SSZ 14 SEER S plit System Heat Pumps • Refer to Service Manual RS6200005 for installation, op- eration, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. • Refer to the appropriate Parts Catalog for part number information.
PRODUCT IDENTIFICA TION 2 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. WARNING WARNING WARNING WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit.
PRODUCT IDENTIFICA TION 3 WARNING WARNING WARNING WARNING To prevent the risk of property damage, personal injury, or death, do not store combustible materials or use gasoline or other flammable liquids or vapors in the vicinity of this appliance. Do not connect or use any device that is not design certified by Goodman for use with this unit.
PRODUCT DESIGN 4 SSZ14 models are available in 1 1/2 through 5 ton sizes and use R-410A refrigerant. They are designed for 208/230 volt single phase applications. The condenser air is pulled through the condenser coil by a direct drive propeller fan. This condenser air is then dis- charged out of the top of the cabinet.
HEA T PUMP SPECIFICA TIONS 5 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
6 COOLING PERFORMANCE DA T A SSZ140181A* EXPA NDED PERFORMAN CE DA TA COOLING OPE RA TION MODEL: SSZ140181A * / CA *F3131*6 A* +TXV / M BR800**-1 D esign Subcooling 9 ± 3 °F @ the liqui d service va.
7 COOLING PERFORMANCE DA T A SSZ140181A* EXPA NDED PERFORMAN CE DATA COOLING O PERATION MODEL: SSZ140 181A * / CA *F3131*6A * +TXV / M BR800**-1 D esign Subc ooling 9 ±3 °F @ t he liquid service v a.
8 COOLING PERFORMANCE DA T A SSZ140241A* EXPA ND ED PERFORM A NCE DATA COOLING OP ERA TION MODEL: SS Z140241A * / CA *F3636*6 A *+TXV / MBR80 0**-1 Design Subco oling 9 ±3 °F @ the liquid service va.
9 COOLING PERFORMANCE DA T A SSZ140241A* EXPA NDED PERFO RMA NCE DA T A COOLING OPERA TION MO DEL: SSZ140241A* / CA *F3636* 6A *+TXV / MB R800**-1 Design Subcoo ling 9 ±3 °F @ the liqui d service va.
10 COOLING PERFORMANCE DA T A SSZ140301A* EXPA NDED PERFORMA NCE DA TA COOLING OPERA TION M ODEL: SSZ140301A* / CA *F3642*6A*+TXV / MBR1600**-1 Design Subcooling 9 ±3 °F @ the liquid service valv e,.
11 COOLING PERFORMANCE DA T A SSZ140301A* EXPA NDED PERFORMA NC E DA TA COOLING OPERA TION M ODEL: SSZ 140301A * / CA*F3642*6A *+T XV / MB R1600**-1 Design Subcooling 9 ±3 °F @ th e liquid serv ice .
12 COOLING PERFORMANCE DA T A SSZ140361A* EXPA NDED PER FOR M A NCE DA T A MODEL: SSZ140 361A * / CA*F4860*6A*+TXV / M BR1600 **- 1 Desig n Subco oli ng 9 ±3 ° F @ th e li qu id serv i ce va lv e, A.
13 COOLING PERFORMANCE DA T A SSZ140361A* EXPA ND ED PERFO RM A NCE D A TA COOLING OP ERATION MODEL: SSZ140361A* / CA *F4860*6A*+TXV / M BR1600 **- 1 Desig n Subco oli ng 9 ±3 ° F @ th e li qu id se.
14 COOLING PERFORMANCE DA T A SSZ140421A* EXPA NDED PERFORMA NCE DA T A MODEL: S SZ1404 21A * / CA *F4860*6 A*+TXV / M BR2000 **-1 Design Sub cooling 9 ±3 °F @ the li quid service valve, A RI 95 tes.
15 COOLING PERFORMANCE DA T A SSZ140421A* EXPANDED PERFORMANCE DA T A COOLING OP ERA TION MODEL: SSZ14 0421A * / CA *F4860*6A *+TXV / MBR2000 **-1 Design Sub cooli ng 9 ±3 °F @ the liquid s ervice v.
16 COOLING PERFORMANCE DA T A SSZ140481A* EXPA NDED PERFORMANCE DA TA COOLING O PERA TION MODEL: SS Z140 481A * / CA *F48 60*6A *+TXV / MBR20 00**-1 Design Sub cooling 9 ±3 °F @ the liq uid service .
17 COOLING PERFORMANCE DA T A SSZ140481A* EXPA NDED PERFORMA NCE DATA COOLING O PERA TI ON MODEL: S S Z140481 A* / C A*F4 860*6A *+TXV / MBR2000**-1 Design S ubcool ing 9 ±3 °F @ the liquid s ervice.
18 COOLING PERFORMANCE DA T A SSZ140601A* EXPA NDED PERFORMA N CE DA TA COOLING O PERATION MODEL: SSZ140 601A * / CA *F4860*6A *+TXV / MBE200 0**-1 Design S ubcooling 9 ±3 ° F @ the liquid s ervice .
19 COOLING PERFORMANCE DA T A SSZ140601A* EXPA NDED PERFORMA NCE DAT A COOLING O PE RA TI ON MODEL: SSZ140 601A * / CA *F4860*6 A *+TXV / MBE2000** -1 Design Subcooling 9 ±3 ° F @ the liquid service.
20 PERFORMANCE DA T A Out door Temp. ° F . Tota l Btuh Sen sibl e Btu h La te nt Btuh Total Wat ts 75° 36,330 24,713 11,617 2,662 80° 35,898 24,729 11,169 2,742 85° 35,465 24,738 10,727 2,822 90°.
21 EXPA NDED PERFORM ANCE DA TA M ODEL: SSZ140361A * / CA*F4860C6A *+T XV / M BR1600**-1 HEATING O PERATION Outdoo r Ambient Tem p era ture 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 MBh 43.5 41.2 38.8 36.2 34.6 33.5 31. 1 28.7 28.8 26.6 24.
22 EXPANDED PERFORM ANCE DA TA MO DEL: SSZ140481A* / CA*F4860*6A *+TX V / MBR 2000**-1 HEA T ING OP ERATION Outdoor A mbient Te mperat ure 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -1 0 MBh 57.8 5 4.7 5 1.5 48. 2 46. 0 44.6 41 .4 38.2 36 .6 33 .
23 HEA TING SPECIFICA TIONS capacit y btuh c.o.p. 4.8 9.6 1 4.4 19.2 65 22.63 4.23 39.01 55.39 71.77 88.16 60 21.42 4.09 37.80 54.18 70.57 86.95 55 20.16 3.93 36.54 52.92 69.31 85.69 50 18.85 3.75 35.23 51.61 67.99 84.38 45 17.44 3.54 33.82 50.21 66.59 82.
24 HEA TING SPECIFICA TIONS capaci t y btuh c. o.p . 4. 8 9. 6 14.4 19 . 2 65 51.5 4 4. 44 67. 92 84. 30 1 00. 68 117. 07 60 48.7 9 4. 28 65. 17 81. 55 9 7.9 4 114 .32 55 45.9 2 4. 11 62. 30 78. 68 9 5.0 7 111 .45 50 42.9 3 3. 92 59. 31 75. 69 9 2.0 7 108 .
25 PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoo r air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1.
WIRING DIAGRAMS 26 TO AVOID POSSI BLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DI SCONNECT THE POWER BEFORE SERVI CING. WARNING ! Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Goodman Mfg SSZ140181A c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Goodman Mfg SSZ140181A - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Goodman Mfg SSZ140181A, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Goodman Mfg SSZ140181A va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Goodman Mfg SSZ140181A, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Goodman Mfg SSZ140181A.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Goodman Mfg SSZ140181A. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Goodman Mfg SSZ140181A ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.