Manuel d'utilisation / d'entretien du produit RC-1000 du fabricant Home Automation
Aller à la page of 16
1 1 RC-1000 Th ermostat Installation Ins tructions DESCRIPTION The RC-1000 is a precision digital thermostat designed for 24 VAC he ating and cooling systems.
2 2 Location When replacing an ex isting thermostat, install the RC-1000 in the same location. If the existing location doesn' t meet the following criteria, choose a n ew location to mount the RC-1000. When choosing a location for the thermostat: 1.
3 3 Connect each wire to the terminal st rip(s) on the thermostat base per the wiring diagram for your system application - See Figures 4 - 7. Form the thermostat wiring so that the ca ble lies flat between the termina l strip(s) and the center of the base - See Figure 2 .
4 4 TYPICAL WIRING DIAGRAMS CA UTION : Do not short gas valve, fan, heat relay, or cool rela y ...even momentaril y. Do not attempt to hook up to live circuits. An accidental connection to a component on the thermostat circuit board could cause damage to the thermostat.
5 5 3. When configured as a co nventional thermostat, by default this the rmostat does not turn the fan on with a call for heat. If the furnace requi res the thermostat to turn the fan on with a call for heat, confi gure the “System Mode” to “Fan On W ith Heat” under “System Options” .
6 6 Single Stage Conventional 24VAC " HOT" Heat 24VAC Com mon* Fan Cool UP 24V AC CONTROL TRANSM FOMER Fan Relay Cool Relay Heat Relay HVAC SYSTEM THERMOSTAT (RC) (C) (Y1) (G) (W1) 1 3 8 6 7 * Common wire is required in “heat only” or “cool only” applications .
7 7 About Heat Pump System s 1) Terminal 5 (O) is energized for coolin g Terminal 6 (B) is energized for heating In most applications, the reversing valve is energiz ed for cooling and should be connected to the "O" terminal.
8 8 Heat Pum p (2 Stage Heat / 1 Stage Cool) 24VAC Common 24VAC "HOT" Auxilirary Heat Compressor Ground Fault Fan Compressor Relay Aux Heat Relay Fan Relay Fault Relay Reversing Valve Energi.
9 9 REMOTE SYSTEM WIRING DIAGRAMS This thermostat has been prepro grammed with energ y saving pro gram schedules in accordance with the ENERGY STAR ® program. W hen used with a remote system, HAI recommends that the Program Mode be configured as “None” or “Occup ancy”.
1 1 0 0 REMOTE SETBACK SWITCH The thermostat can be connected to a remote switch to toggle the desired heat and cool temperature se ttings between preset setpoints.
1 1 1 1 REMOTE TEMPERATURE SENSOR A remote temperature se nsor can be installed to monitor the temperature from a re mote location or can be combined with the onboard temperature sensor for the average temperature of two locations. Run a twisted pair, shielded cable from the RC-10 00 to the remote temperature sensor location.
1 1 2 2 SETUP AND CONFI GURATION NOTE: For proper operation of the features of this thermostat, the Ti me and Date must be set. Even w hen connected to an HAI controller which sets the time and day, the Date must be manually set in the ther mostat under the “S ettings” menu.
1 1 3 3 System Type *Conventional Dual Fuel Heat Pump 1 Heat Pump *Auto Changeover No Fan With Heat Auto Changeover Fan On With Heat Auto Changeover Fan On With Heat Auto Changeover Fan On With Heat M.
1 1 4 4 Cool Mi ni mu m On The number of minutes the thermostat forces the cooling system to remain on before turning off. Raising this number will increase the total time the cooling s y stem is on (saving energ y ), but may allow the temperature to drif t farther from setpoint (decreasing comfort).
1 1 5 5 Auxiliary Heat Diffe rential: This determines how far from the setpoint the temperature has to be b efore the auxiliary heat turns on. This is onl y available for heat pump s y stems.
1 1 6 6 TROUBLESHOOTIN G TIPS SYMP TOM ACTION TO TAKE 1. Check power to the thermostat Thermostat Dead 2. Check wiring diagrams SYMP TOM ACTION TO TAKE 1. Check for break in W or Y wire 2. Allow minimum off time to pass 3. Check sy stem options for correct setting s 4.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Home Automation RC-1000 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Home Automation RC-1000 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Home Automation RC-1000, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Home Automation RC-1000 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Home Automation RC-1000, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Home Automation RC-1000.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Home Automation RC-1000. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Home Automation RC-1000 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.