APC Silcon 480kW 400/415V UPS User Guide Copyright ©2002 APC Japan Information in this document is subject to change without notice and does not represent a commitment on the part of the vendor.
2 User Guide APC Silcon 480kW 400/415V UPS 990-4058GB Thank You Thank you for chosing APC Silcon. Please read this User Guide thoroughly prior to installing the system as it provides important information on safe and efficient installation and use.
990-4058GB User Guide APC Silcon 480kW 400/415V UPS 3 Contents: 1.0 Introduction 4 1.1 Display Unit 4 2.0 Stop/Start UPS and Operating the External Service Bypass Panel 5 2.1 Stop UPS (for stand-by) 5 2.2 Start UPS (from stand-by) 5 2.3 Stop UPS (for complete power down) 6 2.
4 User Guide APC Silcon 480kW 400/415V UPS 990-4058GB Introduction 1.0 Introduction This UPS system is designed to offer reliable and problem-free power supply for several years. The system requires only a minimum of maintenance, but we recommend you follow the maintenance guidelines described in section 6.
Stop/Start UPS and Operating the External Service Bypass 990-4058GB User Guide APC Silcon 480kW 400/415V UPS 5 2.0 Stop/Start UPS and Operating the External Service Bypass Panel Only qualified electricians should start up or shut down APC Silcon UPS systems and instructions in the Installation Guide should be followed.
6 User Guide APC Silcon 480kW 400/415V UPS 990-4058GB Stop/Start UPS and Operating the External Service Bypass 2.3 Stop UPS (for complete power down) 2.
Stop/Start UPS and Operating the External Service Bypass 990-4058GB User Guide APC Silcon 480kW 400/415V UPS 7 The UPS is now isolated. Maintenance/repair, disconnection or removal can now be carried out.
8 User Guide APC Silcon 480kW 400/415V UPS 990-4058GB Stop/Start UPS and Operating the External Service Bypass 2.4 Start UPS (from complete power down) 2.
Stop/Start UPS and Operating the External Service Bypass 990-4058GB User Guide APC Silcon 480kW 400/415V UPS 9 System start-up now completed. NOTICE! One of the following display messages will appear .
10 User Guide APC Silcon 480kW 400/415V UPS 990-4058GB Stop/Start UPS and Operating the External Service Bypass 2.5 Operating the External Service Bypass Switch (single systems) 2.5.1 Bypassing the Single System UPS APC Silcon UPS Mains Load Service Bypass Switch Action 1.
Stop/Start UPS and Operating the External Service Bypass 990-4058GB User Guide APC Silcon 480kW 400/415V UPS 11 2.5.2 Switching the Single System UPS from External Bypass into Normal UPS Operation CAUTION! Do not leave UPS out of service for more than 48 hours.
12 User Guide APC Silcon 480kW 400/415V UPS 990-4058GB Stop/Start UPS and Operating the External Service Bypass NOTICE! If battery has been disconnected, please refer to section 2.4.1 UPS start-up. Action 1. Set the input s witch (Q001) to position 1 2.
Stop/Start UPS and Operating the External Service Bypass 990-4058GB User Guide APC Silcon 480kW 400/415V UPS 13 2.6 Operating the External Service Bypass Switch (parallel systems) 2.
14 User Guide APC Silcon 480kW 400/415V UPS 990-4058GB Stop/Start UPS and Operating the External Service Bypass Action Steps 1-4 apply to all the parallel systems. Note that this will switch all systems into bypass oper ation 1. Press on the ke yboard 2.
Stop/Start UPS and Operating the External Service Bypass 990-4058GB User Guide APC Silcon 480kW 400/415V UPS 15 2.6.2 Switching the Parallel System from External Bypass into Normal UPS Operation NOTICE! If battery has been disconnected, please refer to section 2.
16 User Guide APC Silcon 480kW 400/415V UPS 990-4058GB Stop/Start UPS and Operating the External Service Bypass Action 1. Check that the output s witch (Q004) is set to position 0 2. Check that all output s witches (Q002) are set to position 1 3. Set input s witches (Q001) to position 1 4.
Stop/Start UPS and Operating the External Service Bypass 990-4058GB User Guide APC Silcon 480kW 400/415V UPS 17 2.7 Isolating one UPS in a Parallel Configuration for Service/Maintenance 2.
18 User Guide APC Silcon 480kW 400/415V UPS 990-4058GB Stop/Start UPS and Operating the External Service Bypass NOTICE! With Q002 in position 0, the UPS can be operated and tested as a single system without affecting the other parallel UPS(s) if correct monitoring device has been installed.
Operation 990-4058GB User Guide APC Silcon 480kW 400/415V UPS 19 3.0 Operation The display unit will read parameters, alarms/messages and measured values. LED alarm incorporates audible alarm, indicating unusual operating situations. The keyboard is used to program and control parameters and to display alarm messages and measured values.
20 User Guide APC Silcon 480kW 400/415V UPS 990-4058GB Operation 3.2 Display of Measured Values To read measurements, press one or two keys simultaneously as shown below. (Illustrated values are examples only). 3.3 Using the Remote Display The remote display is an inactive unit that is unable to influence the operation of the APC Silcon UPS.
Operation 990-4058GB User Guide APC Silcon 480kW 400/415V UPS 21 3.4 Economy Mode When the UPS is running in Economy Mode, the load will be supplied directly from mains and output voltages are UPS monitored. In the event of a mains disruption, the UPS will switch to battery mode without affecting the load.
22 User Guide APC Silcon 480kW 400/415V UPS 990-4058GB Parameter Settings 4.0 Parameter Settings Below tables show operating parameters programmable from keyboard.
Parameter Settings 990-4058GB User Guide APC Silcon 480kW 400/415V UPS 23 4.1 Programming Keys 4.2 Switching to Bypass Operation Programming Example Scrolls up through list Scrolls down through list S.
24 User Guide APC Silcon 480kW 400/415V UPS 990-4058GB Parameter Settings To return to normal operation Follow same procedure to program other parameters. Action 6. Press to enter parameter stac k 7. Press or until 8. Press until 9. Press to store 10.
Alarms and Events 990-4058GB User Guide APC Silcon 480kW 400/415V UPS 25 5.0 Alarms and Events Alarms are indicated by the red lamp (above the left hand corner of the keyboard) and a 30 seconds acoustic signal. An alarm is registered in the alarm stack as long as it is present, and if more in the same order as they arise.
26 User Guide APC Silcon 480kW 400/415V UPS 990-4058GB Alarms and Events 5.3 Possible Alarms Alarms Description Action 1. Peak current limiter active Peak current limiter activated and UPS switched to bypass operation. System overload Check for blown fuses in installation 2.
Alarms and Events 990-4058GB User Guide APC Silcon 480kW 400/415V UPS 27 Alarms Description Action 23. Main inverter failure Temperature of main inverter, too high or inverter fuse blown Check fan, check for airflow obstructions, check for overload, check fuse 24.
28 User Guide APC Silcon 480kW 400/415V UPS 990-4058GB Alarms and Events 5.4 Rectifying Alarm Messages Following actions may rectify alarm: • Check local mains supply.
Maintenance & Testing 990-4058GB User Guide APC Silcon 480kW 400/415V UPS 29 6.0 Maintenance & Testing UPS maintenance should be carried out by trained service engineers only. Service and maintenance contract is recommended. 6.1 Fan It is recommended to replace fans every 3 years.
30 User Guide APC Silcon 480kW 400/415V UPS 990-4058GB Maintenance & Testing If the UPS is to be taken out of operation for an extended period, disconnect the battery in order to prevent discharging. For details, refer to Installation Guide. Action 1.
Warranty 990-4058GB User Guide APC Silcon 480kW 400/415V UPS 31 7.0 Warranty 7.1 APC Silcon UPS Limited Factory Warranty APC warrants that the unit, when properly installed and commissioned by APC or .
32 User Guide APC Silcon 480kW 400/415V UPS 990-4058GB How to Contact APC 8.0 How to Contact APC APC Corporate 132 Fairgrounds Road West Kingston, RI 02892 USA Telephone: +1 401 789-5735 Fax: +1 401 7.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté American Power Conversion 480kW c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du American Power Conversion 480kW - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation American Power Conversion 480kW, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le American Power Conversion 480kW va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le American Power Conversion 480kW, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du American Power Conversion 480kW.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le American Power Conversion 480kW. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei American Power Conversion 480kW ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.