GREENHECK P .O. BOX 410 SCHOFIELD, WISCONSIN 54476-0410 PH. 715-359-6171 ® Installation, Operation and Maintenance Instructions for Neutralizer 100% Outdoor Air V entilators W ARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death.
2 T ABLE OF CONTENTS W arrant y ............................................................................................................ Pg. 2 Installation Instructions: N V -45 • Horizontal Discharg e ...........................................
INT AKE DISCHARGE DISCHARGE INT AKE C L C L Equipment Support Footprint C L A A ( fig. 4) Roof mounted arrangement HZ with weatherhood, mounted on three equipment supports.
4 B C L C* Rectangular Curb Footprint C L C L A A/2 A Roof Opening A/2 C* C* *C- Determine equal dimension for these 3 locations Sealant Ductwork Duct Adaptor Supply Ductwork by Others Step 1 Roof Opening Determine the center of the supply duct roof opening.
5 Model TSU Supply Unit Lifting Lugs (4 places) Step 5 Install Supply Unit Use a crane and a spreader bar hooked to the factory lifting lugs (as shown in the diagram) to lift and center the NV unit on the curb and equipment support. Use self-tapping sheet metal screws to fasten unit to the curb and equipment support through holes provided.
6 GREENHECK ® Before beginning this installation: Make sure that there is room to access the unit from all sides. Make sure inlet of unit is located well away from any exhaust fans. Installation Instructions for: SLAB, RAIL, AND CURB MOUNTING NV -90 and NV -120 w/Horizontal Dischar ge Lifting Lugs (4) Spreader Bar NV Unit Intake 1a.
7 Rails located 6-12" in from sides of unit. Rails extend 6" from end of filter section Rails extends 6" from discharge end of unit Lifting Lugs (4) Spreader Bar 2.
8 Straight A B C D Duct Length NV-90 16 1 / 4 24 34 1/ 2 22 3 / 8 81 NV-120 16 1 / 4 25 1 / 2 34 23 1 / 4 96 5. Attach Ductwork to Unit Discha r ge Chart and drawing below show opening size (ID) and location for discharge collar. Also included is the recommended straight duct lengths for optimal performance.
9 Installation Instructions for: CURB MOUNTING* NV -90 and NV -120 *For installations using Greenheck's optional roof curb. 1. Assemble Roof Curb Curbs are shipped knockdown and require assembly by others. Assembly instructions are also included with curb.
10 5. Install Unit. Use a crane and spreader bar to prevent damage to unit. Lifting lugs are provided as shown in illustration. It is highly recommended that all accessory items be lifted separately and attached after the unit is in place. Electrical and pipe connections can be made at this time.
11 Weatherhood fastener locations typical for entire section. T op fasteners are accessed fr om outside, side and bottom fasteners are accessed from inside.
12 Sequence for wiring NV unit: For units without contr ol centers: The motor nameplate is to be used for determining the voltage and amperage required by the unit. For units with control centers: 1. The unit’s nameplate states the voltage and total amperage required.
SYSTEM ST AR TUP For proper unit function and safety, follow everything in this startup procedure in the order presented. This is to be done after the electrical connections are complete. • Voltage meter • Incline manometer or equivalent Special T ools Requir ed • Tachometer • Thermometer • Amperage meter 1.
14 Steam Coils Application Recommendations: Satisfactory operation and service life are best ensured when coils are installed with proper piping, trap, and support arrangement. The following notes and figure 1 ( page 15 ) are recommended for the coil unit installation and operation.
15 Steam Main Return Main Gate V alve Control V alve, Modulating T wo-Position Check V alve-V acuum Breaker Float and Thermostat T rap Strainer Dir ect Expansion Coils Application Recommendations: 1. Piping should be in accordance with accepted industry standards.
16 Coil Maintenance Filters: Filters upstream of the coil should be checked regularly for dirtiness and clogging. If the filters are dirty, they should be cleaned or replaced. It is important that the coils stay clean to maintain maximum heat transfer capability.
17 TROUBLE SHOOTING Blower Unit Symptom Possible Cause Corrective Action Blower fails Blown fuse or open circuit breaker Replace fuse or reset circuit breaker and to operate check amps Broken fan belt.
18 General Dimensions and W eights PLAN VIEW Motor Control Center Optional Filter/Heating Section Optional Heating Coil Cooling Coil 110 1 / 2 ELEV A TION VIEW 88 Optional Curb or Support Blower/Motor.
19 Maintenance Greenheck recommends these procedures to insure trouble free operation of this unit. Most unit failures can be attributed to poor setup or poor maintenance. A record of maintenance performed on this unit should be kept. This information will provide essential information if problems are encountered.
20 Job Information Job Name: ________________________________________ Address: _________________________________________ City: ________________ State: ________ Zip: __________ Phone: _________________.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Greenheck Outdoor Air Ventilator c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Greenheck Outdoor Air Ventilator - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Greenheck Outdoor Air Ventilator, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Greenheck Outdoor Air Ventilator va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Greenheck Outdoor Air Ventilator, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Greenheck Outdoor Air Ventilator.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Greenheck Outdoor Air Ventilator. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Greenheck Outdoor Air Ventilator ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.