection Labels shown without regulator cover AC Line AC Neutral Ground RETURN NO CONNECTION +21.5V IN AC N PWR +V N/C OUT DC I NPUT AND O UTPUT C ONNECTIONS 4 8 DRN-PS Ñ .
5.1 PS Type Labeling DRNÐPSÐ750, where 750 equals mA rating. DRNÐPSÐ750 5.2 Size & Weight Height: 2.76" (70mm) Width: 2.95" (75mm) Depth: 5.95" (151mm) Weight: 2.0 lbs. (0.9 kg) 5.3 Mounting 35mm "top hat" DIN EN 50022 5.
5.5 Input Range 115 or 230V, 49Ð61Hz DRNÐPSÐ750 ± 10% 5.6 Input Current Surge Protection 6kA/275V Varistor 5.7 Output Voltage 21.5V ± 2% - IR, where I = output current amperes and R = 0.
5.10 Temperature Derating None below 50 degrees C DRNÐPSÐ750, 15mA per degree C above 50¡C 5.11 Power-on Indicator Front Panel red LED lamp 5.12 Short-circuit and overload protection DRNÐPSÐ750 foldback current limiting with automatic high temperature shutdown no fuses required 5.
Figure 6.1 Ñ Derating Graph Figure 7.1 Ñ Block Diagram 49-61Hz 115/230vac INPUT: (+V) Ground AC Line AC Neutral V A R I S T O R L C F I L T E R B R I D G E ( ) 21.5V R E G U L A T O R Return 75mA 50 DRN-PS-750 ¡ C Ambient 0 1000 800 600 400 200 60 45 35 25 15 5 -5 I max.
Figure 8.1 Ñ Dimensions SPACED AS SHOWN. POWER SUPPLY WITH [151.1] 5.95 2.76 2.95 3.15 TWO SCREWS FASTEN RAIL UNDER MAX [70.0] [75.0] [80.0] D IMENSIONS D RA WING 8 13 DRN-PS Ñ DIN Rail Power Suppli.
S AFETY C ONSIDERA TIONS 14 DNR-PS Ñ DIN Rail Power Supplies Unpacking & Inspection Unpack the instrument and inspect for obvious shipping damage. Do not attempt to operate the unit if damage is found. This instrument is a panel mount device protected in accordance with Class I of EN 61010 (115/230 AC power connections).
WARRANTY / DISCLAIMER OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of 13 months from date of purchase. OMEGA Warranty adds an additional one (1) month grace period to the normal one (1) year product warranty to cover handling and shipping time.
Where Do I Find Everything I Need for Process Measurement and Control? OM EGAÉOf Course! TEMPERATURE M U Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies M U Wire: Therm.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Omega Engineering DRN-PS-750 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Omega Engineering DRN-PS-750 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Omega Engineering DRN-PS-750, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Omega Engineering DRN-PS-750 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Omega Engineering DRN-PS-750, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Omega Engineering DRN-PS-750.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Omega Engineering DRN-PS-750. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Omega Engineering DRN-PS-750 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.