IMPORTANT SAFETY INSTRUCTIONS 1. SAVE THESE INSTRUCTIONS. THIS MANUAL CONTAINS IMPORTANT SAFETY INSTRUCTIONS. Read all safety and operating instructions before operating the Uninterruptible Power System (UPS). Adhere to all warnings on the unit and in this manual.
1 10. Storing magnetic media on top of the UPS may result in data loss or corruption. 11. Turn the UPS off and isolate the UPS before cleaning. Use only a soft cloth, never liquid or aerosol cleaners.
2 INTRODUCTION AND SYSTEM DESCRIPTION Congratulations on your choice of the UPStation GXT™ Uninterruptible Power System (UPS). It provides conditioned power to microcomputers and other sensitive electronic equipment. Upon generation, AC power is clean and stable.
3 RECTIFIER/POWER FACTOR CORRECTION (PFC) CIRCUIT In normal operation, the rectifier/power factor correction (P FC) circuit converts mains AC power to regulated DC power for use by the inverter, while ensuring that the wave shape of the input current used by the UPS is near ideal.
4 CONTROLS AND INDICATORS Fault Indicator (Red) The Fault indicator is illuminated if the UPS has detected a problem. Also, one or more of the load/battery level indicators may be illuminated (refer to Troubleshooting Guide). BYPASS Indicator (Amber) The BYPASS indicator is illuminated when the UPS is operating from BYPASS power.
5 The UPStation GXT is equipped with au tomatic and remote battery test features. The automatic test occurs every 14 days if a manual battery test has not been performed or if mains has not been interrupted (14 day timer resets if unit goes to battery).
6 Input Breaker Output Breaker Battery Breaker Hardwire Terminal Blocks Intellislot Communications Port TM DB-9 Communications Port Output Voltage Selector Switches Battery Breaker Hardwire Terminal B.
7 OPERATING MODES NORMAL MODE OPERATION - UPS mode During normal operation, mains power provides energy to the UPS. The filters, the power factor correct ion circuit and the inverter process this power to provide computer grade power to connected loads.
8 BYPASS MODE OPERATION During BYPASS operation, mains power provides energy to your load and maintains the batteries in a fully charged state. The four green LED’s indicate an approximate level of load in 25% increments. If the BYPASS becomes loaded beyond full rating, the fifth (amber) LED indicator will illumi nate and sound an alarm.
9 STARTING THE UPS 1. Ensure the load equipment is t urned off, and all loads are properly connected to the UPS output. 2. Check that the mains wall isolator is ON. Turn On (Close) the Battery circuit breaker, the Input and Output circuit breakers in that order.
10 SWITCHING FROM OUTPUT OFF TO UPS or UPS to BYPASS to OFF 1. If the UPS is in OUTPUT OFF condition, with all rear mounted breakers in the ON position, and the AC input LED and the bottom LED of the BATTERY/LOAD array lit. To go to UPS mode, press the UPS ON/ALARM /BATTERY TEST button until a “Beep” is heard.
11 TROUBLESHOOTING The information below indicates various symptoms a user may encounter in the event the UPStation GXT develops a problem. Use this infor mation to determine whether external factors cause the problem and how to remedy the situation. 1.
12 AUDIBLE ALARM CONDITIONS CONDITION ALARM Battery mode (utility failure) One short beep every ten seconds Low battery Two short bee ps every five seconds Output overload (bypass) One short beep ever.
13 TROUBLESHOOTING GUIDE PROBLEM CAUSE SOLUTION Fault and Bypass indicators and all load level LED's are illuminated UPS overl oaded or load equipment is faulty Check load level display and remove non - essential loads. Recalculate load VA and reduce number of loads connected to UPS.
14 UPS MONITORING The UPStation GXT UPS has the capability of being monitored with stand alone computers, network workstations, network servers, or UNIX hosts via the DB - 9 socket located on the rear of the UPS. This capability is used in applications requiring the UPS to provide status and power monitoring information to the computer system.
15 MAINTENANCE The UPStation GXT UPS requires very little maintenance. The batteries are valve regulated, non - spillable, lead acid, and should be kept charged to obtain their designed life. The UPS continuously charges the batteries when connected to the mains supply.
16 INSTALLATION INSTRUCTIONS These instructions are for use by competent personnel only. INSTALLATION CONSIDERATIONS Detailed instructions to help you install the UPS are provided in the following pa ges; however, you should give some consideration to the proposed environment in which the UPS is to be installed, and carry out some preparatory work.
17 AIRFLOW DISSIPA TION OUTPUT RATING INPUT CURRENT Amps max Cfm m 3 h Watts K Btu/hr VA Watts Including mains variation/battery charge 130 221 504 1.7 6000 4200 GXT6000 = 33 amps 270 459 840 2.
18 ELECTRICAL CONNECTIONS T he UPS is supplied with an input/output/ battery terminal block assembly on the rear of the UPS within a cable box. (see outline drawing) The cable box can be removed to enable knockouts to be removed or new holes drilled, to secure the cables .
19 Connecting the UPS Power cables Power cables connect to screw terminals on a terminal block that is located behind the rear mounted cable box (see figure). The cables enter the UPS through a Gland Plate attached to the rear of the UPS. The Gland Plate must first be removed and drilled to suit the glands or bushes for the cables used.
20 Stabilisers/Levelling Feet When the UPS is located in its final position before or after wiring, it is necessary to fit stabiliser brackets and, if necessary, adjust the levelling feet. If the UPS is wired using a rigid wiring system, then movement of the UPS must be prevented by winding down the 4 levelling feet under the UPS as shown below.
21 COMMUNICATIONS INTERFACE PORT The UPStation GXT UPS contains a standard DB - 9 socket loca ted on the rear of the UPS unit. Several signals are provided on this port and are assigned as follows: PI.
22 FERRITE BEAD INSTALLATION When using either of the options below, to reduce the risk of radio interference, fit the ferrite assemblies supplied with the UPS as follows: Serial Communications Attach.
23 COMMISSIONING THE UPS Output Voltage Selector Switches The Output Voltage Selector Switches, lo cated on the rear of the UPS, are designed to allow selecting or changing the desired output voltage to match the mains. The settings to choose from are 208, 220, 230, and 240 VAC output.
24 Battery Run Times Load % 6kVA 6kVA + (1) GXT240VBATT 6kVA + (2) GXT240VBATT 10% 69 250 360 20% 58 197 301 25% 52 174 278 30% 48 155 248 40% 33 117 190 50% 23 88 140 60% 17 73 110 70% 14 60 94 75% 1.
25 SPECIFICATIONS MODEL NUMBER GXT6000T - 230 GXT10000T - 230 MODEL RATING VA/W (max) 6000 / 4200 10000 / 7000 DIMENSIONS: mm (in) Unit W x D x H 260 x 555 x 803 (10.5 x 22.0 x 31.5) 340 x 650 x 960 (13.5 x 25.5 x 38.0) Shipping W x D x H 400 x 850 x 1065 (16.
26 SPECIFICATIONS MODEL NUMBER GXT6000T - 230X GXT10000T - 230X MODEL RATING VA/W (max) 6000 / 4200 10000 / 7000 DIMENSIONS: mm (in) Unit W x D x H 260 x 555 x 803 (10.5 x 22.0 x 31.5) 340 x 650 x 960 (13.5 x 25.5 x 38.0) Ship ping W x D x H 400 x 850 x 1065 (16.
27 LIMITED WARRANTY Liebert Corporation extends the fo llowing LIMITED WARRANTY to the purchaser and to its customer (collectively referred to as the "Purchaser"): the enclosed Uninterruptib.
28 Technical Support Worldwide Support +1 614 841 - 6755 Worldwide Fax Tech Support +1 614 841 - 5471 U.K. +44 1628 403 200 France +33 1 4 360 26 19 Germany +49 21669649340 Italy +39 2 98250 1 Netherlands +00 31 475 504050 E - mail upstech@liebert.com Web site http://www.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Liebert GXTTM c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Liebert GXTTM - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Liebert GXTTM, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Liebert GXTTM va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Liebert GXTTM, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Liebert GXTTM.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Liebert GXTTM. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Liebert GXTTM ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.