www .rosemount-tg.com Reference Manual 300530EN, Rev BA September 20 12 Rosemount 2410 Ta n k H u b.
.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 www .rosemount-tg.com Rosemount 2410 T ank Hub Cover Photo: 2410_coverfoto.tif NOTICE Read this manual before working with t he produ ct.
.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 www .rosemount-tg.com T able of Content s SECTION 1 Introduction 1.1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 1.2 Symbols . . . . . . . .
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 TOC -2 Table of Contents 4.6.1 Installation Wizard . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5 4.6.2 Advanced Configuration . . . . . . . . . . . . . . . . . . . . . . . 4-5 4.
Reference Manual 300530EN, Rev BA September 20 12 TOC -3 Rosemount 2410 Table of Contents C.5 Relay Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-6 C.6 Hybrid Density Calculation . . . . . . . . . . . . . . . .
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 TOC -4 Table of Contents.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 www .rosemount-tg.com Section 1 Introduction 1.1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age 1- 1 1.2 Symbols . . . . . . . . . . . . . . . . . . . . . .
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 1-2 Section 1. Introducti on 1.2 SYMBOLS The CE marking symbolises the conformity of the prod uct with the applicable Eu ropean Community Directives.
Reference Manual 300530EN, Rev BA September 20 12 1-3 Rosemount 2410 Section 1. Introduction 1.3 MANUAL OVERVIEW This manual provides information on installation, configuration and maintenance of the Rosemount 2410 T a nk Hub.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 1-4 Section 1. Introducti on 1.4 T ECHNICAL DOCUMENT ATION The Raptor T ank Gauging System includes the following do cumentation: • Ra.
Reference Manual 300530EN, Rev BA September 20 12 1-5 Rosemount 2410 Section 1. Introduction 1.5 SERVICE SUPPORT For service support cont act the nearest Emerson Process Management/Rosemount T ank Gauging representative. Co ntact information can be found on the web site www .
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 1-6 Section 1. Introducti on.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 www .rosemount-tg.com Section 2 Overview 2.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age 2-1 2.2 Components . . . . . . . . . . . . . . . . . . . . .
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 2-2 Section 2. Overview The Rosem ount 2410 has two ex ternal buse s for commu nication with host systems. The Primary Bus is typically used with the TRL2 Modbus o r RS-485 Modbus protocol for communica tion with a 2160 Fi eld Communication Unit.
Reference Manual 300530EN, Rev BA September 20 12 2-3 Rosemount 2410 Section 2. Overview 2.1.1 Communication The Raptor system support s various communication interfaces between a Rosemount 2410 and a T ank Master PC or other host computers as illustrated in Figure 2-2 to Figure 2 -4.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 2-4 Section 2. Overview A THUM Adapter , connected to t he Intrinsically Safe Secondary (1) bus, allows wireless communication between a 2410 T ank Hub and a Smart Wireless Gateway . Figure 2-4.
Reference Manual 300530EN, Rev BA September 20 12 2-5 Rosemount 2410 Section 2. Overview 2.2 COMPONENT S Figure 2-5. Ros emount 2410 component s 1. Intrinsically safe terminal compa rtment 2. Non-intrinsically safe terminal compartment 3. Integral dis play (optional) 4.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 2-6 Section 2. Overview 2.3 SYSTEM OVERVIEW Raptor is a state-of-th e art inventory and custody transfer radar tank leve l gauging sy stem.
Reference Manual 300530EN, Rev BA September 20 12 2-7 Rosemount 2410 Section 2. Overview Figure 2-6. Raptor system architecture 2230 Display 2240S T emperatu re T ransmitter 5900S Radar Level Gauge 24.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 2-8 Section 2. Overview Figure 2- 7. Raptor sy stem architecture for wir eless systems 2230 Display 2240S T emperature T ransmitter 5900.
Reference Manual 300530EN, Rev BA September 20 12 2-9 Rosemount 2410 Section 2. Overview T ankMast er HMI Software T ankMaste r is a powerful Windows-based Human Machine Interface (HMI) fo r complete tank inve ntory management.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 2-10 Section 2. Overview The Rosemount 5900S sends micr owaves towards the su rfac e of the product in the tank.
Reference Manual 300530EN, Rev BA September 20 12 2-1 1 Rosemount 2410 Section 2. Overview Rosemount Smart Wireless Gateway and Rosemount Smart Wire less THUM Adapter A THUM Adapter allows wireless communication between a 2410 T ank Hub and a Smart Wireless Gateway .
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 2-12 Section 2. Overview 2.4 INST ALLATION PROCEDURE Follow these steps for a prope r installation: Review Mounting Considerations . See “Installation Considerations” on page 3-2. Mount the 2410.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 www .rosemount-tg.com Section 3 Inst allation 3.1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age 3-1 3.2 Inst allation Consideration s . . . . . . . . . . .
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 3-2 Section 3. Installation 3.2 INST ALLATION CONSIDERATIONS The Rosem ount 2410 T ank Hub ma y be installed on v arious location s at the plant.
Reference Manual 300530EN, Rev BA September 20 12 3-3 Rosemount 2410 Section 3. Installation 3.3 MECHANICAL INST ALLATION The Rosemount 2410 is designed for moun ting on a pipe stand or on a wall. NOTE! Ensure that the 2410 is installe d to minimize vibration and mechanical shock.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 3-4 Section 3. Installation 3.3.2 W all Mounting 1. Mount the bracket on the wall by using four M8 screws and flat washers. Note ! Countersunk screws are not suitable. 2. Attach the 2410 to the bracket and tighten the screw .
Reference Manual 300530EN, Rev BA September 20 12 3-5 Rosemount 2410 Section 3. Installation 3.4 ELECTRICAL INST ALLATION 3.4.1 Cable Entries The Rosemount 2410 electronics hou sing has four ½ - 14 NPT and two ¾ - 14 NPT entries. The connections must be made in accordance with local or plant electrical code s.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 3-6 Section 3. Installation 3.4.4 Grounding The housing should always be grounde d in accordance with national and local electrical codes. Failu re to do so may impair the protection provide d by the equipment.
Reference Manual 300530EN, Rev BA September 20 12 3-7 Rosemount 2410 Section 3. Installation 3.4.6 Power Budget The Rosemount 2410 T ank Hub delivers 250 mA to the T ankbus. In Smart Wireless systems a 2410 T ank Hub eq uipped with active ana log inputs/output s may deliver 200 mA.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 3-8 Section 3. Installation 3.4.7 T ankbus The Raptor system is easy to inst all and wire.
Reference Manual 300530EN, Rev BA September 20 12 3-9 Rosemount 2410 Section 3. Installation Since the field devices on the T ankbus must have at least a 9 V input voltage at their terminals, you will have to t ake into account the vo ltage drop in the fieldbus cables.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 3-10 Section 3. Installation Example 1 The example illustrated in Figure 3-2 in cludes a tank located 300 m away from a Rosemount 2410 T ank Hub acting as power supply .
Reference Manual 300530EN, Rev BA September 20 12 3-1 1 Rosemount 2410 Section 3. Installation Example 2 The second example, illust rated in Figure 3-3, includes two tanks with a Rosemount 2410 T ank Hub acting as power supply to the field devices on both tanks.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 3-12 Section 3. Installation T ankbus Segment Coupler In case “d aisy-chain” co nnection is not suitable, a T ankbus Segm ent Coupler (1) can be used to connect the various devices to th e Raptor T ankbus.
Reference Manual 300530EN, Rev BA September 20 12 3-13 Rosemount 2410 Section 3. Installation Figure 3-5. Segment coupler In case there ar e different device type s connected to the segment couple r , set the current limitation switch (3 ) to the closest value abo ve the largest curr ent consumptio n of the connected de vices.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 3-14 Section 3. Installation Figure 3-6. Example of Raptor system with field devices connected to the T ankbus via segment couplers T an.
Reference Manual 300530EN, Rev BA September 20 12 3-15 Rosemount 2410 Section 3. Installation 3.4.8 T ypical Inst allations The example below (Figure 3-7) illustrates a Raptor system with daisy-chained fi eld devices on a single tank. T erminators are inst alled at both ends of the fieldbus se gment as required in a F OUNDATION fieldbus syst em.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 3-16 Section 3. Installation Figure 3-8 illustrates an example with a 2- in-1 version of th e 5900S in a SIL safety insta llation. A 4-wire cable is used to connect the Primary and Secondary T ankbuses through the same cab le entry .
Reference Manual 300530EN, Rev BA September 20 12 3-17 Rosemount 2410 Section 3. Installation Figure 3-9 illustrates an example with four tanks connected to a Rosemount 2410 T ank Hub (requires 2410 with multiple tanks option). T he field devices are connected to a segment couple r at the end of the T ankbus.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 3-18 Section 3. Installation Figure 3-10 illustrates an example with a number of tanks daisy-chained to a Rosemount 2410 T ank Hub (requires multiple tanks option).
Reference Manual 300530EN, Rev BA September 20 12 3-19 Rosemount 2410 Section 3. Installation Figure 3-1 1 illustrates an example with three t anks connected to a Rosemount 2410 T ank Hub (require s multiple tanks option) . For each tank th e field devices are connected to the T ankbus via a segment coupler .
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 3-20 Section 3. Installation In case the last device on the T ankbus has no internal termin ator , an external terminator (1) according to FISCO model a nd Entity model can be used instead.
Reference Manual 300530EN, Rev BA September 20 12 3-21 Rosemount 2410 Section 3. Installation 3.4.9 Cabling for the TRL2/RS485 Bus In a Raptor system a Rosemount 2410 T ank Hub communicates with a 216 0 Field Communication Unit using th e TRL2/RS485 Modbus protocol, see Section 2: Overv iew .
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 3-22 Section 3. Installation 3.4.10 Non-IS Connection The non-IS explosion-proof/flam eproof compartment has a terminal block fo r connecting power sup ply , communication buse s to host systems, relay outputs, and HART 4-20 m A analog in put and ou tput.
Reference Manual 300530EN, Rev BA September 20 12 3-23 Rosemount 2410 Section 3. Installation Conductor Recommendat ions Ensure that you use cables suitable fo r the termina l block of the 2410. The terminal block is designed for cables that meet the sp ec ifications as illustrated below .
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 3-24 Section 3. Installation Use a screw driver to insert the conduct or into the terminal block as illustrated in Figure 3 -16.
Reference Manual 300530EN, Rev BA September 20 12 3-25 Rosemount 2410 Section 3. Installation 3.4.1 1 Non-IS T erminal Block Figure 3-17. T erminal block in the explosion- proof/flame proof compartment T able 3-8.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 3-26 Section 3. Installation Relay Output s There are two optional relay ou tputs. Y ou can ch oose Normally Open (NO) or Normally Closed (NC) by setting a switch as described in “Relay Output Configurat ion” on page 6-15.
Reference Manual 300530EN, Rev BA September 20 12 3-27 Rosemount 2410 Section 3. Installation Non-IS T erminal Block for SIL Safety Systems For Safety Integrity Level (SIL) systems the Rosemount 2410 ha s a terminal block on the Non- IS side with connect ion to a SIL Alarm Relay outp ut.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 3-28 Section 3. Installation 3.4.12 IS Connection The IS comp artment has a terminal block for connecting th e intrinsically safe T ankbus for communication with field devic es on the tank.
Reference Manual 300530EN, Rev BA September 20 12 3-29 Rosemount 2410 Section 3. Installation 3.4.13 Intrinsically Safe Te r m i n a l B l o c k The Intrinsically safe side of the Ro semount 2410 T ank Hub connects to the T ank bus which commu nicates with field devi ces on the tank.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 3-30 Section 3. Installation IS T erminal Block for SIL Safety Systems For Safety Integrit y Level ( SIL) system s the Rosem ount 2410 h as a terminal block with a SIL Alarm output for connection to a Rosemount 5900S Radar Level Gauge.
Reference Manual 300530EN, Rev BA September 20 12 3-31 Rosemount 2410 Section 3. Installation 3.4.14 Wiring Diagrams Figure 3-22. Wiring diagram on the intrinsically safe (IS/Exi) side ROSEMOUNT 2410 .
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 3-32 Section 3. Installation Figure 3- 23. Wiring diagram on the non-intrinsically safe (XP/Exd/Exe) side Figure 3- 24.
Reference Manual 300530EN, Rev BA September 20 12 3-33 Rosemount 2410 Section 3. Installation Rosemount 5900S Radar Level G auge Rosemount 2410 Ta n k H u b SIL Alarm Relay SIL Alarm Output Ta n k b u.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 3-34 Section 3. Installation.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 Series www .rosemount-tg.com Section 4 Configuration 4.1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age 4-1 4.2 Introduction . . . . . . . . . . . . . . . .
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 Series 4-2 Section 4. Configuration 4.2 INTRODUCTION A Raptor system includes a wide range of devices for t ank monitoring. It is a flexible and scalable system wh ich can be adapted to various applications and small or large t ank farms.
Reference Manual 300530EN, Rev BA September 20 12 4-3 Rosemount 2410 Series Section 4. Configuration 4.4 BASIC CONFIGURATION OF A ROSEMOUNT 2410 This is a general descript ion of how to con figure a Rosemoun t 2410 T an k Hub. The Raptor Syst em Configur ation Manual (Document no .
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 Series 4-4 Section 4. Configuration 4.5 ADVANCED CONFIGURATION The installation wizard in T ankMaster Winsetup comprises a basic configuration of the Rosemount 241 0.
Reference Manual 300530EN, Rev BA September 20 12 4-5 Rosemount 2410 Series Section 4. Configuration 4.6.1 Inst allation Wiza rd The T ankMaster W inSetup wizard is t he recommended tool for installing the Rosemount 2410. It suppor ts basic configuration of the 2410 .
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 Series 4-6 Section 4. Configuration 4.6.3 FCU 2160 Configuration In case the system includes a 2160 Fie l d Communication Unit (FCU), it has to be installed prior to installing the Ro semount 2410 T ank Hub.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 www .rosemount-tg.com Section 5 Operation 5.1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age 5-1 5.2 Integral Display . . . . . . . . . . . . . . . . . . . .
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 5-2 Section 5. Operation 5.2 INTEGRAL DISPLAY The Rosemount 2410 T ank Hub can be equi pped with an optional integral display for present ation of measurement dat a and diagnostics.
Reference Manual 300530EN, Rev BA September 20 12 5-3 Rosemount 2410 Section 5. Operation T able 5-1. Measurement variables and pres entation on the Rosemount 24 10 display Va r i a b l e Present atio.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 5-4 Section 5. Operation 5.3 ST ART-UP INFORMATION When the Rosemount 2410 st arts up , all LCD segments light up for approximately 5 seconds. The st art-up information appears on the display when the software initia lization procedure is finished.
Reference Manual 300530EN, Rev BA September 20 12 5-5 Rosemount 2410 Section 5. Operation 5.4 ERROR MESSAGES In addition to pr esenting measurement values, the display can show sof tware and hardwar e error messag es. In case of an erro r , th e upper row shows “ERROR” and the lower r ow toggles between “F AIL” and the er ror code.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 5-6 Section 5. Operation 5.5 LED There ar e three Ligh t Emitting Diod es (LED) o n the Rosemo unt 2410 f ront for status and e rror information. Figure 5-3. The Rosemount 2410 has three LED s The following color codes a re used for the 2410 LEDs: T able 5-4.
Reference Manual 300530EN, Rev BA September 20 12 5-7 Rosemount 2410 Section 5. Operation 5.5.2 Error LED In normal op eration the Error LED (R ed) is turne d off. In case a dev ice error occurs, the LED will flash a sequence th at corresponds to the error code followed by a five second pa use.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 5-8 Section 5. Operation 5.6 SPECIFYING DISPLAY V ARIABLES The Rosemount 2410 can be configured to present measurement dat a on the optional integral displa y . Measurement data such as Level, Level Rate, Free W ater Level and many other tank variab les can be displayed.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 www .rosemount-tg.com Section 6 Service and T roubleshooting 6.1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age 6-1 6.2 Service . . . . . . . . . . . . . . .
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 6-2 Section 6. Service and Troubleshoo ting 6.2 SERVICE This section briefly describes func tion s which may be useful for service and maintenance of a Rosemount 2410 T ank Hub.
Reference Manual 300530EN, Rev BA September 20 12 6-3 Rosemount 2410 Section 6. Service and Troubl eshooting 4. Choose Predefined for a basic selection of registers. Choose the All option if you would like to view a ran ge of registers by your own choice.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 6-4 Section 6. Service and Troubleshoo ting 6.2.3 Device Live List The 2410 Hu b Device Live List let s you view devices connected to the T ankbus. Y ou can, for example, see the Device Id, T ag, and whether the devices are configured or not.
Reference Manual 300530EN, Rev BA September 20 12 6-5 Rosemount 2410 Section 6. Service and Troubl eshooting 6.2.4 Configuration Backup Input and Holding Reg isters of the Rosemount 2410 T ank Hub can be stored on disk, which can be usefu l for back up purposes and trouble shooting.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 6-6 Section 6. Service and Troubleshoo ting 6.2.5 Configuration Recovery T ankMaster WinSetup of fers the opti on to replace th e current Holding Register database with a ba ckup database stored on disk.
Reference Manual 300530EN, Rev BA September 20 12 6-7 Rosemount 2410 Section 6. Service and Troubl eshooting 6.2.6 Diagnostics T ankMaste r WinSetup offers the option to view diagnostic registers for the Rosemount 2410 T ank Hub.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 6-8 Section 6. Service and Troubleshoo ting 6.2.7 Device Sof tware Upgrade The Rosemou nt T ankMaster WinSetup program allows you to upgrade the 2410 T ank Hub and other Raptor devices with new software.
Reference Manual 300530EN, Rev BA September 20 12 6-9 Rosemount 2410 Section 6. Service and Troubl eshooting c. From the A vailable Devices pa ne choose a 2410 T ank Hub to be programmed and click the Move bu tton. d. Repeat for each device to be programmed.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 6-10 Section 6. Service and Troubleshoo ting 6.2.8 Write Protection A Rosemount 24 10 T ank Hub can be write protec ted to avoid uninten tional configuration changes whe n using the T ankMaster programs.
Reference Manual 300530EN, Rev BA September 20 12 6-1 1 Rosemount 2410 Section 6. Service and Troubl eshooting 6.2.9 Write Protection Switch A switch on th e front of th e Rosemoun t 2410 T ank Hub can be used to prevent unauthor ized changes of the holding registe r database.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 6-12 Section 6. Service and Troubleshoo ting 6.2.10 Simulation Mode The Simulation M ode function lets you verify comm unication be tween a Rosemount 24 10 T a nk Hub and a ho st syst em without connecting actual field devices.
Reference Manual 300530EN, Rev BA September 20 12 6-13 Rosemount 2410 Section 6. Service and Troubl eshooting Figure 6-4. Simulation mode active is indicated in the WinSetup wor kspace NOTE Simulation continues for the specifie d period of time. It can also be stopped manually at any time by pressing the S top button in the Simulation window .
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 6-14 Section 6. Service and Troubleshoo ting 6.2.1 1 T esting the Relays The Manual Control of Relay function let s you manually open or close th e Rosemount 2410 T ank Hub built-in relays in order to verify the relay function.
Reference Manual 300530EN, Rev BA September 20 12 6-15 Rosemount 2410 Section 6. Service and Troubl eshooting 6.2.12 Relay Output Configuration T o change the Normallly Open/Normally Closed setti ngs of the K1 and K 2 relays, do the following: 1. Disconnect the power sup ply .
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 6-16 Section 6. Service and Troubleshoo ting 6.2.13 Loading the Default Dat abase The various configuration p arameters of the 2410 T ank Hub is stored in a Holding Registe r database . The Holding Register fac tory setting is stored in the default dat abase .
Reference Manual 300530EN, Rev BA September 20 12 6-17 Rosemount 2410 Section 6. Service and Troubl eshooting 6.2.14 Logging Measurement Dat a The Rosemount 2410 supports logging of diagnostic registers. This function is useful for verifying that the gauge wor ks prop erly .
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 6-18 Section 6. Service and Troubleshoo ting 6 . 3 T ROUBLESHOOTING T able 6-3. T roubleshooting chart Symptom Possible cause Action No contact with the Rosemount 2410 T ank Hub Wiring • Check that wires are properly connected to the terminals.
Reference Manual 300530EN, Rev BA September 20 12 6-19 Rosemount 2410 Section 6. Service and Troubl eshooting No communication with one or more devices on the T ankbus Wiring • Check that the devices appear in the Device Live List (see “Device Live List” on page 6-4).
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 6-20 Section 6. Service and Troubleshoo ting T ankMaster does not present measurement data from one or more devices connected to the T ankbus. The devices communicate on the T ankbus and appear in the Device Live List.
Reference Manual 300530EN, Rev BA September 20 12 6-21 Rosemount 2410 Section 6. Service and Troubl eshooting Incorrect level reading from radar level gauge Configuration error • Check configuration of the level gauge; in T ankMaster Winsetup open Properties for the level gauge associated with the tank.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 6-22 Section 6. Service and Troubleshoo ting 2410 icon in T ankMaster WinSetup is red Simulation mode active • S top simulation mode; open WinSetup Set Simulation Mode window and click the S top button.
Reference Manual 300530EN, Rev BA September 20 12 6-23 Rosemount 2410 Section 6. Service and Troubl eshooting 6.3.1 Device St atus The curr ent device status is shown in Input Register 10 00 .
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 6-24 Section 6. Service and Troubleshoo ting 6.3.2 W arning Messages W arning messages are displayed in the Rosemount T ankmaster program.
Reference Manual 300530EN, Rev BA September 20 12 6-25 Rosemount 2410 Section 6. Service and Troubl eshooting Map conflict tank no. Input register no. 6260 Check that tank measurement variables are ma.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 6-26 Section 6. Service and Troubleshoo ting 6.3.3 Error Messages Error messages may be displayed on the Rosem ount 2410 integral display and in the Rosemount T ankmaster progra m.
Reference Manual 300530EN, Rev BA September 20 12 6-27 Rosemount 2410 Section 6. Service and Troubl eshooting Other Memory Error Input register no. 6108: Bit 0: CheckSum Bit 1: S tack Contact Emerson Process Management/Rosemount T ankGauging service department Sys Error Input register no.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 6-28 Section 6. Service and Troubleshoo ting.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 www .rosemount-tg.com Appendix A Reference Dat a A.1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p age A-1 A.2 Dimensional drawings . . . . . . . . . . . . .
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 A-2 Appendix A. Reference Data Analog input/output electrical characteristics Analog Input Maximum number of input channels: 1 Input Current range: 0 - 23 mA Configurable Min and Max alarm limits.
Reference Manual 300530EN, Rev BA September 20 12 A-3 Rosemount 2410 Appendix A. Reference Data Mechanical Housing m aterial Polyurethane-covered die-cast aluminum Installation Can be installed on a 33.4-60.3 mm (1-2 in.) diameter pipe or wall Dimensi ons See “Dimensional drawin gs” on page A-4.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 A-4 Appendix A. Reference Data A.2 D IMENSIONAL DRAWINGS Figure A-1. Rosemount 241 0 dimensions 254 mm 193 mm 164 mm.
Reference Manual 300530EN, Rev BA September 20 12 A-5 Rosemount 2410 Appendix A. Reference Data A.3 O RDERING INFORMATION Model (Pos 1) Product Description Note 2410 T ank Hub Code (Po s 2) T ankbus: .
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 A-6 Appendix A. Reference Data Code (Pos 8) Integral Display Note 1 LCD 0 None Code (Pos 9) Power Supply Note P Extended input range: 48.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 www .rosemount-tg.com Appendix B Product Certifications B.1 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . p age B-1 B.2 EU Conformity . . . . . . . . . . . . . . .
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 B-2 Appendix B. Product Certifications B.2 E U CONFORMITY The EC declaratio n of confor mity for a ll applicable European directives for this product can be found on the Rosem ount website at www .
Reference Manual 300530EN, Rev BA September 20 12 B-3 Rosemount 2410 Appendix B. Product Certifications B.3 H AZARDOUS LOCATIONS CERTIFICATIONS The Rosemou nt 2410 T ank Hubs that have the followin g labels attached have been certified to comply with the requir ements of the appr oval agencies noted.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 B-4 Appendix B. Product Certifications HART/4-20 mA ENTITY IS I/O Option Active Current Loop XP-AIS CL I, DIV . 1 GP C & D AEx de[ia IIC] IIB U o = 23.1 V , I o = 95.3 mA, P o = 550 mW Group IIC: C o 0.
Reference Manual 300530EN, Rev BA September 20 12 B-5 Rosemount 2410 Appendix B. Product Certifications B.3.2 Factory Mutual Canadian Approvals Certificate of Co mpliance: 3035492C.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 B-6 Appendix B. Product Certifications HART/4-20 mA ENTITY IS I/O Option Active Current Loop XP-AIS CL I, DIV . 1 GP C & D Ex de[ia IIC] IIB U o = 23.1 V , I o = 95.3 mA, P o = 550 mW Group IIC: C o 0.
Reference Manual 300530EN, Rev BA September 20 12 B-7 Rosemount 2410 Appendix B. Product Certifications B.3.3 European A TEX Directive Information The Rosemount 2410 T ank Hubs that hav e the followi .
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 B-8 Appendix B. Product Certifications FISCO Power Supply Ex de[ib] IIB T4 (-50 °C Ta +70 °C) U o =15V , l o =354mA, P o =5.32W Um=250 V HART/4-20 mA ENTITY IS I/O Option Active Current Loop Ex de[ia IIC] IIB T4 (-50 °C<T a<+70 °C) U o = 23.
Reference Manual 300530EN, Rev BA September 20 12 B-9 Rosemount 2410 Appendix B. Product Certifications B.3.4 IECEx Approval Figure B-4. IEC Ex approval labels E7 The following information is provided.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 B-10 Appendix B. Product Certifications FISCO Power Supply Ex de[ib] IIB Gb T4 (-50 °C Ta +70 °C) U o =15V , l o =354mA, P o =5.32W Um=250 V HART/4-20 mA ENTITY IS I/O Option Active Current Loop Ex de[ia IIC Ga] IIB Gb T4 (-50 °C<T a< +70 °C) U o = 23.
Reference Manual 300530EN, Rev BA September 20 12 B-1 1 Rosemount 2410 Appendix B. Product Certifications B.4 A PPROVAL DRAWINGS Follow the installation gui delines presented in Factory Mutual system control drawings in order to maintain cert ified r atings for installed devices.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 B-12 Appendix B. Product Certifications.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 www .rosemount-tg.com Appendix C Advanced Configuration C.1 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . p age C-1 C.2 Advanced Configuration in W inset up . . . .
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 C-2 Appendix C. Advanced Configuration High voltage that may be present on leads could cau se electrical shock: Avoid contact with leads and terminals.
Reference Manual 300530EN, Rev BA September 20 12 C-3 Rosemount 2410 Appendix C. Advanced Configuration C.2 A DVANCED CONFIGURA TION IN WINSETUP There are advanced config uration options for the Rosemount 2410 T ank Hub which are not included in the T ankMaster WinSetup inst allation wizard.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 C-4 Appendix C. Advanced Configuration C.3 P RIMARY BUS The Rosemount 2410 has a Prim ary Bus which is used for communication with a Rosemoun t 2160 Field Comm unicat ion Unit (FCU) or a control room computer .
Reference Manual 300530EN, Rev BA September 20 12 C-5 Rosemount 2410 Appendix C. Advanced Configuration C.4 S ECONDARY BUS The Rosemount 2410 Secon dary Bus is used for communication with emulated devices. It support s protocols such as the TRL2 Modbus, Enraf, V arec, L&J, and Profibus.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 C-6 Appendix C. Advanced Configuration C.5 R ELAY OUTPUT The Rosemount 2410 has two relays which can be configured with one or two set points. Control mode (auto/ disabled), relay output source, set-point etc.
Reference Manual 300530EN, Rev BA September 20 12 C-7 Rosemount 2410 Appendix C. Advanced Configuration Virtual Relay St ates There are thre e virtual relay states available: T able C-1. 2410 Relay S tates Virtual Relay Output The Vi rtual Relay Output setting determines whether the relays are active or disabled.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 C-8 Appendix C. Advanced Configuration Relay output configuration The relay output can be selected as either Normally Open or Normally Closed referring to the co ntact position when the relay is de-ener gized.
Reference Manual 300530EN, Rev BA September 20 12 C-9 Rosemount 2410 Appendix C. Advanced Configuration Relay Zones Y ou can use on e or two set points for relays connecte d to the Rosemount 2410 T ank Hub. Consequently , there are two or three zones in which different relay states can be specified.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 C-10 Appendix C. Advanced Configuration C.6 HYBRID DENSITY CALCULATION The Rosem ount T ankMaster sof tware can be used in a hybrid density system to calculate Observed Density .
Reference Manual 300530EN, Rev BA September 20 12 C-1 1 Rosemount 2410 Appendix C. Advanced Configuration 6. In the 22XX A TD / Advanced Parameter Source Co nfiguration wind ow , ensure that the V apor Pressure (P3) and Liquid Pressure (P1) paramete rs are mapped to the actual source devices on the t ank.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 C-12 Appendix C. Advanced Configuration C.6.1 Hybrid Density Configuration T o configure the Rosemount 2410 hybrid density function do the following: 1. Open the 2410 T ank Hub/Configuration window .
Reference Manual 300530EN, Rev BA September 20 12 C-13 Rosemount 2410 Appendix C. Advanced Configuration 3. From the T ank Name/Hub Position list se lect the t ank to be configured for hybrid density calculations. 4. Enter Local Gravity , Air Density and V apor Density .
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 C-14 Appendix C. Advanced Configuration C.7 V OLUME CONFIGURATION T o c onfigure the Rosemount 24 10 T an k Hub for volu me calculations , choose one of the sta ndard tank shapes, or th e strapping table option, see T able C-4 on page C-15.
Reference Manual 300530EN, Rev BA September 20 12 C-15 Rosemount 2410 Appendix C. Advanced Configuration Holding and Input Registers for V olume Configuration Holding registers 4300 to 4732 are used for volume configuration.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 C-16 Appendix C. Advanced Configuration The T ankMaster WinSetup program let s you edit Holding registers for volu me calculations as illust rated in Figure C-10.
Reference Manual 300530EN, Rev BA September 20 12 C-17 Rosemount 2410 Appendix C. Advanced Configuration C.8 A RITHMETIC OPERATIONS The Rosemount 2410 T ank Hub support s various arithmetic calculations. Holding Registers 4800 to 4879 are used for up to 10 arithmetic operations.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 C-18 Appendix C. Advanced Configuration Arithmetic1 B tank number 4807 T ank for the arithmetic operation parameter B.
Reference Manual 300530EN, Rev BA September 20 12 C-19 Rosemount 2410 Appendix C. Advanced Configuration C.8.1 Delt a Level Calculation The following example illustrates how to use T ankMaster WinSetup to configure a Rosemount 241 0 to calculate the diff erence between product levels for two tanks Ta n k 1 and Ta n k 3 .
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 C-20 Appendix C. Advanced Configuration.
Reference Manual 300530EN, Rev BA September 2012 Rosemount 2410 www .rosemount-tg.com Index Numerics 2160 Field Communication Uni t 2-9 , 4-6 2410 . . . . . . . . . . . . . . . . . . . . . 2-9 2410 Tank Hub . . . . . . . . . 2-1 , 2-9 2410 Tank Hub Simulation window 6-12 5300 Guided Wave Radar .
Rosemount 2410 Index-2 Reference Manual 300530EN, Rev BA September 2012 Relay output . . . . . . . . . . . . . . C-6 Relay output configuration first and second set points C-6 hysteresis . . . . . . . . . . . . . C-6 hysteresis zone . . . . . . . . C-6 jumper settings .
.
Reference Manual 300530EN, Rev BA September 20 12 Rosemount 2410 Emerson Process Management © 2012 Rosemount T ank Radar AB. All rights reserved. Rosemount and the Rosemount logotype are trademarks o f Rosemount Inc. HART is a trademark of the HART Communication Foundation.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Emerson Process Management Rosemount 2410 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Emerson Process Management Rosemount 2410 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Emerson Process Management Rosemount 2410, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Emerson Process Management Rosemount 2410 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Emerson Process Management Rosemount 2410, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Emerson Process Management Rosemount 2410.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Emerson Process Management Rosemount 2410. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Emerson Process Management Rosemount 2410 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.