Do Not Attempt Installing Unit Without First Reading Entire Manual. OPERA TION AND INST ALLA TION MANUAL CAUTION Before installation, careful consideration must be given to how the system will operate if connected to any other piece of mechanical equipment, i.
2 INTRODUCTION These Heat Recovery Ventilators (HRVs) are designed for commercial and industrial applications to provide fresh air to a building while exhausting an equal amount of stale air. During the winter months the incoming cold fresh air is warmed by utilizing the heat recovered from the stale air before it is exhausted to the outdoors.
3 MAKE UP HEA T REQUIREMENT at 1200 CFM (566L/s) Nominal Nominal Nominal Outdoor Temp. kW Req. for kW Req. for kW Req. for C° F° 20°C (68°F) 25°C (77°F) 30°C (86°F) Air Delivery Air Delivery A.
4 Supply to building Supply from outside Exhaust from building Exhaust to outside Heat Exchanger Service Panel* Filter Service Panel* Electrical Service Panel* 47" 47" 89.9" 38.4" 24" 16" SIDE VIEW FRONT VIEW BACK VIEW *NOTE: Removable service access panels on both sides of 2500IFD cabinet.
5 PERFORMANCE OPTIONS AND ACCESSORIES 99-101: CRANK TIMER Mechanical timer to activate high speed. 99-116: DEHUMIDISTAT VENTILATION CONTROL (DVC) Turns unit on/off via slider switch and high/low via built-in dehumidistat. 99-130: DEHUMIDISTAT Activates high speed when indoor humidity rises above set point on control.
6 Hoods (2) c/w Bug Screen Motors (2) Supply to Duct 24"x16" Drain Pans (2) Heat Exchange Core Exhaust Duct 24"x16" 4" Filters Supply Hoods Exhaust Hoods Roof Curb Heat Exchanger Service Panel* Filter Service Panel* Electrical Service Panel* 47" 18" 18" 27" 89.
7 PERFORMANCE OPTIONS AND ACCESSORIES 99-101: CRANK TIMER Mechanical timer to activate high speed. 99-116: DEHUMIDISTAT VENTILATION CONTROL (DVC) Turns unit on/off via slider switch and high/low via built-in dehumidistat. 99-130: DEHUMIDISTAT Activates high speed when indoor humidity rises above set point on control.
8 Oper ation Instructions The LIFEBREA TH 2500 series HRV is designed tobe operated continuously or intermittently to meet the requirements of the application. CONTINUOUS OPERA TION For continuous operation, a simple jumper across the ON/OFF and COMMON jumper terminals is needed.
9 Off 10 20 30 40 50 60 Optional Remote Controls ON OFF HIGH LOW Supplied and Installed by Contractor Dehumidistat Setting Relative to Outside Conditions WINTER: Set dehumidistat between 30% to 40%. If home is too dry, adjust to higher setting.
F an Defrost The Models 2500IFD and 2500EFD are equipped with an electronically controlled fan defrost system to remove frost that collects on the warm air side of the aluminum heat transfer surfaces of the heat exchanger core.
11 Mounting the 2500 2500EFD Roof mount NOTE: Roof curb is one inch smaller than outside dimensions of cabinet Roof curb 2500IFD Platform mount (not provided) Mount unit on wooden or metal support assembly. Unit must be raised an adequate height for installation and slope of drain lines.
FRAME ASSEMBL Y 1. T ake one end piece (locking tabs) and one side piece (slots). Stand both pieces vertically on the floor or roof. See Figure 1. 2. Raise slightly the corner of the end piece (locking tabs) and mate with side piece (slots), ensuring that lower locking tab with leading edge is through slot opening.
13 Dr ains Connect the stainless steel drain pans in the bottom of the HRV to a drain line fastened to the holes provided. See pg.10 for location of the drain pans and the drain connections. Create a "P" trap to prevent odours from being drawn through.
14 Stale Air Return S yst em The stale air return system is used to draw air from the points in the building where the worst air quality prob- lems occur . Balancing dampers and/or adjustable grilles are recommended on all return air lines which are used during installation to help balance the "draw" from different areas of the building.
15 It is necessary to have balanced air flows in an HRV. The volume of air brought in from the outside must equal the volume of air exhausted b y the unit.
16 The Integr ated HV A C S ystem The 2500 is a quiet, efficient, low pressure system. Special care and attention should be given if connecting this unit to any other air handler that may draw more air than the 2500 is designed to accommodate. The HRV has become an integral component of the HV AC system.
17 DAMPERS OR ADJUSTABLE GRILLES BALANCING DAMPERS HRV UNIT EXHAUST TO HRV SUPPLY DUCT RETURN AIR DUCT FRESH AIR SUPPLY FRESH AIR TO BUILDING STALE AIR EXHAUST ROOFTOP HEAT/COOL UNIT Check design stat.
18 C1 HIGH BLACK - HIGH YELLOW - COM BLUE - MID RED - LOW SUPPL Y M OTO R SUPPL Y BRO WN BRO WN CAP C2 F2 L1 L2 F3 MAX 15A MAX 15A LOW TIMER ON/OFF ON/OFF 24V F.
19 CO MMERCIAL LIFEBREA TH ® HEA T REC O VER Y VENTILA TORS • T wo Y ear Limited W arranty • 15 Y ear Core W arranty NUTECH ENERGY SYSTEMS INC. ® (NUTECH) warrants to the purchaser of the Commercial LIFEBREATH ® model and accessories referred to below, to be free from manufacturing defects.
511 McCormick Blvd. London, Ontario N5W 4C8 Ph: (519) 457-1904 Fx: (519) 457-1676 Email: nutech@lifebreath.com Website: www.lifebreath.com.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Lifebreath 2500IFD c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Lifebreath 2500IFD - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Lifebreath 2500IFD, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Lifebreath 2500IFD va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Lifebreath 2500IFD, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Lifebreath 2500IFD.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Lifebreath 2500IFD. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Lifebreath 2500IFD ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.