Manuel d'utilisation / d'entretien du produit 6000 du fabricant Herrmidifier Co
Aller à la page of 24
6000 Series Electronic Steam Humidifiers Installation Operation Service OWNER’S MANUAL The 6000 Series Humidifiers represent tha t latest in humidification technology. Please read these instructions carefully for trouble free operation and to get the most out of you r purchase.
TABLE OF CONTENTS TABLE OF CONTENTS ...................................................................................................................................................... 3 SECTION I WARRANTY............................................
SECTION I WARRANTY Warranty 1. Herrmidifier warrants to the buyer or any user during the duration of the Warr anty that the humidifier described in this manual will be free from defects of material and workmanship for a period of two (2) years from the date of shipment.
SECTION II UNIT OPERATION Basic Operation Controlled humidification requires a very precise control system. The 6000 utilizes a solid state control to monitor performance and maintain humidity. The humidifier evaluates the operation and alerts the operator to problem conditions and prevents undesirable operation.
Key Features Adjustable Setpoints Capacity • Range = 50-100% • Preset at 100% for 6000-1,3,4 Preset at 50% for 6000-2 Low Drain Threshold • Range = 50-100% • Preset at 90% Cycle Time • Range.
Engineering and Application The Herrmidifier 6000 Series Steam Humidifiers can be applied in a variety of applications. The simplest application is to utilize the model with the built-in blower package (6000-1,2). The steam generated by the unit is distributed into the conditi oned space by the built-in blower package (Figure 1).
SECTION III INSTALLATION INSTRUCTIONS Mounting The cabinet is designed to safely contain the working components of the Herrmidif ier 6000 series humidifier and dissipate heat to protec t the electronics. Locate humidifier, steam pipe and accessories in a manner to allow routine inspection and any necessary maintenance.
Steam Distribution Blower Version (6000-1,2) The 6000 Series Steam Humidifier with the built in blower pack should be mounted a minimum of 18” from the ceiling. There should also be 5' of horizontal clearance in front of the unit to prevent stem from condensing on obstructions (S ee Figure 1).
Wiring All field wiring should be routed up through the knockout in the bottom panel or in the back of the unit. Supply Power. 1. Insure that minimum circuit ampacity is 15 amps. 2. Terminals are provided in the electrical compartment for field connection of the main power supply legs (single phase) and a ground wire.
SECTION IV OPERATING INSTRUCTIONS Start-up Instructions 1. Check that the humidif ier is properly mounted and level. 2. Check that the water fill and drain are properly connected. 3. Check that the correct voltage and amperage services are supplied. 4.
Checklist NOTE The Herrmidifier 6000 Humidifier checklist is provided to help the installer insure a successful installation. I f further assistance is needed from the Herrmidifier represent ative or the factory, the checklist is expected to be completed.
Maintenance To maintain output, the water level in the cylinder will slowly move upwards, exposing new electrode to the water as the electrodes become coated with minerals. Eventually, all of the usable electrode surfaces will be coated and the cylinder will be full of water.
SECTION V TROUBLESHOOTING GUIDE All Herrmidifier 6000 Series Humidifiers are manufactured under strict quality control and are subjected to a complete operational test.
Problem / Symptom Probable Cause Reason - Correction Dead short between electrodes. Replace the steam cylinder. Check resistance between electrodes with power “off” Restricted or blocked drain. Clean and inspect drain system. Restricted fill system Clean and inspect the fill system.
Non-Fault Activated Problems: Problem / Symptom Reason - Correction Check the wiring at the 24 VAC breaker for a short or loose connection. Disconnect the contractor coil from the circuit and repeat. If 24-volt breaker doesn’t blow, replace the contractor.
Problem / Symptom Reason - Correction Check drain valve and insure that water drains freely. If necessary , clean or replace valve if defective. Check water supply. If it is commercially softened, either increase the drain threshold (R18) to 92% or rec onnect the unit to raw water.
Blow er Version Wiring Diagram(6000-1 and 6000-2) 17.
Blow er Version Exploded View (6000-1 and 6000-2) 18.
Blow er Version Parts List (6000-1 and 6000-2) 1845 Door Interlock 1826 Humidistat Element EST-003 Cylinder Full Interface (Set to “A”) EST-105A Toroid Transformer EST-1001B Main Circuit Board EST.
Ducted Version Exploded View (6000-3 and 6000-4) 20.
Ducted Version Parts List (6000-3 and 6000-4) 1845 Door Interlock EST-003 Cylinder Full Interface (Set to “A”) EST-105A Toroid Transformer EST-596 Steam Hose EST-1001B Main Circuit Board EST-1062 .
Ducted Version Wiring Diagram (6000-3 and 6000-4) 22 22.
SECTION VI SUGGESTED SPECIFICATIONS Suggested Specifications Part I-Scope • Furnish a system of humidificat ion for the areas known as______________________________________. • Operation of the system shall be cont rolled automatically to maintain _____%R.
Herrmidifier Office: 101 McNeill Road • Sanford, NC 27330 Phone: 800-884-0002 • Fax: 919 -777-6300 • www.herrmidifier.com • email: herrsales @therrmidifier.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Herrmidifier Co 6000 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Herrmidifier Co 6000 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Herrmidifier Co 6000, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Herrmidifier Co 6000 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Herrmidifier Co 6000, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Herrmidifier Co 6000.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Herrmidifier Co 6000. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Herrmidifier Co 6000 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.