Manuel d'utilisation / d'entretien du produit L7224A du fabricant Honeywell
Aller à la page of 16
INST ALLA TION INSTRUCTIONS 68-0281-16 L7224A,C; L7248A,C,L Oil and Electric Boiler Electr onic Aquastat ® Contr oller s APPLICA TION The L7224A,C and L72 48A,C,L 2012 Compliant Electronic Aquastat ® Cont rollers provide electronic temperature sensing in a UL limit-rate d control with a single sensing pr obe.
L7224A,C; L7248A, C,L OIL AND ELEC TRIC BOILER ELECTRONIC AQ UASTAT ® CONTROLLERS 68-0281—16 2 Accessorie s: W8735Y1000 Wire less Outdoor Reset Kit W8735ER1000 Wi reless Outdoor Res et Module C7089.
L7224A,C; L724 8A,C,L OIL AND ELECTR IC BOI LER ELECTRONIC AQUASTAT ® CONTROLLERS 3 68-0281—16 New Installation Order well assemblies separate ly; see T able 1 and form no. 68-0040, Immersion Wells and Compre ssion Fittings for T emperatu re Controllers.
L7224A,C; L7248A, C,L OIL AND ELEC TRIC BOILER ELECTRONIC AQ UASTAT ® CONTROLLERS 68-0281—16 4 Fig. 4. Replace ment sensor inst allation. Replacement Sensor Installation T ur n off all power and: 1. Carefully disconn ect sensor from circuit boar d by pulling gently on the connector.
L7224A,C; L724 8A,C,L OIL AND ELECTR IC BOI LER ELECTRONIC AQUASTAT ® CONTROLLERS 5 68-0281—16 A separate electromecha nical high-limit is no t required in a system that u ses this contr ol to meet Underwr iters Laboratorie s Inc. requirem ents for oil-fired boiler assemblies, UL 726.
L7224A,C; L7248A, C,L OIL AND ELEC TRIC BOILER ELECTRONIC AQ UASTAT ® CONTROLLERS 68-0281—16 6 1 Display shows local setting; not the setting as modified by an external enviracom control. 2 Settings are viewable only if the outdoor reset module and ou t- door temperature sensor are installed and functioning properly.
L7224A,C; L724 8A,C,L OIL AND ELECTR IC BOI LER ELECTRONIC AQUASTAT ® CONTROLLERS 7 68-0281—16 NO TE: This feature is b locke d if a Domestic Hot W ater demand occurs.
L7224A,C; L7248A, C,L OIL AND ELEC TRIC BOILER ELECTRONIC AQ UASTAT ® CONTROLLERS 68-0281—16 8 Fig. 8. L7224A, C; L7248L single hea t zone with indirec t water tank and cir culator s.
L7224A,C; L724 8A,C,L OIL AND ELECTR IC BOI LER ELECTRONIC AQUASTAT ® CONTROLLERS 9 68-0281—16 * Error condit ion only available when the Outdoor Reset M odule is installed. T able 6. L7224/L724 8 Controller Opera ting Sequence . Action System Respons e Thermostat calls fo r heat.
L7224A,C; L7248A, C,L OIL AND ELEC TRIC BOILER ELECTRONIC AQ UASTAT ® CONTROLLERS 68-0281—16 10 . a W ar nings ar e generated to enunciate the system is not operating optimally , b ut t he Aquastat is still o perating and maintaining boiler temperature.
L7224A,C; L724 8A,C,L OIL AND ELECTR IC BOI LER ELECTRONIC AQUASTAT ® CONTROLLERS 11 68-0281—16 Fig. 9. L72 24A,C multiz one system with cir culator connec tions. Boiler is hot, house is cold. Display is ON. 120 V ac at C1 -C2 • 120 V ac at C1-C2, check wir ing to pump.
L7224A,C; L7248A, C,L OIL AND ELEC TRIC BOILER ELECTRONIC AQ UASTAT ® CONTROLLERS 68-0281—16 12 Fig. 10. L7 224A,C sing le zone s ystem with circulator and in direct wate r tank wit h EnviraCOM™ thermosta t. M32025B POWER SUPPL Y . PRO VIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQ UIRED.
L7224A,C; L724 8A,C,L OIL AND ELECTR IC BOI LER ELECTRONIC AQUASTAT ® CONTROLLERS 13 68-0281—16 Fig. 11. L72 48L multizon e system with cir culator con nections. M29655A POWER SUPPL Y . PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 1 CONTROL CASE MUST BE CONNECTED TO EARTH GROUND.
L7224A,C; L7248A, C,L OIL AND ELEC TRIC BOILER ELECTRONIC AQ UASTAT ® CONTROLLERS 68-0281—16 14 Fig. 12. L7 224/L7248 m ultizone system wi th Outdoor Reset an d Domestic Hot W ater Modules (indirect tank applicatio ns). M32024A POWER SUPPL Y . PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
L7224A,C; L724 8A,C,L OIL AND ELECTR IC BOI LER ELECTRONIC AQUASTAT ® CONTROLLERS 15 68-0281—16 Fig. 13. L7248L Ext ernal Low Li mit connec tions. M271 13 POWER SUPPL Y . PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 1 CONTROL CASE MUST BE CONNECTED TO EARTH GROUND.
L7224A,C; L7248A, C,L OIL AND ELEC TRIC BOILER ELECTRONIC AQ UASTAT ® CONTROLLERS Automation and Control Solutions Honeywell Intern ational Inc. 1985 Douglas Drive North Golden Valley, MN 55422 customer.hone ywell.com ® U.S . Registered T rademark © 2013 Honey well International Inc.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Honeywell L7224A c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Honeywell L7224A - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Honeywell L7224A, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Honeywell L7224A va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Honeywell L7224A, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Honeywell L7224A.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Honeywell L7224A. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Honeywell L7224A ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.