FIELDPOINT ™ OPERATING INSTRUCTIONS AND SPECIFICATIONS FP-DO-403 and cFP-DO-403 16-Channel, 5 to 30 V Sinking Digit al Output Module These operating instructions descri be ho w to install and use the National Instruments FP-DO-403 a nd cFP-DO-40 3 digital output modules, referred to inclusi v ely as the [c]FP-DO-403.
[c]FP-DO-403 2 ni.com 2. Align the FP-DO-403 alignment slots with the guide rails o n the terminal base. 3. Press firmly to seat the FP-DO-403 on the terminal base. When the module is firmly seated, the te rminal base latch locks it into place. Figure 1.
© National Instruments Corp. 3 [c]FP-DO-403 Figure 2. Installing the cFP-DO-403 Wiring the [c]FP-DO-403 The FP-TB- x terminal base has conne ctions for each FP-DO-403 output channel and for an external supply to po wer field devices. The cFP-CB- x connector block provides the same connections for the cFP-DO-403.
[c]FP-DO-403 4 ni.com loads on the output channels, up to 2 A per channel. 1 Connect the external po wer supply to multiple V and V SUP terminals and to multiple C and COM terminals as need ed to ensure that the maximum current through any terminal is 2 A or less.
© National Instruments Corp. 5 [c]FP-DO-403 Figure 3. Wiring for Low-Current Applica tions Wiring for High-Current Applications If your application requires more than 2 A combined current through all channels of the [c]F P-DO-403, wire your application as shown in Figure 4.
[c]FP-DO-403 6 ni.com Digital Output Circuit The [c]FP-DO-403 digital output ch annels are optically isolated from the rest of the FieldPoint bank . In the ON state, a transistor is turned on between the V OUT terminal and the ex ternal supply (the C and COM terminals).
© National Instruments Corp. 7 [c]FP-DO-403 mount the flyback diode within 18 in. of the load. Figure 5 shows a flyback diode connected to an inductiv e load.
[c]FP-DO-403 8 ni.com 250 V rms Measurement Cate gory II contin uous isolation, ve rified by 2,300 V rms , 5 s dielectric withst and test. The [c]FP-DO-403 provides double insulation (compliant with IEC 61010-1) for working v oltages of 250 V rms 1 .
© National Instruments Corp. 9 [c]FP-DO-403 •D o not use the [c]FP-DO-403 as the only isolating barrier between human cont act and working v o ltages higher than 250 V rms . • Operate the [c]FP-DO-403 only at or belo w Pollution Degree 2. Pollution De gree 2 means that only nonconductive pollution occurs in most case s.
[c]FP-DO-403 10 ni.com Caution For Zone 2 applications, install a protection device across the e xternal power supply and the COM terminal. The device must pre vent the external po wer supply voltage from e xceeding 42 V if there is a transient ov ervoltage conditi on.
© National Instruments Corp. 11 [c]FP-DO-403 Power Requirements Power from network module ............ 600 mW Safety Isolat ion Voltage Isolation voltage is v erified by a dielectric withstand te st. Channel to ground Continuous .............. ......
[c]FP-DO-403 12 ni.com Safety This product is designed to meet the requirements of the following standards of safety for electric al equipment for measurement, control, and laboratory use: • IEC 61010-1, EN-61010-1 • UL 61010-1, CSA 61010-1 Note For UL and other safety certif ications, refer to the product label or visit ni.
© National Instruments Corp. 13 [c]FP-DO-403 contains the en vironmental regulat ions and directi v es with which NI complies, as well as othe r en vironmental information not included in this document.
[c]FP-DO-403 14 ni.com Where to Go for Support For more information about settin g up the FieldPoint system, refer to these National Instruments documents: • FieldPoint network module user manual • Other FieldPo int I/O m odule operating instructions • FieldPoint terminal base and connector block operating instructions Go to ni.
© 2002–2007 Nati onal Instruments Corp. All rights reserved. 373354C-01 Aug07 National Instruments, NI, n i.com, and LabVIEW are trademarks of National I nstruments Corporation. Refer to the Terms of Use section on ni.com/legal for more information about National Instruments tra demarks.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté National Instruments cFP-DO-403 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du National Instruments cFP-DO-403 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation National Instruments cFP-DO-403, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le National Instruments cFP-DO-403 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le National Instruments cFP-DO-403, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du National Instruments cFP-DO-403.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le National Instruments cFP-DO-403. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei National Instruments cFP-DO-403 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.