506 01 5102 00 March 2008 INST ALLA TION INSTRUCTIONS 3-Phase R-410A Split System Heat Pump Product Fam ily: H4H3 These instructions must be read and understood completely before attempting installation. DANGER, W ARNING, CAUTION, and NOTE The signal words DANGER, W ARNING, CAUTION, and NOTE are used to identify levels of hazard seriousness.
INST ALLA TION INSTRUCTIONS 3-phase R-410A Split System Heat Pump 2 506 01 5102 00 INSPECT NEW UNIT After uncrating unit, inspect thoroughly for hidden damage. If damage is found, notify the transportation company immediately and file a concealed damage claim.
INST ALLA TION INSTRUCTIONS 3-phase R-410A Split System Heat Pump 506 01 5102 00 3 Figure 1 Clearances (various examples) W all 6” 24” Service W all W all W all 6” 6” Post W all W all 18” 18.
INST ALLA TION INSTRUCTIONS 3-phase R-410A Split System Heat Pump 4 506 01 5102 00 UNIT SUPPORT NOTE: Unit must be level 2 degrees ( inch rise or fall per foot of run) or compressor may not function properly . A. GROUND LEVEL INST ALLA TION The unit must be lev el and support ed above grade by beams, platfor m, or a pad.
INST ALLA TION INSTRUCTIONS 3-phase R-410A Split System Heat Pump 506 01 5102 00 5 REFRIGERA TION SYSTEM A. COMPONENT MA TCHES Check to see that the proper system components are in place, especially the indoor coil. R-410A outdoor units can only be used with R-410A specific indoor coils.
INST ALLA TION INSTRUCTIONS 3-phase R-410A Split System Heat Pump 6 506 01 5102 00 transmission between the tubing and the foundation or wall. Along floor or ceiling joists, suspend refrigerant lines so that they do not contact the building structure, water pipes, or ductwork.
INST ALLA TION INSTRUCTIONS 3-phase R-410A Split System Heat Pump 506 01 5102 00 7 F . SERVICE V AL VES Service valves are closed and plugged from the factory . Outdoor units are shipped with a refrigerant charge sealed i n the unit. Leave the service valves closed until al l other refrigerant system work is complete or the charge will b e lost.
INST ALLA TION INSTRUCTIONS 3-phase R-410A Split System Heat Pump 8 506 01 5102 00 Figure 7 Deep V acuum Gauge Response and System Conditions 500 MINUTES 01 24 6 1000 1500 LEAK IN SYSTEM V ACUUM TIGHT.
INST ALLA TION INSTRUCTIONS 3-phase R-410A Split System Heat Pump 506 01 5102 00 9 ELECTRICAL WIRING ! W ARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in per‐ sonal injury or death. Before installing, modifying or servicing system, turn OFF the main (remote) electrical disconnect device.
INST ALLA TION INSTRUCTIONS 3-phase R-410A Split System Heat Pump 10 506 01 5102 00 Figure 1 1 T ypical Thermostat (Control Circuit) Connections LEGEND 24-V FACTORY WIRING 24-V FIELD WIRING FIEL.
INST ALLA TION INSTRUCTIONS 3-phase R-410A Split System Heat Pump 506 01 5102 00 11 DEFROST SYSTEM A. DEFROST THERMOST A T The defrost thermostat is factory installed on a short tube stub extending from the coil end plate. Refer to Figure 12 and confirm that the thermostat is securely fastened in place on the tube stub.
INST ALLA TION INSTRUCTIONS 3-phase R-410A Split System Heat Pump 12 506 01 5102 00 ST ART-UP PROCEDURE 1. Set indoor thermostat selector switch to OFF . 2. T urn ON all electrical disconnect devices. 3. I f unit has a crankcase heater , energize the heater and wait 24 hours before proceeding.
INST ALLA TION INSTRUCTIONS 3-phase R-410A Split System Heat Pump 506 01 5102 00 13 Figure 14 R-410A Required Liquid Line T emperature ( ° F) - Cooling Mode Measured Liquid Pressure (psig) Rating Pla.
INST ALLA TION INSTRUCTIONS 3-phase R-410A Split System Heat Pump 14 506 01 5102 00 TROUBLESHOOTING Some models are factory equipped with the Comfort Alert t Diagnostics device in the control box (refer to Figure 15). Comfort Alert provides around-the-clock monitoring for common electrical problems, compressor defects, and broad system faults.
INST ALLA TION INSTRUCTIONS 3-phase R-410A Split System Heat Pump 506 01 5102 00 15 Figure 16 Comfort Alert t Diagnostics (some models) Status LED Status LED Description Status LED T roubleshooting In.
INST ALLA TION INSTRUCTIONS 3-phase R-410A Split System Heat Pump 16 506 01 5102 00 Figure 17 Comfort Alert t Diagnostics (some models) Miswired Module Indication T roubleshooting Information Green LED is not on, module does not power up Determine if both R and C module terminals are connected.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté HP (Hewlett-Packard) H4H3 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du HP (Hewlett-Packard) H4H3 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation HP (Hewlett-Packard) H4H3, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le HP (Hewlett-Packard) H4H3 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le HP (Hewlett-Packard) H4H3, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du HP (Hewlett-Packard) H4H3.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le HP (Hewlett-Packard) H4H3. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei HP (Hewlett-Packard) H4H3 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.