60 kW InfraStruXur e PDU PD60H5HK1 PDRPPH1000 Operation and Configuration 400/230 V.
.
60kW InfraStruXure PDU—Op eration and Co nfigur ation i About This Manual Audience This manual is intended for end-users of a 60 kW InfraStruXure PDU. It covers the operation, customization, and quick config uration of the PDU, and includ es basic InfraStruXure system operation.
.
Contents 60kW InfraStruXure PDU—Operation and Configuration iii Safety ............................. ........................ ................. 1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Save these instructions .
iv 60kW InfraStruXure PDU—Operation and Configuration Alarms Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 View Active Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Alarm/Event Log . . . . .
60kW InfraStruXure P DU—Operation and Config uration v Communication Configuration ................................ 31 InfraStruXure PDU Management Options . . . . . . . . . . . . . . . . . 31 Overview . . . . . . . . . . . . . . . . . . . . . . . .
vi 60kW InfraStruXure PDU—Op eration and Configuration How to Test the Emergenc y Power Off Switch . . . . . . . . . . . . . 49 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Testing the switch . . . . . . . . . .
60kW InfraStruXure PDU—Op eration and Co nfigur ation 1 Safety Over view Save these instru ctions This manual contains important instructions t hat must be followed during installation, operation, and maintenance of the PDU.
2 60kW InfraStruXure PDU—Op eration and Configuration Wa r n i n g s Unpacking/moving DO NOT tilt the PDU greater than 45° from its ver tical axis. Never l a y the PDU on its side.
Safety 60kW InfraStruXure PDU—Op eration and Co nfigur ation 3 Emer gen cy Power Off (EPO) This InfraStruXure PDU is provided with an Em ergency Power Off switch connection. When this EPO switch is energized, electrical power to the units is de-ener gized and the system will not transfer to on-battery operation.
.
60kW InfraStruXure PDU—Op eration and Co nfigur ation 5 PDU Display Interface Over view Use the display interface to config ure settings, set alarm thresholds, and provide audible and visual alarms.
PDU Display Interface 6 60kW InfraStruXure PDU—Op eration and Configuration T op-level status screens After displaying a brief start-up screen after system start-up, the display interface scrolls automatically and continuously through four screens of basic status information.
PDU Display Interface 60kW InfraStruXure PDU—Op eration and Co nfigur ation 7 On some screens, continue arrows ( indicate that there are additional screens to view in the category . Press the Up or Down arrow key to vi ew the additio nal screens.
8 60kW InfraStruXure PDU—Op eration and Configuration Load-Meter Scr een From the Load-Meter screen, you can select the following items: T otal Load by Phase The load supported by e ach phase in kV A, in RMS current ( Ir ms ), and as a percentage of the maximum allowable load ( %LD ).
60kW InfraStruXure PDU—Op eration and Co nfigur ation 9 V olt-Meter Scr een From the V olt-Meter sc reen, you can select the following items: Output V oltage Displays each phase-to-phase output voltage (e.g., L1-2 for phase L1 to phase L2) and each phase-to-neutral output voltage (e.
10 60kW InfraStruXure PDU—Op eration and Configuration Contacts Scr een Overview The PDU can monitor external contact closure even ts. Possible applications include the following: • Magnetic conta.
PDU Display Interface 60kW InfraStruXure PDU—Oper ation and Conf igur ation 11 Alarm Relay Map Configure the relay outputs, using th e Alarm Relay Map. Each Alarm Map corresponds to a rela y output. For example, Alarm Map 01of04 corresponds to the first of four relay outputs.
PDU Display Interface 12 60kW InfraStruXure PDU—Op eration and Configuration How to connect contacts to the PDU monito ring unit 1. Choose one or more contact numbers on the user connection plate to wh ich you will connect the contacts. The user connec tion plate connects to the User/EPO port on the PDU monitoring unit.
60kW InfraStruXure PDU—Oper ation and Conf igur ation 13 Br eakers Scr een Use the Breakers screen to view the status of the system and PDU circuit breakers. Main Input Reports status of PDU Mai n Input switch ( Open or Closed ). Under normal operation, this switch is Closed .
14 60kW InfraStruXure PDU—Op eration and Configuration Alarms Scr een View Active Alarms Use this option of the Al arms screen to display active alarms (alarm s that have not been resolved).
PDU Display Interface 60kW InfraStruXure PDU—Oper ation and Conf igur ation 15 Alarm Setup Use this option of the Al arms screen to access the following options: Alarm Beeper Use this option of the Al arms screen to turn the alarm beeper ON or OFF .
PDU Display Interface 16 60kW InfraStruXure PDU—Op eration and Configuration PDU Alarms This table lists all alarms that can be generated by the PDU, as displayed by the All Possible Alarms option, with numeric variables between the < > charac ters.
60kW InfraStruXure PDU—Oper ation and Conf igur ation 17 Panel Scr een Branch Ckt Loading Y ou can display Branch Ckt Loading (Branch Circuit Loading) stat us if the option to measure current at the distribution ci rcuit breakers is installed. Y ou can view data for each individual panel positio n on the distribution panel.
PDU Display Interface 18 60kW InfraStruXure PDU—Op eration and Configuration Panel Configuration Configure the branch metering se ttings for each circuit breaker on the distribution panel, or con figure both panels simultane ously . T o configure a circuit breaker , select the range that includes the circuit breaker .
PDU Display Interface 60kW InfraStruXure PDU—Oper ation and Conf igur ation 19 Global Panel Config Configures the same number of poles or circuit br eaker ratings for all circuit breakers in both distribution panels simultaneously .
20 60kW InfraStruXure PDU—Op eration and Configuration Config Scr een System/Network Use this option of the Co nfig screen to access these options: System Password • Password : Change the system password required to access protected screens and fields in the display interface.
PDU Display Interface 60kW InfraStruXure PDU—Oper ation and Conf igur ation 21 Electrical Config This option of the Config scre en displays informat ion about the e lectrical serv ice that provides input to the PDU. All of the values displayed on this screen are set at the factory .
PDU Display Interface 22 60kW InfraStruXure PDU—Op eration and Configuration System ID Use this option of the Co nfig screen to identify your PDU. The following fields can b e configured: Factory Defaults Use this option of the Co nfig screen to reset all PDU settings to their factory default values.
60kW InfraStruXure PDU—Oper ation and Conf igur ation 23 Over view InfraStruXur e PDU Fr ont view The PDU Shielding T rough accommodates the power cables exiting the roof of the PDU, and separates power cables from data cables. The PDU power cables supply power to equipment racks; they are fed through knockouts on the top of the PDU.
Overview 24 60kW InfraStruXure PDU—Op eration and Configuration Fr ont view (interior) The two 42-position circuit br eaker panels provide 84 total si ngle pole positions. Each single pole provides power at 230 volts L-N. The amperage each position provides depends on the size of the circuit breaker used.
Overview 60kW InfraStruXure PDU—Oper ation and Conf igur ation 25 Rear view of PDU with transformer (interior) The Main input switch connects to your main power source. The switch accepts 400V input and re quires L1, L2, L3, and PE input conductors.
Overview 26 60kW InfraStruXure PDU—Op eration and Configuration Rear view of PDU without transformer (interior) The Main input circuit breaker connects to either the upstream UPS or Mains. The circuit breaker accepts 400V input and requires L1, L2, L3, N, and P E input conductors.
Overview 60kW InfraStruXure PDU—Oper ation and Conf igur ation 27 PDU monitoring unit This connection provides the input power for the PDU monitoring unit.
Overview 28 60kW InfraStruXure PDU—Op eration and Configuration User connection plate For a detailed description of the user connection plate, see ( ) on page 24. For clarity , the user connection plate in the following illu stration is shown in greater detail.
60kW InfraStruXure PDU—Oper ation and Conf igur ation 29 System Operation How to Apply Power to the System 1. Close (turn ON) the main circuit break er of the power source supplying power to the PDU. 2. Close (turn ON) the Main Input on the PDU. 3. Power the PDU distribution circuit br eakers .
30 60kW InfraStruXure PDU—Op eration and Configuration How to Ensur e T otal Power Off 1. Open (turn OFF) the main breaker on the power source feeding the PDU. 2. Open (turn OFF) the Main Input switch on the PDU. 3. For PDU with transformer : Open (turn OFF) the Main Output circuit breaker on the front of the PDU.
60kW InfraStruXure PDU—Oper ation and Conf igur ation 31 Communication Configuration InfraStruXur e PDU Management Options Overview Y ou have two management options for the InfraS t ruXure PDU.
32 60kW InfraStruXure PDU—Op eration and Configuration Configuring the InfraStruXur e Manager Connect the InfraStruXur e PDU to the InfraStruXur e Manager 1. Connect a Cat-5 netw ork cable to the surge-protected etherne t port on the PDU user con nection plate.
60kW InfraStruXure PDU—Oper ation and Conf igur ation 33 Configuring the Network Management Interface Connect the InfraStruXur e PDU to your network 1. Connect a Cat-5 netw ork cable to the surge-protected etherne t port on the PDU user con nection plate.
Communication Configu ration 34 60kW InfraStruXure PDU—Op eration and Configuration TCP/IP configuration methods Use one of the following methods to define the TCP/I P settings needed by the InfraS truXure PDU: • Device IP Configuration W izard (See “Devi ce IP Configuration W iza rd” on this page.
Communication Configu ration 60kW InfraStruXure PDU—Oper ation and Configuration 35 BOOTP & DHCP configuration The Boot Mode setting, a T C P/IP option in the InfraSt ruXure PDU’ s Network menu, identifies how the TCP/IP settings will be defi ned.
Communication Configu ration 36 60kW InfraStruXure PDU—Op eration and Configuration 3. When the InfraS truXure PDU reboots, the BOOTP server provid es it wi th the TCP/IP settings. – If you specified a bootup file name, the InfraStru Xure PDU att empts to transfer that file from the BOOTP server using TFTP or FTP .
Communication Configu ration 60kW InfraStruXure PDU—Oper ation and Configuration 37 Local access to the control console Y ou can use a local computer that connects to the InfraS truXure PDU through the console po rt on the InfraStruXure PDU monitoring un it to access the control console.
Communication Configu ration 38 60kW InfraStruXure PDU—Op eration and Configuration 2. Use Ping with a size of 1 13 bytes to assign the IP address defined by th e ARP command. For the IP address defined in step 1, use one of the following Ping commands: – W indows command format: ping 156.
60kW InfraStruXure PDU—Oper ation and Conf igur ation 39 How to Access a Network Management Interface on a Configur ed InfraStruXur e PDU We b i n t e r f a c e As your browser, you can use Microsoft ® Intern et Explorer 5.0 (and highe r) or Netscape ® 4.
Communication Configu ration 40 60kW InfraStruXure PDU—Op eration and Configuration T elnet for basic access. T elnet provides the basic sec urity of authentication by user name and password, but not the high-security benefits of encr yption.
Communication Configu ration 60kW InfraStruXure PDU—Oper ation and Configuration 41 FT P a n d S C P Y ou can use FTP (enabled by default) or Secure CoPy (SCP) to transfer new firmware to the InfraStruXure PDU, or to access a copy of the In fraS truXure PDU’ s event logs.
42 60kW InfraStruXure PDU—Op eration and Configuration How to Recover Fr om a Lost Network Management Interface Passwor d 1. Select a serial port at the local computer , and disable a ny service that uses that port.
60kW InfraStruXure PDU—Oper ation and Conf igur ation 43 Customizing and Updating the PDU Important Safety Instructions Ele c tric al Ha zar d APC does not r ecommend that you perform maintenance of the PDU while it is receiving input p ower . However , due to the cr itical nature of data cent er loads, this may occur .
44 60kW InfraStruXure PDU—Op eration and Configuration PDU Or derable Part List Breakers 0M-1293 10 A, single-pole breaker 0M-1706 32 A with 100 mA ELCB, th ree-pole breaker 0M-1304 16 A, single-po .
60kW InfraStruXure PDU—Oper ation and Conf igur ation 45 How to Add Cir cuit Br eakers and Power Cables Add a cir cuit br eaker on the PDU 1. Move the clip on the back of the circuit break er to correspond to the phase to which you are connecting to ( L1 , L2 , or L3 ).
Customizing and Updating th e PDU 46 60kW InfraStruXure PDU—Op eration and Configuration 4. At the front of the PDU, connect the power cord’ s individual wires: a. If you have branch current monitoring insta lle d, route the phase conductor through a current sensor .
60kW InfraStruXure PDU—Oper ation and Conf igur ation 47 How to Connect User Input Contacts and Relay Outputs to the PDU User Connection Plate Overview Make contact closure conn ections (NO or NC) at the us er connectio n plate to monitor dry contacts.
Customizing and Updating th e PDU 48 60kW InfraStruXure PDU—Op eration and Configuration How to connect contacts to the PDU monito ring unit 1. Choose one or more contact numbers on the user connection plate to wh ich you will connect the contacts. The user connec tion plate connects to the User/EPO port on the PDU monitoring unit.
60kW InfraStruXure PDU—Oper ation and Conf igur ation 49 How to T est the Emer gency Power Off Switch Overview Connecting the switch. The Emergency Power Of f (EPO) switch connects to the PDU user connection plate. The figure on the right show s the location of th e user connection plat e on the roof of the PDU.
Customizing and Updating th e PDU 50 60kW InfraStruXure PDU—Op eration and Configuration Configuring and testing. Configuring and testing of the switch is done through the EPO interface on th e PDU monitoring unit. The figure to the right shows the PDU monitoring unit and the location of the EPO LEDs and DIP switches.
Customizing and U pdating the PD U 60kW InfraStruXure PDU—Oper ation and Conf igur ation 51 c. Observe the EPO LEDs. If the switch is wire d and working properly , when the switch is engaged, both of the EPO state LEDs are red. d. If the test was successful, place the Arm/T est rocker switch back to the Arm position.
52 60kW InfraStruXure PDU—Op eration and Configuration How to Download Firmwar e Upgrades Upgrading the PDU monitor pr ocessor Y ou can download available PDU monito r processor upgrades through the PDU display interface.
Customizing and U pdating the PD U 60kW InfraStruXure PDU—Oper ation and Conf igur ation 53 6. From the Control Console menu, select System , then To o l s , then File T ransfer , then XMODEM . 7. The system will prompt you with Perform transfer with XMODEM -CR C? Ty p e Yes and press E NTER .
.
60kW InfraStruXure PDU—Oper ation and Conf igur ation 55 Specifications InfraStruXur e PDU Electrical With T ransformer Without T ransformer Output V oltage A C L1, L2, L3, N, PE 400/230 V : 3W , N, PE Full Load Rating 60 kV A 10 0 A Nominal Cur rent 167 A 180 A Number of Distribution Panels 2 × 225 A, 42-position Max.
Specifications 56 60kW InfraStruXure PDU—Op eration and Configuration Environmental Operating Environment Protected from water and conduct ive contaminates Humidity Operating 0–95%, non-condensing.
60kW InfraStruXure PDU—Oper ation and Conf igur ation 57 Pr oduct Information InfraStruXur e Standar d W arranty APC warrants that all components of the InfraS truXure system will be free from defec.
Product Informati on 58 60kW InfraStruXure PDU—Op eration and Configuration THERE ARE NO W ARRANTIES, EXPRESS OR IMPLIED, BY OPERA TION OF LA W OR OTHER WISE, OF PRODUCTS SOLD, SER VICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH.
60kW InfraStruXure PDU—Oper ation and Conf igur ation 59 Life-Support Policy APC Thr ee-Phase Systems As a general policy , American Po wer Conversion Corporation and its affiliates and subsidiaries.
60 60kW InfraStruXure PDU—Op eration and Configuration How to Obtain Service How to Contact APC Customer support for this or any other APC product is available at no char ge in any of the follow ing ways: • V isit the APC W eb site to access documents in the APC Knowledge Base and to submit any customer support requests.
60kW InfraStruXure PDU—Oper ation and Conf igur ation 61 Appendix A: Changes in This Manual Overview The following list documents the specific changes made to this manual since its last release (990-1662B). General changes Communication configuration instructi ons were added.
.
Index 60kW InfraStruXure PDU—Operation and Configuration 63 A Alarm beeper , 20 Alarm LED , 11 Alarm relay map , 17 Alarm types , 22 Alarm/event log , 20 Alarms screen , 20 – 22 B BOOTP configurat.
64 60kW InfraStruXure PDU—Operation and Configuration Network management interface accessing on a configured PDU , 39 configuration , 33 – 42 recovering from a lost password , 42 Network port, on .
.
.
.
*990-1662C-001* APC W orldwide Customer Support Customer support for this or any other APC produ ct is available at no char ge in any of the following ways: • V isit the APC W eb si te to access documents in the APC Knowledge Base and to submit customer support requests.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté American Power Conversion PDRPPH1000 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du American Power Conversion PDRPPH1000 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation American Power Conversion PDRPPH1000, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le American Power Conversion PDRPPH1000 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le American Power Conversion PDRPPH1000, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du American Power Conversion PDRPPH1000.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le American Power Conversion PDRPPH1000. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei American Power Conversion PDRPPH1000 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.