2175 West Park Place Blvd. • Stone Mountain, GA 30087 • (770) 465-5600 • Fax: (770) 465-5990 INST ALLA TION & OPERA TING INSTRUCTIONS FOR 02/01 Part Number 25001501 ®.
BEACON CONTROLLER 2 QUICK GUIDE Installation, Start-Up, Operation, T roubleshooting Installation • Use 18 gauge wire for 24-volt connections between evaporators and condensing unit. • Remove suction line sensor before brazing; reinstall suction sensor after brazing is completed and suction line has cooled; insulate with insulation provided.
BEACON CONTROLLER 3 QUICK GUIDE (cont’d.) Defrost • The actual defrost time is determined when power is first applied to the system as well as the number of defrosts per day . If a Smart Controller is used, the actual defrost times are programmed into the Smart Controller .
BEACON CONTROLLER 4 INST ALLA TION INSTRUCTIONS Before Installing or Starting Unit: • Use a minimum 18 gauge wire for low voltage connections to cooler , condensing unit and Smart Controller . • T ransformer is shipped wired for 240V primary; if your supply voltage is 208V , change to the 208V tap.
BEACON CONTROLLER 5 REFRIGERANT LINE BRAZING (CAUTION) The electric expansion valve on the liquid line and the suction temperature sensor on the suction line are factory installed. Care must be taken when brazing these lines at the evaporator . T oo high a temperature may destroy these components.
BEACON CONTROLLER 6 ROOM TEMPERA TURE CONTROL (Cont’d.) • Another method of setting the room set-point is to use the Beacon board thermostat pot. If a value other than that available by using a fixed resistor is required, the pot on the Beacon board can be used.
BEACON CONTROLLER 7 BEACON MICROPROCESSOR SETTINGS (See T able 3 for more details.) Selections to be made by applying movable jumpers: Defrost cycles or time - Controlled by the board in master unit only . Selection must be either “elapsed” time or “run” time.
BEACON CONTROLLER 8 OPERA TING INSTRUCTIONS REFRIGERA TION MODE ST ART UP 1. Check all wiring connections to be sure they are correct and tight. 2. Check voltage taps on transformer . The transformer is shipped wired for 240. If your supply voltage is 208 volt systems, charge to 208 voltage tap.
BEACON CONTROLLER 9 Ambients below 50 ° F and above 10 ° F At the initial application of power to the system, the compressor and the evaporator fans will be in a four minute hold-off cycle and will not start immediately . When there is a call for cooling, the compressor starts and the electric expansion valve (EEV) stays closed for 12 seconds.
BEACON CONTROLLER 10 PUMP-DOWN At the end of each cooling cycle, when the box temperature is met, the system will pumpdown and shut off. T o pumpdown, the EEV closes and the compressor pumps down until the low pressure switch trips the unit off, or two minutes have elapsed.
BEACON CONTROLLER 11 ST A TUS INDICA TOR There is a red status indicator light on the Beacon board. This light has a controlled blink sequence to indicate modes such as cooling, superheat, off, defrost, or error . (See status light blink sequence chart.
BEACON CONTROLLER 12 Error Codes • One blink — Superheat sensor shorted or open • T wo blinks — Room temperature sensor shorted or jumper not installed • Three blinks — Compressor discharg.
BEACON CONTROLLER 13 OPTIONAL SMART CONTROLLER The Beacon Smart Controller performs all the standard Beacon functions with the additional benefit of remote mounting for easy access. From the Smart Controller , the refrigeration system can be monitored and the program parameters changed, without the user going into the Cooler or Freezer Box.
BEACON CONTROLLER 14 T ABLE 3 The initial factory settings for the BEACON MICROPROCESSOR BOARD are indicated on the following chart. ELECTRIC DEFROST AIR DEFROST F ACTOR Y SETTINGS F ACTOR Y SETTINGS .
BEACON CONTROLLER 15 T o test the Beacon board place the test jumper to the “TEST” position. The board will then cycle through each output for 10 seconds. It will energize and de-energize the fan motor , electric heater, expansion valve and compressor for 10 seconds.
BEACON CONTROLLER 16 F AUL T OR PROBLEM THINGS T O CHECK System runs 4 minutes then cycles off, then repeats 1. Check if sensors are connected correctly; if evaporator in/out are switched, this will cause low superheat 2. Check if system is piped properly 3.
BEACON CONTROLLER 17 BEACON TROUBLE-SHOOTING GUIDE (cont’d.) System will not run 1. Check if red jumper wire (next to blue pot) is correctly connected across “X” terminals 2. Check red jumper wire terminals to make sure they are connected to the wire, not the insulation 3.
BEACON CONTROLLER 18 BEACON UNI-POLAR EXP ANSION V AL VE TEST VOL T AGES ESV TEST (Beacon Board connection) (dc volts) BLUE RED WHT BLK YEL V AL VE OPEN 4.4 15.6 15.6 15.7 15.6 V AL VE CLOSED 0 15.3 15.3 15.4 15.5 Com 24 Vdc Notes: 1. All volts shown are measured while in the “TEST” mode and are DC 2.
BEACON CONTROLLER 19 SERVICE DIAGNOSIS CHART - BEACON PROBLEM POSSIBLE CAUSE POSSIBLE CORRECTIVE ACTION Compressor will not run 1. 4 min. off cycle 1. W ait 4 min. 2. Box temp is below t’stat setting 2. Lower t’stat setting 3. Loose wiring 3. Check all wire terminals; tighten if necessary .
BEACON CONTROLLER 20 PROBLEM POSSIBLE CAUSE POSSIBLE CORRECTIVE ACTION Beacon Board Status 1. Supply voltage too high 1. Check 24 volt supply; if above 30 volt Light Flashes Erratically correct immediately . 2. Supply voltage too low 2. Change transformer primary to correct supply 3.
BEACON CONTROLLER 21 SERVICE DIAGNOSIS CHART - GENERAL PROBLEM POSSIBLE CAUSE POSSIBLE CORRECTIVE ACTION Low suction pressure 1. Insufficient refrigerant 1. Check system for leaks; repair leaks & add refrigerant 2. Freezer coil iced up 2. Check defrost system operation & correct fault condition 3.
BEACON CONTROLLER 22.
BEACON CONTROLLER 23.
BEACON CONTROLLER 24.
BEACON CONTROLLER 25.
BEACON CONTROLLER 26.
BEACON CONTROLLER 27.
BEACON CONTROLLER 28.
BEACON CONTROLLER 29.
BEACON CONTROLLER 30.
BEACON CONTROLLER 31.
BEACON CONTROLLER 32.
BEACON CONTROLLER 33.
BEACON CONTROLLER 34.
BEACON CONTROLLER 35 Notes.
Visit our web site at www .heatcraftrpd.com for T echnical Literature Online. Since product improvement is a continuing effort at Heatcraft, we reserve the right to make changes in specifications without notice.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Heatcraft Refrigeration Products 25001501 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Heatcraft Refrigeration Products 25001501 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Heatcraft Refrigeration Products 25001501, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Heatcraft Refrigeration Products 25001501 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Heatcraft Refrigeration Products 25001501, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Heatcraft Refrigeration Products 25001501.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Heatcraft Refrigeration Products 25001501. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Heatcraft Refrigeration Products 25001501 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.