Manuel d'utilisation / d'entretien du produit 700-3000 VA du fabricant Liebert
Aller à la page of 28
P OWER P ROTECTION U SER M ANUAL English / Español R 700 - 3000 VA 120V UPStation GXT™ DISCONTINUED PR ODUCT.
2 IMPORTANT SAFETY INSTRUCTIONS WARNING: Do not attempt to service this product yourself except to replace the battery. Opening or removing the cover may expose you to dangerous voltages, even when the AC cord is disconnected from the electrical outlet.
3 10. Route power supply cords so they are not walked on or pinched. 11. Never block or insert any object into the ventilation holes or other openings. Maintain a clearance of four (4) inches in front and rear of the UPS for proper air flow and cooling.
4 MAJOR COMPONENTS N G TVSS and EMI/RFI Filters INPUT Dynamic Bypass Rectifier/PFC Inverter OUTPUT DC to DC Converter Battery Battery Charger TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) AND EMI/RFI FILTERS These UPS components pr ovide surge protection, and filter both electromagnetic interference (EMI) and radio frequency interference (RFI).
5 DC TO DC CONVERTER The DC - DC converter utilizes energy from the battery system and raises the DC vo ltage to the optimum operating voltage for the inverter. This allows the inverter to operate continuously at its optimum efficiency and voltage, thus increasing reliability.
6 GENERAL INSTALLATIO N MINI - TOWER/TOWER UPS INSTALLATIONS 1. Unpack the UPS carefully noting the packing method. Retain the box and packing m aterial for possible future shipment. 2. CAUTION: The UPS is heavy (see specifications). Take proper precautions when lifting or moving it.
7 RACK - MOUNT CONVERSI ON DIAGRAMS To p Cove r Screw s Flange Screws Aerial Vie w w/top cover remove d Rubber Fee t Lift here t o change orientation o f display template ! + - E D C B A Faul t BYPAS S UPS ON BATTER Y AC INPUT RACK - MOUNT UPS CONVERSION AND INSTALLATION 1.
8 12. Plug the UPS into a dedicated wall receptacle properly protected by a circuit breaker or fuse in accordance with the National And Local Codes. Use a 15 amp rated device fo r the 1000, or 1500 VA units, a 20 amp device for the 2000 VA unit, and a 30 amp device for the 3000 VA unit.
9 FERRITE BEAD INSTALLATION Serial Communications Attach the smaller enclosed ferrite bead clamp to the communication cable as shown in the drawing using the fo llowing directions: � Open the ferrite bead. � Place the communication cable inside the ferrite bead grove.
10 UPSTATION GXT™ On/Alarm Silence/ Manual Battery Test Button Off/ Bypass Button Fault Indicator Bypass Indicator UPS On Indicator Battery Indicator AC Input Indicator Load/Battery Level Indicators.
11 CONTROLS AND INDICATORS On/Alarm Silence/Manual Battery Test Button This button controls output power to connected load(s) and has three functio ns: On, Alarm Silence, and Manual Battery Test. Pressing this button will start up the UPS in order to provide conditioned and protected power into the utility socket.
12 UPS On Indicator (Green) The UPS On indicator is illuminated when the UPS inverter is operating and supplying power to your connected loads. Battery Indicator (Amber) The Battery indicator is illuminated when the UPS is operating from the battery system.
13 BATTERY MODE OPERATION Battery mode occurs in event of a n extreme input voltage condition or complete utility failure. The battery system supplies power through the DC - DC converter to the inverter to generate power for the connected load. During battery mode an alarm sounds every 10 seconds.
14 COMMUNICATIONS INTERFACE PORT The UPStation GXT™ UPS contains a standard DB - 9 female connector located on the rear of the UPS unit. Several signals are provided on this port and are assigned as.
15 UPS INTELLIGENT COMMUNICATIONS The UPStation GXT™ UPS has the capability to communicate intelligently with stand alone computers, network workst ations, network servers, or UNIX hosts via the DB - 9 female connector located at the rear of the UPS.
16 BATTERY REPLACEMENT PROCEDURES CAUTION – A battery can present a risk of electrical shock and high short circuit current. The foll owing precautions should be observed before replacing the batteries: - Turn off and disconnect the UPS from the utility power prior to opening the battery replacement door.
17 7. Replace battery door by inserting the three metal tabs into the slots and pushing it toward the front of the UPS. Replace and tighten the five screws to lock the battery door closed. 8. Carefully stand the UPS upright. Connect the UPS to the utility supply socket and turn on the UPS by pressing the on button.
18 RACK / TOWER BATTERY REPLACEMENT Large battery doo r Battery connecto r Large battery doo r Screw hidden b y small battery doo r Small battery doo r Two front rubber fee t Front bezel (cover ) Rear.
19 UPSTATION GXT BATTERY RUN TIMES (Discharge times are at 25° C ambient) Internal Battery (minutes) Load% 700MT 1000MT 1000RT 1000RTE 1500RT 2000RT 3000RT 10% 52 95 95 170 80 160 101 20% 38 46 46 12.
20 FUSE REPLACEMENT PROCEDUR ES CAUTION: Before changing the input fuse, turn off the UPS, and unplug the supply lead from the AC input supply and from the UPS. Replace the fuse with the same type and rating. 700 / 1000 V A 1500 V A Insert flat blad e screwdriver into slo t Input Fuse Fuse Holder Remov e Remov e Instal l Instal l 1.
21 TROUBLESHOOTING The information below indicates various symptoms a user may encounter in the event the UPStation GXT™ develops a problem. Use this information to determine whether external factors cause the problem and how to remedy th e situation.
22 TROUBLESHOOTING GUIDE PROBLEM CAUSE SOLUTION UPS is short circuited or overloaded Ensure UPS is off. Disconnect all loads and ensure nothing is lodged in output sockets.
23 SPECIFICATIO NS MODEL NUMBER GXT700MT - 120 GXT1000MT - 120 MODEL RATING VA/W 700 / 490 1000 / 700 DIMENSIONS: in (mm) Unit W x D x H 6.4 x 15.6 x 8.9 (162 x 430 x 225) 6.4 x 15.6 x 8.9 (162 x 430 x 225) Shipping W x D x H 11.0 x 19.75 x 14.25 (280 x 502 x 362) 11.
24 SPECIFICATIONS MODEL NUMBER GXT1 000RT - 120 GXT1000RTE - 120 MODEL RATING VA/W 1000 / 700 1000 / 700 DIMENSIONS: in (mm) Unit W x D x H 7.0 x 19.3 x 16.9 (177 x 522 x 430) 7.0 x 19.3 x 16.9 (177 x 522 x 430) Shipping W x D x H 13.38 x 26.0 x 22.25 (340 x 660 x 565) 13.
25 SPECIFICATIONS MODEL NUMBER GXT1500RT - 120 GXT2000RT - 120 GXT3000RT - 120 MODEL RATING VA/W 1500 / 1050 2000 / 1400 3000 / 2100 DIMENSIONS: in (mm) Unit W x D x H 7.0 x 19.3 x 16.9 (177 x 522 x 430) 7.0 x 19.3 x 16.9 (177 x 522 x 430) 7.0 x 19.3 x 16 .
26 BATTERY CABINET SPECIFICATIONS MODEL NUMBER GXT36VBATT GXT48VBATT GXT96VBATT Used w/ UPS Model 1000RT 1500RT 2000RT/3000RT DIMENSIONS: in (mm) Unit W x D x H 177 x 522 x 430 (7.0 x 19.3 x 16. 9) 177 x 522 x 430 (7.0 x 19.3 x 16. 9) 177 x 522 x 430 (7.
27 LIMITED WARRANTY Liebert Corporation extends the following LIMITED WARRANTY to th e purchaser and to its customer (collectively referred to as the "Purchaser"): the enclosed Uninterruptib.
28 1050 Dearborn Drive Columbus, OH 43229 614 - 888 - 0246 Technical Support U .S.A. 1- 800 - 222 - 5877 Outside the U.S.A. 614 - 841 - 6755 U.K. +44 (0) 1793 553355 France +33 1 4 87 51 52 Germany +49 89 99 19 220 Italy +39 2 98250 1 Netherlands +00 31 475 503333 E- mail upstech@liebert.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Liebert 700-3000 VA c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Liebert 700-3000 VA - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Liebert 700-3000 VA, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Liebert 700-3000 VA va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Liebert 700-3000 VA, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Liebert 700-3000 VA.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Liebert 700-3000 VA. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Liebert 700-3000 VA ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.