Manual No. H-104 2008-02-18 NHRS Series RESISTIVE ELEMENT STEAM HUMIDIFIER Engineering Manual TM.
2008-02-18 PROPRIETARY NOTICE This document and the info rmation disclosed herei n are propriet ary data of W AL TER MEIER L TD. Neither this document nor the information cont ained herein shall be reproduced used, or disclosed to others without the written authoriza tion of W AL TER MEIER L TD.
2008-02-18 TABLE OF CONTENTS Subject Page 10-00 INTRODUCTION 1. PRINCIPLE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 10-10 HUMIDITY, STEAM ABSO RPTION & DISTRIBUT ION 1. CONTROLS . . .
2008-02-18 LIST OF FIGURES Figure Page 10-00 INTRODUCTION Figure 1. NHRS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 10-10 HUMIDITY, STEAM ABSO RPTION & DISTRIBUT ION Figure 1.
2008-02-18 THIS PAGE INTENTIONALLY LEFT BLANK.
10-00 Page 1 2008-02-18 10-00 INTRODUCTION.
10-00 Page 2 2008-02-18 1. PRINCIPLE OF OPERATION (1) The NORTEC NHRS uses an advanced control system to monitor and maintain optimum operating conditions within the humidifier cylinder. (2) The NHRS humidifier operates on Potable, DI (De-ionized), or RO (Reverse osmosis) water supply.
10-00 Page 3 2008-02-02 Figure 1. NHRS.
10-00 Page 4 2008-02-18 THIS PAGE ITENTIONALLY LEFT BLANK.
10-10 Page 1 2008-02-18 10-10 HUMIDITY, STEAM ABSORPTION & DISTRIBUTION.
10-10 Page 2 2008-02-18 1. CONTROLS A. STANDARD CONTROLLE RS (1) NORTEC has a wide range of modulation packages for use with the NHRS humidifiers. The packages all provide humidity controllers complete with point for accuracy up to ±3%. For accuracy u p to ±1% a high precision humidistat is required.
10-10 Page 3 2008-02-18 D. VARIABLE AIR VOLUME (VAV ) CONTROL SYSTEM (1) NORTEC offers several VAV control packages where VAV or variable duct temperature, air flow or humidity conditions require additional control fle xibility. 2. STANDARD FEAT URES AND BENEFITS (1) NORTEC NHRS humidifiers can be suited for all humidity control applications.
10-10 Page 4 2008-02-18 3. ELECTRICAL (1) Humidifiers require field wiring to the primary voltage terminal block. Power and fusing requirements are as indicated on the Specificat ion label. Wiring is fed through an electrical knockout in the bottom back of the electrical cabinet.
10-10 Page 5 2008-02-18 Table 1. Technical Data NHRS Model / Capacity (lbs/hr) VOLTAGE PHASE RATED AMPS RATED K.W. MAX. EXT. CIRCUIT PROTECTION 010 [11.25] 208 1 18.39 3.83 25 010 [11.25] 230 1 15.94 3.83 20 010 [11.25] 460 1 7.97 3.83 15 010 [11.25] 575 1 6.
10-10 Page 6 2008-02-18 Figure 2. NHRS Physical Data – 010-090.
10-10 Page 7 2008-02-18 Figure 3. NHRS Physical Data – 135-180.
10-10 Page 8 2008-02-18 Figure 4. RMBP Physical Data Dimensions.
10-20 Page 1 2008-02-18 10-20 SPECIFICATION.
10-20 Page 2 2008-02-18 1. HUMIDIFIERS A. GENERAL (1) Work Included (a) NORTEC NHRS Resistive Element steam humi difier[s] as indicated on drawing[s] and as indicated on schedule[s]. (b) Complete and operable humidification system [which meets applicable building codes].
10-20 Page 3 2008-02-18 (4) Extra Material (a) Furnish extra materials described below that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. (5) References (a) ANSI/NFPA 70 - National Electrical Code.
10-20 Page 4 2008-02-18 (vii) Float level check. (viii) Drain pump check. (ix) Dual signal status light indicates unit operation. (x) Cabinet has powder coated paint fini sh with removable door to allow the user full front access. (xi) Plumbing door interlock safety switch.
10-20 Page 5 2008-02-18 (b) Seal humidifier dispersion-tube duct penetrations with flange. (c) Install with required clearance for service and maintenance.
10-20 Page 6 2008-02-18 2. ACCESSORIES / OPTIONS AVAILABLE A. NHRS UNIT CONFI GURATION OPTIONS (1) Solid State Relay option provides the highest level of relative humidity control available. With de-ionized water and high precision control the Solid State Relay option is capable of maintaining ±1% relative humidity control.
10-20 Page 7 2008-02-18 E. BLOWER PACK (1) Wall mounted direct steam distribution system allows for direct space/room humidification when steam introduction into a ducted system is not feasible. The factory assembled remote mounted blower pack includes an integral steam distributor, 3 direct drive fans.
WARRANTY (1) WALTER MEIER INC. and/or WALTER MEIER LTD. (hereinafter collective ly referred to as THE COMPANY), warrant for a period of two years afte r installation or 30 months from manufacturer’s.
U.S.A. W alter Meier (Climate USA) Inc. 826 Proctor Avenue Ogdensburg, NY 13669 TEL: 1-866-NORTEC-1 EMAIL: northamerica.climate@waltermeier .com WEBSITE: www .
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Nortec NHRS Series c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Nortec NHRS Series - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Nortec NHRS Series, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Nortec NHRS Series va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Nortec NHRS Series, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Nortec NHRS Series.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Nortec NHRS Series. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Nortec NHRS Series ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.