INST ALLA TION INSTRUCTIONS Place Bar Code Here 62-2016-05 TB7600 Series Comm unicating R TU/Heat Pump Thermostats F OR COMMERCIAL HV A C APPLICATIONS APPLICATION The TB7600 Serie s PI thermostat fami ly is specif ically designed for single stage and multi-stage control of h eating/ cooling eq uipment such as rooftop and self -contained unit s.
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS 62-2016—05 2 • Remote indo or averagin g sensing with 2, 3, 4, 9 or 16 sensors • Remote dis charge air sensor i nput • Automatic frost pro.
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS 3 62-2016—05 1 Use prog rammabl e models only when i nstalling as sta ndalone thermostats th at may e ventu ally be added to a WEBs- AX network. When a programmable thermo stat is added to a net work, schedu les should be applied t hrough the WEB- Station-AX.
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS 62-2016—05 4 CAUTION Electronic controls ar e static sensitive device s. Discharge yourself properly befo re manipulation an d installing the thermo stat. Short cir cuit or wrong wir ing may permanent ly damage the th ermostat or th e equipment.
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS 5 62-2016—05 Wiring Identification and Screw T erminal Arra ngement Ta b l e 1 . T erminal i dentifica tion Fig.
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS 62-2016—05 6 Detailed Wiring Diagra ms for Selected Models Fig. 6. TB765 6B5x00(x) 2 Heat/2 Cool/Economizer/Pr ogrammable Fig. 7. TB7652H5x0 0(x) Heat pump/Pro grammable Sensor Wiring f or all Thermostat Models Remote mo unt outdoor tem perature sens ors must be10 K ohm NTC @ 7 7 F .
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS 7 62-2016—05 Fig. 8. Wiring example of single re mote wall mounted ro om sensor Fig. 9. Wiring examples of tw o remote wall mounted r oom sensors f or averagin g applications Fig.
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS 62-2016—05 8 THERMOSTAT USER INTERFACE The ther mostat features a two-line, eight-characte r display . There is a low-le vel backlit lev el that is a lwa ys ac tive and can only be seen at night.
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS 9 62-2016—05 User menu flo w char t NO TE: Promp ts may not all be pres ent depending on model se lected User Contr ol Options The TB7600 Series.
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS 62-2016—05 10 T able 6. Sequence o f user menu: **Appears only in unoccupied mo de ***Appears on ly in ov err ide mode There is a default profile set in the therm ostat from th e factory . This enables the ther mostat to operate as a non- programmable unit in day mode ope ration at star t up.
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS 11 62-2016—05 T EMPERATURE SETPOINTS P ermanent setpoint c hanges This menu per mits the adju stment of all per manent temperature set points (occupied and unoccupied) as well as the desired temperature un its (°F or °C) as shown in T able 7.
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS 62-2016—05 12 2 Event Schedule Setup an d Examples T able 8. Set 2 Events P er Day Men u Navigation T able 9.
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS 13 62-2016—05 4 Event Schedule Setup an d Examples T abl e 11. Set 4 Events P er Day Menu Navigation T able 12. Example 1 - Fou r event retail establishment s chedule * Programming events to the same time will ca ncel the last pe riod and le av e th e ther mostat in unoccup ied mode T able 13.
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS 62-2016—05 14 CLOCK/DAY SETTINGS This secti on of the menu perm its the user to set the time an d day .
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS 15 62-2016—05 INSTALLER CONFIGURATI ON PARAMETER MENU This section des cribes the parameters available f or TB76 00 Series t hermo stat configuration.
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS 62-2016—05 16 Get F rom Get F rom another thermostat configuration utility Def ault va lue = 255 Range is : 0-254 Conditional p arameter to wireless m odels (TB76xxX5 x14W) This parameter is only available f or w ireless ther mostats.
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS 17 62-2016—05 Pwr del Po wer-up delay Default value = 10 seconds On initial power up of the ther mostat (each tim e 24 V ac power supply is removed and re-applie d) there is a d elay bef ore any operation is autho rized (fan, cooling or he ating).
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS 62-2016—05 18 Anticycle Minimum on/ off operation time for stages Def ault val ue = 2 minutes Minimum on/off op eration time of co oling and heatin g stages. CAUTION Anti-sho rt cycling can b e set to 0 minutes f or equipment th at has an anti cycling t imer .
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS 19 62-2016—05 C stage Or HP stage Number of coolin g stages 2 stages model only Def ault val ue = 2 stages For heat pump models, HP stage select.
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS 62-2016—05 20 NO TE: For Heat Pump models: When the outsi de air sensor is not connect ed or is shorted, the thermostat bypa sses the heati ng/cooling loc kouts and the low/h igh balance poin ts.
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS 21 62-2016—05 T able 17. Addition al Configurat ion Parameters for Economiz er Models Configurati on parameter s Signific ance Default v alue Adjustments Chngstpt Changeover setpoint Default value = 55 F (13.
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS 62-2016—05 22 T able 18. T roubleshooting Gu ide for all Models Symptom Possible Cause Corrective Ac tion No display on the therm ostat Absent o.
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS 23 62-2016—05 T able 19. T roubleshooting Guide for Heat Pump Mode ls Symptom P ossible Cause Correctiv e Action Auxiliary heat doe s not operat.
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS 62-2016—05 24 SPECIFICATIONS Networ k Protocol: Models av ailable in BA Cnet MS/TP or ZigBee wireless mesh WEBs-AX Controllers: Compatible with WEB-2xx, WEB-6xx, and W EB-7xx Platform: WEB-2xx and WEB-6xx - W EBStation-AX 3.
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS 25 62-2016—05 Agency Approvals all models: UL: UL 873 (US) and CSA C22.2 No . 24 (Canada), File E277 34 with CC N XAPX (US) and XAPX7 (Canada) I.
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS 62-2016—05 26.
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS 27 62-2016—05.
TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS Automation and Control Solutions Honeywell Intern ational Inc. 1985 Douglas Drive North Golden Valley, MN 55422 customer.hone ywell.com ® U.S . Registered T rademark © 2011 Honey well International Inc.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Honeywell SERIES COMMUNICATING TB7600 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Honeywell SERIES COMMUNICATING TB7600 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Honeywell SERIES COMMUNICATING TB7600, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Honeywell SERIES COMMUNICATING TB7600 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Honeywell SERIES COMMUNICATING TB7600, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Honeywell SERIES COMMUNICATING TB7600.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Honeywell SERIES COMMUNICATING TB7600. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Honeywell SERIES COMMUNICATING TB7600 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.