Manuel d'utilisation / d'entretien du produit 47-116-08. 47-116-09 du fabricant Ariston
Aller à la page of 32
Installation Instructions T ype C Boile r s G. C .N: 41-116-01 47-116-08 47-116-09 47-116-13 LE A VE THES E INST R UCTIONS AD J A CENT T O TH E GA S METER Count r y of destination : GB.
2 B004 T ABLE OF CONTENTS 1. GENERAL INFORMA TION 1.1 General Instructions 1.2 T echnical Information 1.3 Ov erall View 2. INST ALLA TION 2.1 Ref erence Standards 2.2 Siting the Appliance 2.3 Ov erall Dimensions 2.4 Clearances 2.5 Mounting the Appliance 2.
3 B004 This manual is an integr al and essential par t of the product. It should be kept with the appliance so that it can be consulted by the user and our authorised personnel.
4 B004 23 MFFI 27 MFFI 27 RFFI SYSTEM 30 MFFI CE Cer tification Heat Input max/min kW 25.6/11.0 29.8/12.0 29.8/12.0 33.0/12.0 Heat Output max/min kW 23.1/9.2 27.3/10.1 27.3/10.1 30.3/10.2 Efficiency of Nominal Heat Input % 90.2 91.6 91.6 92.0 Efficiency at 30% of Nominal Heat Input % 87.
5 B004 GENUS 23/27/30 MFFI Legend: 1. Flue Connector 2. Combustion Chamber Hood 3. Main Heat Exchanger 4. Combustion Chamber Insulation P anel 5. Bur ner 6. Expansion V essel 7. Ov erheat Ther mostat 8. Spark Generator 9. Div er ter V alv e (MFFI) Motorised V alv e (RFFI) 10.
6 B004 The technical inf ormation and instr uctions provided herein below are intended f or the installer so that the unit ma y be installed correctly and saf ely .
7 B004 Legend: A = Central Heating Flow (3/4”) B = Domestic Hot Water Outlet (1/2”) C = Gas Inlet (3/4”) D = Domestic Cold Water Inlet (1/2”) E = Central Heating Return (3/4”) F = Cylinder Flow (3/4”) G = Cylinder Return (3/4”) 2.
8 B004 F asten the boiler in place using the template and anchors supplied with the unit. It is highly recommended that a spirit lev el be used to position the boiler so that it is perf ectly lev el. F or additional inf or mation, please consult the instr uctions contained in the connection kit and the flue kit.
9 B004 2.8 W ater Connections Legend A = Central Heating Flo w B = Domestic Hot W ater Outlet C = Gas Inlet D = Domestic Cold Water Inlet E = Central Heating Return F = Cylinder Flow G = Cylinder Retu.
10 B004 Residual Head of the Boiler 27/30 kW 23 kW Air Release P oints: These must be fitted at all high points where air naturally collects and m ust be sited to f acilitate complete filling of the system. The appliance has an integral sealed e xpansion vessel to accommodate the increase of water v alue when the system is heated.
TERMINAL POSITION mm A - Directly below an open windo w or other opening 300 B - Below gutters , solid pipes or drain pipes 75 C - Below ea ves 200 D - Below balconies or car-port roof 200 E - F rom v.
12 B004 A Ø 80 mm Ø 80 mm In addition, it is also possible to use a split system b y fitting a special adapter to the flue discharge collar and using one of the aper tures for the air v ent intake located on the top par t of the combustion chamber (A).
13 B004 In Fig. 2.11 below , se veral diff erent types of flue systems are shown. F or additional inf or mation regarding the flue accessor ies, please consult the Flue Pipe Accessories manual.
14 B004 In calculating the lengths of the pipes, the maxim um length must also take into consider ation the v alues for the e xhaust/air intake end terminals, as well as 90° elbo ws for coaxial systems. The C52 types must comply with the f ollowing requirements: 1 .
15 B004 4 Remov e the grommet “E” shown in the photo 4, mak e a hole in it and pass the room ther mostat wire through. 5 Remov e the link located in the ter minal bloc k and connect the wire.
16 B004 2.11 Electrical Diagram Legend: A T = High V oltage P .C .B. BT = Low V oltage P .C .B. A = Remote Connector Kit B = Flame F ailure L.E.D . C = Insufficient W ater Pressure L.E.D . D = Water T emperature Indicator L.E.D .s E = Overheat Thermostat Warning L.
17 B004 Aa GENUS 23/27/30 MFFI Aa GENUS 27 RFFI SYSTEM.
18 B004 CN202 P GENUS 23/27/30 MFFI P GENUS 27 RFFI SYSTEM.
19 B004 GENUS 23/27/30 MFFI 2.12 W ater Circuit Dia gram Legend 1. Air Pressure Switch 2. F an 3. Main Heat Exchanger 4. Bur ner 5. Electronic Ignitor and Electronic Flame Detector 6. Gas V alv e 7. Ov erheat Ther mostat 8. Heating Sensor 9. Div er ter V alv e (MFFI) Motorised V alv e (RFFI) 10.
20 B004 3. COMMISSIONING 3.1 Initial Preparation Preliminar y electrical system checks to ensure electrical saf ety must be carried out by a competent person i.e . polar ity , ear th continuity , resistance to ear th and shor t circuit. Filling the Heating System: Remov e the panels of the case and lower the control panel (see point 3.
21 B004 3 2. Lift the front panel up until it stops after the click; 3. Remove the front panel from the rest of boiler casing; 4. Unhook the two cords from the location slots. 4 3.3 Control P anel A - Ignition Loc kout Reset Button/Saf ety (Overheat)Thermostat Reset B - Ignition Loc kout L.
The boiler was designed to mak e regulation easy . T o access the adjustment and control area, simply remov e the cov er by unscre wing the screws “A” and “C” and lift up the small ser vice panels “B1” and “B2” respectiv ely . The first provides access to the control (lo w voltage) P .
23 B004 3.6 Combustion Anal ysis The boiler is designed to make it easy to analyse the comb ustion by-products. Using the especially designed aper tures, readings can be taken on the temperature of the comb ustion by-products and of the comb ustion air , as well as of the concentrations of O 2 and CO 2 , etc.
24 B004 3.9 Draining the System Draining the heating system. The heating system must be emptied as f ollows: - T ur n off the boiler ; -Open the drain v alve f or the system and place a container below to catch the water that comes out; - Empty the system at the low est points (where present).
CA TEGOR Y II2H3+ Methane Gas Liquid Butane Gas Liquid Pr opane Gas G20 G30 G31 Recommended Soft-light Pressure (mbar) 5-5.5 17 - 18 18 - 19 Lower W obbe Index (15°C;1013mbar) MJ/m 3 h 45.67 80.58 70.69 Nominal Delivery Pressure mbar 20 30 37 Minimum Deliv er y Pressure mbar 17 20 25 23 MFFI Main Burner : n.
26 B004 It is recommended that the follo wing checks be made on the boiler at least once a year: 1 - Chec k the seals for the water connections; replacement of any f aulty seals. 2 - Chec k the gas seals; replacement of any f aulty gas seals. 3 - Visual chec k of the entire unit.
27 B004 6. MISCELLANEOUS 6.1 Wiring Diagram f or T wo Heating Zones V4043H VA LV E BRO WN 8 BLUE 2 GREY 9 ORANGE 10 GREEN/YELLO W 3 Honeywell ST 699B 1002 63 N L Link L-5-8 ST 6400/ST 6300 ST 6200 3 4.
28 B004 6.2 Wiring Diagram f or Connection to Ariston Un vented Cylinder Honeywell ST 699B 1002 63 N L Link L-5-8 ST 6400/ST 6300 ST 6200 3 4 N L Drayton T empus 7 3 4 N L Horstmann 425, 525, 527 14 E.
B004 NO TES.
30 B004 NO TES.
31 B004.
B004 - Cod. 23 99 84 1259 111 - Stampa: b b i i e e f f f f e e RECANATI Manuf acturer : Merloni T ermoSanitari SpA - Italy Commercial subsidiar y: MTS (GB) LIMITED MTS Building Hughenden A venue , Hi.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Ariston 47-116-08. 47-116-09 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Ariston 47-116-08. 47-116-09 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Ariston 47-116-08. 47-116-09, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Ariston 47-116-08. 47-116-09 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Ariston 47-116-08. 47-116-09, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Ariston 47-116-08. 47-116-09.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Ariston 47-116-08. 47-116-09. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Ariston 47-116-08. 47-116-09 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.