Manuel d'utilisation / d'entretien du produit GPC 13 SEER R-410A du fabricant Goodmans
Aller à la page of 47
GPC 13 SEER R-410A Package Air Conditioners with R-410A Copyright © 2008 - 2010 Goodman Manufacturing Company, L.P. RT6322006r6 September 2010 This manual is to be used by qualified, professionally trained HV AC technicians only .
PRODUCT IDENTIFICA TION 2 The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information. WARNING WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit.
PRODUCT IDENTIFICA TION 3 The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information.
4 PRODUCT DESIGN GPC Package Cooling Units are designed for outdoor instal- lations only in either residential or light commercial applica- tions. The connecting ductwork (Supply and Return) can be con- nected for either horizontal or vertical airflow.
PRODUCT DESIGN 5 In installations where the unit is installed above ground level and not serviceable from the ground (Example: Roof Top in- stallations), the installer must provide service platform fo.
6 PRODUCT DIMENSIONS GPC13[24-60]H41** B A 66” Ch ass i s M o d el A B G P C 132 4 33 3 0½ G P C 133 0 33 3 0½ G P C 133 6 33 3 5½ G P C 134 2 33 3 5½ G P C 134 9 33 3 5½ La rg e GPC 134 8 33 3.
ACCESSORIES 7 GPC13[24-60]H41** P a rt Nu m b e r De s cr i p t i on O T 18- 60 A O ut door T her mosta t Ki t w /Loc kout S t at O T /EHR18-60 Em e r genc y Heat Rel ay Ki t HKR El ectric Heat Ki t P.
8 PRODUCT DESIGN ELECTRICAL DA T A (*Blower Only , Heat Mode) All wires and overcurrent protection devices are sized for use with electric heaters only and without refrigeration. If heaters are not installed with above wire size, overheating and fire could occur.
BLOWER PERFORMANCE DA T A 9 Dry Coil Data NOTES: 1. Data shown is Dry Coil. Wet Coil Pressure Drop is approximate. 2. 0.1" H 2 O, for 2 row indoor coil; 0.2” H 2 O, for 3 row indoor coil; and 0.3” H 2 O, for 4 row indoor coil. 3. Data shown does not include filter pressure drop, approx.
10 BLOWER PERFORMANCE DA T A 30 40 50 60 70 80 90 110 1 2 0 100 13 0 140 15 0 100 90 80 70 60 50 40 30 20 10 OUT P UT B TU/ H R x 10 0 0 BT U OUTPUT vs TEMPER AT URE RISE CHART TEMPERAT URE RISE 600 C FM 700 900 1000 1100 1200 140 0 160 0 1800 2000 220 0 240 0 C F M FORMULA S BTU OUTPUT = CFM x 1.
P ACKAGE COOLING SPECIFICA TIONS 11 GPC13[24-30]H41AA IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes.
P ACKAGE COOLING SPECIFICA TIONS 12 IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes.
P ACKAGE COOLING SPECIFICA TIONS 13 GPC13[48-60]H41BA IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes.
14 COOLING PERFORMANCE DA T A GPC1324H41AA MOD E L: GP C1 324 H4 1A* EX PAN DE D P ER F O R MANC E D ATA C OOLI NG OP ER AT I ON De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i q u i d a cce ss f i tti n g co n n ect i o n A H R I 95 t e st co n d i t i o n s .
15 COOLING PERFORMANCE DA T A GPC1324H41AA MOD EL : GP C1 324 H4 1A* EX PAN DE D P ER F O R MANC E D ATA C OOL I NG OP ER ATI ON De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i qu i d a cce ss fi tti ng co n n ect i o n A H R I 95 t e st co n d i ti o n s .
16 COOLING PERFORMANCE DA T A GPC1330H41AA MOD E L : G P C 1330H 4 1A* EX PAN DE D P ER F O R M AN C E D ATA C OOL ING OPER AT ION D es ign S ub c oo l ing , 1 2 ± 3 ° F @ t he li qu id ac c e s s f it t ing c o nn e c tio n A H R I 9 5 t es t c o nd itio ns.
17 COOLING PERFORMANCE DA T A GPC1330H41AA MOD E L : G P C 1330H 4 1A* EX PAN DE D P ER F O R M ANC E D ATA C OOL ING OPER AT ION D es ign S u bc oo l in g, 1 2 ± 3 ° F @ th e liqu id ac c e s s f it t ing c o nn e c tio n A H R I 9 5 t es t c on dit io n s.
18 COOLING PERFORMANCE DA T A GPC1336H41AA MOD E L : G P C 1336H41A * EX PAN DE D P ER F O R MANC E D ATA C OOLI NG OP ER AT I ON De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i q u i d a cce ss f i tti n g co n n ect i o n A HR I 95 t e st co n d i t i o n s .
19 COOLING PERFORMANCE DA T A GPC1336H41AA MOD E L : G P C 1336H41A * EX PAN DE D P ER F O R MANC E D AT A C OOLI NG OP ER AT I ON De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i qu i d a cce ss fi tti ng co n n ect i o n A H R I 95 t e st co n d i ti o n s .
20 COOLING PERFORMANCE DA T A GPC1342H41AA MOD E L : G P C 1342H41A * EX PAN DE D P ER F O R M AN C E D ATA C OOL I NG OP ER ATI ON De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i q u i d a cce ss f i tti n g co n n ect i o n A H R I 95 t e st co n d i t i o n s .
21 COOLING PERFORMANCE DA T A GPC1342H41AA MOD E L : G P C 1342H41A * EX PAN DE D P ER F O R MANC E D AT A C OOLI NG OP ER AT I ON De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i qu i d a cce ss fi tti ng co n n ect i o n A H R I 95 t e st co n d i ti o n s .
22 COOLING PERFORMANCE DA T A GPC1348H41BA MOD E L: GP C 1348H41** EX PAN DE D P ER F O R MANC E D ATA C OOLI NG OP ER AT I ON De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i q u i d a cce ss f i tti n g co n n ect i o n A H R I 95 t e st co n d i t i o n s .
23 COOLING PERFORMANCE DA T A GPC1348H41BA MOD E L: GP C 1348H41** EX PAN DE D P ER FO R MANC E D ATA C OOL ING OP ER AT ION De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i qu i d a cce ss fi tti ng co n n ect i o n A H R I 95 t e st co n d i ti o n s .
24 COOLING PERFORMANCE DA T A GPC1360H41BA MOD E L: GP C 1360H41** EX PAN DE D P ER F O R MANC E D ATA C OOLI NG OP ER AT I ON De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i q u i d a cce ss f i tti n g co n n ect i o n A H R I 95 t e st co n d i t i o n s .
25 COOLING PERFORMANCE DA T A GPC1360H41BA MOD E L: GP C 1360H41** EX PAN DE D P ER FO R MANC E D ATA C OOL ING OP ER AT ION De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i qu i d a cce ss fi tti ng co n n ect i o n A H R I 95 t e st co n d i ti o n s .
26 COOLING PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoo r air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1.
WIRING DIAGRAMS 27 WARN I NG HIGH V OLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT . MULTI PLE PO WER S OUR CES MA Y BE PRESENT . F AILURE TO DO SO MAY CAUSE PROPERTY DAM AGE, PERSONAL INJURY OR DEATH. Wiring is subject to change.
28 WIRING DIAGRAMS Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. WARN I NG HIGH V OLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT . MULTI PLE PO WER S OUR CES MA Y BE PRESENT .
29 GPC1324H41AB GPC1330H41AB GPC1336H41AB GPC 13 SEER R-410A 5 mm Package Air Conditioners GPC Package Cooling Units are designed for outdoor instal- lations only in either residential or light commercial applica- tions. The connecting ductwork (Supply and Return) can be con- nected for either horizontal or vertical airflow.
30 PRODUCT DESIGN Location and Clearances NOTE: To ensure proper condensate drainage, unit must be installed in a level position. 36" 36" 10" UNIT WALL 36" Outside Slab Installation - Horizontal (H) Minimum clearances are required to avoid air recirculation and keep the unit operating at peak efficiency.
P ACKAGE COOLING SPECIFICA TIONS 31 MODELS WITH 5MM COILS GPC13[24-36]H41AB IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes.
P ACKAGE COOLING SPECIFICA TIONS 32 MODELS WITH 5MM COILS GPC1342H41AB GPC1349H41AA GPC1360H41BB IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes.
33 COOLING PERFORMANCE DA T A 5MM COILS GPC1324H41AB MOD E L : GPC 1324H 41A * EX PAN DE D P ER FO R M ANC E D AT A C OOL ING OP ER AT IO N Ou t doo r A m bi en t Te mpera ture 65 75 8 5 95 10 5 115 E.
34 COOLING PERFORMANCE DA T A 5MM COILS GPC1324H41AB MOD E L : GP C 1324H41 A * EX PAN DE D P ER F O R MANC E D ATA CO O LI N G O PE RA TI O N O ut d o or A m b i en t T em per atu r e 65 75 8 5 95 10.
35 COOLING PERFORMANCE DA T A 5MM COILS GPC1330H41AB MOD EL: GPC 1330H41A * EX PAN DE D P E R F O R M ANC E D ATA C OOL ING OP ER AT I ON Ou t doo r A m bi e nt Te mpera ture 65 75 8 5 9 5 10 5 115 E .
36 COOLING PERFORMANCE DA T A 5MM COILS GPC1330H41AB MOD EL: GPC 1330H41A * EX PAN DE D P E R F O R M ANC E D AT A C OOL I NG OP E R AT ION Ou t doo r A m bi e nt Te mpera ture 65 75 8 5 9 5 10 5 115 .
37 COOLING PERFORMANCE DA T A 5MM COILS GPC1336H41AB MOD E L: GPC 1336H 41A * EX PA N DE D P ER F O R M AN C E D AT A C OOL ING OP ER AT I ON Ou t doo r A mbi e nt Te m pera ture 65 75 8 5 95 10 5 115.
38 COOLING PERFORMANCE DA T A 5MM COILS GPC1336H41AB MOD E L: GP C 1336H41A * EX PA N DE D P ER F O R M AN C E D ATA C OOLI NG OP ER ATI ON O ut d o o r A m b i ent T em p er atu r e 65 75 8 5 95 10 5.
39 COOLING PERFORMANCE DA T A 5MM COILS GPC1342H41AB MOD E L: GP C 1342H41A * EX PA N DE D P ER FO R MANC E D ATA C OOL ING OP ER AT ION O ut d o o r A m b i ent T em p er atu r e 65 75 8 5 95 10 5 11.
40 COOLING PERFORMANCE DA T A 5MM COILS GPC1342H41AB MOD EL: GP C 1342H41A * EX PAN DE D P ER F O R MAN C E D ATA C O OL ING OP ER AT I ON Ou t doo r A mbi e nt Tempe r a ture 65 75 8 5 95 10 5 115 E .
41 COOLING PERFORMANCE DA T A 5MM COILS GPC1349H41AA MOD EL: GP C 1349H41A * E XP A ND E D PE RF O RM A N CE DA T A C OO LIN G OP E R ATION O ut d o o r A m b i en t T em p er at u r e 65 75 8 5 95 10.
42 COOLING PERFORMANCE DA T A 5MM COILS GPC1349H41AA MOD E L: GP C 1349H41A * EX PA N DE D P ER F O R M AN C E D ATA C OOLI NG OP ER ATI ON O ut d o o r A m b i ent T em p er atu r e 65 75 8 5 95 10 5.
43 COOLING PERFORMANCE DA T A GPC1360H41BB 5MM COILS MOD E L: GP C 1360H41B* EX PAN DE D P ER F O R M AN C E D ATA C OOLI NG OP ER AT I ON O ut d o o r A m b i ent T em p er atu r e 65 75 8 5 95 10 5 .
44 COOLING PERFORMANCE DA T A GPC1360H41BB 5MM COILS MOD E L: GP C 1360H41B* EX PAN DE D P ER F O R M AN C E D ATA C OOLI NG OP ER ATI ON O ut d o o r A m b i ent T em p er atu r e 65 75 8 5 95 10 5 1.
45 COOLING PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoo r air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1.
46 WIRING DIAGRAMS Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. WARN I NG HIGH V OLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT . MULTI PLE PO WER S OUR CES MA Y BE PRESENT .
WIRING DIAGRAMS 47 WARN I NG HIGH V OLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT . MULTI PLE PO WER S OUR CES MA Y BE PRESENT . F AILURE TO DO SO MAY CAUSE PROPERTY DAM AGE, PERSONAL INJURY OR DEATH. Wiring is subject to change.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Goodmans GPC 13 SEER R-410A c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Goodmans GPC 13 SEER R-410A - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Goodmans GPC 13 SEER R-410A, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Goodmans GPC 13 SEER R-410A va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Goodmans GPC 13 SEER R-410A, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Goodmans GPC 13 SEER R-410A.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Goodmans GPC 13 SEER R-410A. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Goodmans GPC 13 SEER R-410A ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.