Manuel d'utilisation / d'entretien du produit Liebert Xtreme Density du fabricant Emerson
Aller à la page of 84
Precision Cooling For Business -Critic al C ontinuity™ Li eber t ® Xtreme De nsit y ™ Sys tem Des ign Ma nual.
.
i T ABLE OF CONTENTS 1.0 S YSTEM D ESCR IPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.1 European Union Fluorinated Greenho use Gas Requirements . . . . . . . . . . . . . . . . . . . .
ii 3.20 Display Panel and Remote Temperature/Humidity Se nsor Locations . . . . . . . . . . . . . . . . . 29 4.0 L IEBERT XD C OOLING M OD ULES —L IEBERT XDO, L IE BERT XDV , L IEBERT XDH AND L IEBERT XDCF . . . . . . . . . . . . . . . . . . . . . .
iii Figure 24 Hydraulic diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Figure 25 Bypass flow controller details, dimensions . . . . . . . . . . . . . . . . . . . .
iv TA B L E S Table 1 Liebert XD field-installed port kits header connection size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 0 Table 2 Maximum and minimum modules supported by a Liebert XDP or Liebert XDC .
System Description 1 1.0 S YSTEM D ESCRIPTION The Liebert XD™ family of cooling units delivers efficient, sensible cooling to high-heat environ- ments. Liebert XD systems are desi gned to cool computer racks and hot zones in a data center or com- puter room without taking up expensiv e floor space for co olin g components.
System Description 2 1.1 European Union Fluorinated Greenhouse Gas Requirement s Stationary air conditioning, refrigerat ion, heat pu mp equipments and stationa ry fire protection sys- tems in the Eur.
System Description 3 1.3 Liebert XDO—Over head Cooling Module The Liebert XDO ceiling-mounted cooling module draw s in hot air rising from densely populated cab- inets, passes it over the Liebert X DO’s coils and exha usts cooled air downward into the cold aisle.
System Description 4 1.4 Liebert XDV—V ertical, Ab ove-Cabinet Cooling Module The Liebert XDV is installed o n top of or above a rack enclosure. It is available with optional flexible metal pipes with automatic shutoff with quick-connect couplings at the ends for easy connection to the refrigerant distribution pi pes.
System Description 5 1.5 Liebert XDH—Horizontal Cooling Module The Liebert XDH cooling module is designed to be placed within a row of server enclosures in a hot aisle-c old aisle arrang ement. The Li ebert XDH ha s dual refrigerat ion circuits and is availabl e in a half-rack-width un it.
System Description 6 1.6 Liebert XDCF The Liebert XDCF is a self-contained module design ed to cool Ege nera’s BladeFrame EX cabinets and equipment without exhausting heat into the room. T wo modules (top and bottom) may be mounted on the rear of a BladeFrame cabinet.
System Description 7 1.7 Liebert XDA—Air Flow Enhancer The Liebert XDA is a fan unit that boosts the airf low through densel y populated enclosures, removing hot spots from within the racks. One or two units ca n be mounted on the rear of most rack enclosure s.
System Description 8 1.8 Liebert XDP—Pumping Unit The Liebert XDP isolates the buildi ng’s chilled water circuit from th e pumped refrigerant circuit.
System Description 9 1.9 Liebert XDC—Refrigerant Chiller The Liebert XDC is an indoor chi ller that connects directly to the Liebert XD cooling modules and pro- vides refrigerant circulati on and control.
System Description 10 1.10 Liebert XD Piping Liebert XD Piping is prefabricated di stribution piping that is installed in a nticipation of a growing sys- tem. Liebert XD cooling modules are a dded as required and are quickly made operational with f lexible connection piping with threaded couplings.
Starting a New Equipment Cooling Project 11 2.0 S TA R T I N G A N EW E QUIPMENT C OOLING P ROJECT 2.1 Determining Cooling Equipment Needs 1. Is adequate space av ailable for a Lieb ert XD installation? 2. Is the hot aisle/cold aisle approach being util ized for this room design or can it be utilized in this room design? 3.
Starting a New Equipment Cooling Project 12 2.2 Implementing a Hot-Aisle/Cold Aisle Design A best practice is to use rows of equipment racks in an alternating arrangemen t of cold aisles and hot aisles.
Designing a Li ebert XD Solution 13 3.0 D ESIGNING A L IEBERT XD S OLUTION Liebert XD systems are intended for use with p recis ion air conditioni ng equipment, such as the Lie- bert Delux e System/3 and Liebert D S. The precision ai r conditioning equi pment is required to control the room’s humid ity and to filter the ai r.
Designing a Li ebert XD Solution 14 3.3 Selecting Liebert XD Cooling Modules The next step is to select the Li ebert XD coo ling modules to be con figured into the solution. Liebert XD modules that use pumped refrigerant can be co nnected to the same Liebert XDP/Liebert XDC pip- ing circuit.
Designing a Li ebert XD Solution 15 3.6 Liebert XDO Placement 3.6.1 Determining S p acing of Liebert XDOs in an Aisle Liebert XDO units should be placed in rows directly above the cold aisles of a room for optimum cool- ing. Each Liebert XDO serves an area equal in width to the cold aisle spacing, typically 12 to 16 feet (3.
Designing a Li ebert XD Solution 16 3.6.2 Determining V ertical Placeme nt of Liebert XDOs Above the Cold Aisle In the maximum density configuration, Emerson recommends pl acing the Liebert XDOs between 18 and 24 inch es (457-609mm) above the equipment cabinets.
Designing a Li ebert XD Solution 17 3.7 Liebert XDV Unit Placement Liebert XDV units sh ould be placed o n top of the ca binets that g enerate the greatest amount of heat. If heat loads are dispersed evenly throughout th e room, the Lieber t XDV mo dules may be spread out accordingly.
Designing a Li ebert XD Solution 18 3.8 Liebert XDCF Placement The Liebert XDCF is a self-contained module design ed to cool Ege nera’s BladeFrame EX cabinets and equipment. Liebert XDCF modules a ttach to the rear of the Egenera BladeFrame EX ca binet, b eside the power modules (see Figure 17 ).
Designing a Li ebert XD Solution 19 3.9 Liebert XDH Placement The free-standi ng Liebert X DH cooling unit is best p laced amon g the equipm ent cabinets in a hot aisle-cold aisle arrangement (see Figure 18 ).
Designing a Li ebert XD Solution 20 3.1 1 Examples of Exp ansion and Interlaced Connection of Lieber t XD Cooling Modules Figure 19 Liebert XDV unit s mounted on racks emitting 3k W of heat, top view .
Designing a Li ebert XD Solution 21 Figure 21 Liebert XDV unit s mounted on racks emitting 8k W of heat top view Figure 22 Liebert XDV unit s mounted on racks emitting 16kW of hea t top view Do wn f l.
Designing a Li ebert XD Solution 22 3.12 Liebert XD Refrigerant The refrigerant used in the Liebert X D system is HFC-134a ( 1,1,1,2-tetrafluoroetha ne), made by a number of manufacturers. The amo unt of refrigerant used by the Liebert XD system may be signi fi- cantly higher than in typical DX coo ling systems.
Designing a Li ebert XD Solution 23 Figure 23 Piping for Liebert XDP/Liebert XDC used with Liebe rt XD cooling units The assembly and connection means used for piping in the Liebert XD system are similar to that of conventional refrigeration systems. All pi ping should be in stalled with high te mperature brazed joints.
Designing a Li ebert XD Solution 24 Figure 24 Hydraulic diagram 3.14 Liebert XD Piping Slope The main supply and return lines to and from the XDP/XDC must be sloped downward toward the XDP/XDC at a rate of 1-2" per 20 feet (25-51mm per 6m) of pipe run.
Designing a Li ebert XD Solution 25 Figure 25 Byp ass flow controller det ails, dimensions Figure 26 Byp ass flow controller arrangement Figure 27 Byp ass flow controller piping 7/8 " (2.
Designing a Li ebert XD Solution 26 3.16 Determining Refrigerant V olume After the preliminary system design is complete d, Tables 7 , through 15 may be used to determine the amount o f refrigeran t required . Perform the calculation below fo r each Liebert XD system being configured.
Designing a Li ebert XD Solution 27 T able 10 R-134a refrigerant charg e for Flex Pipe connector lines t o and from any model Liebert XDO/Liebert XDH/ Lie bert XDV/Liebert XDCF Refrigerant Charge, lb. (kg) Metal Flex Pipe Connector Length Supply Line Diameter 1/2" 0.
Designing a Li ebert XD Solution 28 3.16.2 Calculating Refrigerant Charge—Example Using Tables 7 , 8 , 9 and 10 , calculate the refrigerant charge of th e indiv idual sections of your Liebert XD system.
Designing a Li ebert XD Solution 29 3.18 Chilled W ater Piping The Liebert XDP is offered only with a two-way ch illed water control valve. Some applications may require the use of a pressure acti vated bypass va lve, to prevent dead- heading of the ch illed water pump.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 30 4.0 L IEBERT XD C OOLING M ODULES —L IEBERT XDO, L IEBERT XDV , L IEBERT XDH AND L IEBERT XDCF 4.1 Liebert XDO St andard Features • Micro Channel Heat Exchanger—The Liebert XDO unit incl udes two all-aluminum micro channel heat exchangers.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 31 Figure 28 Dimensional dat a—Liebert XDO hard-piped unit s Figure 29 Dimensional dat a—Liebert XDO with pre-.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 32 Figure 30 Liebert XDO internal mounting location DPN 000771 Pg.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 33 Figure 31 Liebert XDO top and front elec trical access point s 4.2 Liebert XDV St andard Features • Micro Channel Heat Exchanger—Th e Liebert XDV unit includes one al l-aluminum micro channel heat exchanger.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 34 4.2.1 Optional Features—Liebert XDV • Refrigerant Pr e-Charge —Liebert XDV units with the pre-char g ed refrigerant option will have one-shot style fittings or removable couplings that contain pressurized refr igerant inside the Lie- bert XDV.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 35 Figure 33 Liebert XDV dimensions with one-shot conn ection Deta il Area “A” De tail “A” Retur n Connect.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 36 Figure 34 Liebert XDV electrical connections for CE approved unit s PRI MARY PO WER SO URCE SE CO NDARY 82 83 60 Hz MO DE LS O NLY. FIE LD W IRING CONN E CTIONS AT T E RM INAL S TRIP TO BE N.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 37 Figure 35 Liebert XDV electrical connections for CSA-approved unit s Rear of XD V Condensa te Detecti on Dry Con tact s – Low Voltage Connections IEC Prim ary and Secon dary P o w e r In let PRI M ARY POWER SO URCE SECOND ARY 82 83 60 Hz MODE LS O NLY .
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 38 Figure 36 Suspending single Liebert XDV from Unistrut s Figure 37 Suspending single Liebert XDV from the roof s.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 39 Figure 38 Alternative mounting methods —mounting multiple Liebert XDV unit s Attach hanger brackets to each corner of each XD V . This arrangement permits mounting from either Unistrut s or from overhead structure.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 40 4.3 Liebert XDCF S tandard Features The Liebert XDCF is a self-contained module design ed to cool Ege nera’s BladeFrame EX cabinets and equipment without exhausti ng heat into the roo m.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 41 4.4 Liebert XDCF Mechanical Considerations The Liebert XDCF is engineered to fit on the rear of the Egenera BladeFrame enclosure. Figure 40 illustrates the unit’s dimensions and the location of pi pes.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 42 4.5 Liebert XDCF Inst allation Considerations No cutting or dril ling is required to attach the modules to the rear of the Egenera BladeFrame cabi- net. All mounting holes, slots and pins required are fabricated at the factory.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 43 4.6.1 Header System The Liebert XDCF module system requires use of the Liebert XD prefabrica ted piping a ssembly. The prefabricated pi ping is compatible with the flex pipe required to at tach to the Liebert XDCF modules.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 44 Figure 43 Liebert XDH dimensions Figure 44 Supply and return piping connections 78" (1981mm) 42 (1067mm) F.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 45 4.7.2 Piping Connections to Lieb ert XDP or Liebert XDC Piping Inst allation for Hard Piped System The assembly and connection means for piping in the Liebert XD system are similar to those used for conventional refrigeration systems.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 46 4.8 Liebert XD Flex Pipe Kit Flex Pipe kits are available in lengths of 4, 6, 8 and 10 feet (1.2, 1.8,2.4 and 3 meters). Connect ion style to the unit end may be straight or 90 degre e s.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 47 4.9 Liebert XD Piping Di mensions and Features 4.9.1 Piping Inst allation Method prefabricated headers The assembly and connection means used for piping in the Liebert XD system are similar to those used for conven tional refrigeration s ystems.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 48 Figure 47 Four-port prefabr icated piping for Liebert XD cooling modules T able 19 Four-port pref abricated pip.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 49 Figure 48 Five-port prefabrica ted piping for Liebert XD coo ling modules T able 20 Five-port pref abricated pi.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 50 Figure 49 T en-port pre fabricated piping for Liebert XD coolin g modules T able 21 T e n-port pref abricated p.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 51 4.10 Liebert XDP St andard Features • Heat Exchanger—Brazed plate design with in terw oven circuiting constructed of stainless steel plates, copper brazed. • Pumps—Centrifugal type, end suction, internally cooled, canned rotor design.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 52 Figure 51 Liebert XDP piping access point s and external features T able 23 Unit piping outlet connection sizes.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 53 Figure 52 Front view of Liebert XDP and elect rical enclosure Figure 53 Liebert XDP electrical enclos ure kno c.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 54 Figure 54 Liebert XDP 60Hz high volt age connections Figure 55 Liebert XDP 50Hz high volt age connections Custo.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 55 4.1 1 Liebert XDC St andard Features • Compressors—Sc roll with a suction ga s cooled motor, v ibration isolato rs, thermal overloa ds, man- ual reset high-pressure switch and pump down low-pressu re switch.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 56 Figure 57 Liebert XDC piping locations T able 25 Liebert XD Chiller piping connection sizes Air Cooled Models P.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 57 Figure 58 Positioning a water/g lycol Lieb ert XDC for placement on a floor st and T able 26 Liebert XDC W ater.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 58 Figure 59 Piping locations—flo or st and and valve assembly Shaded ar eas indicat e a rec ommended clearance of 36" (915mm) f or comp onent access an d water/ glycol pip ing.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 59 Figure 60 Front view of Liebert XDC and ele ctrical enclosures Figure 61 Liebert XDC electrical enclosur e knoc.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 60 Figure 62 Liebert XDC high volt age connecti ons —primary disconnect switch , 60Hz models Figure 63 Liebert X.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 61 Figure 64 Liebert XDC high volt age connections—secondary disconnect switch, 60Hz mo dels Figure 65 Liebert X.
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 62 Figure 66 Liebert XDC heat reject ion electrical conn ection point s Figure 67 Liebert XDC electrical enclosur .
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV , Liebert XDH and Lie bert XDCF 63 Figure 68 Liebert XDC Extra Low V oltage f ield connections point s Control wiring must be Class 2 and install .
Specifications 64 5.0 S PECIFICATIONS T able 27 Liebert XDC160 specifications Models XDC160 Air XDC160 Water / Glycol XDC160AA XDC160AM 189192G3 189192G5 Cooling Capacity, tons (kW) 46 (160) 37 (130) .
Specifications 65 T able 28 Floor st and specificat ions—water-c ooled Liebert XDC Models - 60 Hz XDC160 W ater Floor St and - 60Hz Entering Fluid Temp °F (C) 65 (18) 70 (21) 75 (24) 85 (29) 95 (35) Performance Data Cooling capacity, tons (kW) 46.1(162.
Specifications 66 T able 30 Floor st and specifications—Liebert XDC with 40% ethylene glyc ol Models - 60 Hz XDC160 Glycol Floor St and - 60Hz - 40% EG Outside Ambient °F (°C) 95 (35) 100 (38) 105 (41) Entering Fluid Temp °F (°C) 110 (43) 110 (43) 110 (43) Performance Da t a Cooling capacity, tons (kW) 42.
Specifications 67 T able 31 Liebert XDP160 specifications Models XDP160RC XDP160RA XDP160RM Cooling Capacity, Nominal 160 kW / 46 Tons, 60Hz 140 kW / 40 Tons, 50Hz Each capacity is based on 45ºF (7ºC) entering water te mperature and 140gpm (530lpm) water flow rate.
Specifications 68 T able 32 Liebert XDO16 specific ations Models XDO16BK--0 XDO16DK--0 XDO16BK-E0 XDO16DK-E0 XDO16BKP-0 XDO16BKPE0 XDO16DKP-0 XDO16DKPE0 (60Hz) XDO16BSP-0 XDO16BSPE0 XDO16DSP-0 XDO16DS.
Specifications 69 T able 33 Liebert XDO20 specific ations Models XDO20DK--*; XDO20BKP-* XDO20DKP-*; XDO20BK-E* XDO20DK-E*; XDO20BKPE* XDO20DKPE* XDO20BS--*; XDO20DS--* XDO20BSP-*; XDO20DSP-v XDO20BS-E*; XDO20DS-E* XDO20BSPE*; XDO20DSPE* 60Hz 60Hz 50Hz Cooling Capacity Nominal (92°F [33°C] EAT): 20kW / 5.
Specifications 70 T able 34 Liebert XDO20 dime nsio ns—domestic and export Model Shipping Dimensions, inches (mm) Unit Dimension Unpacked, inches (mm) Domestic Export Length Width Height Length Widt.
Specifications 71 T able 36 Liebert XDV8 specifications Models XDV8BK--*; XDV8DK--* XDV8BKP-*; XDV8DKP-* XDV8BK-E*; XDV8DK-E* XDV8BKPE*; XDV8DKPE* XDV8BKR-*; XDV8BKRE* XDV8DKR-*; XDV8DKRE* XDV8BT--*; .
Specifications 72 T able 37 Liebert XDV10 s pecifications Models XDV10BK--*; XDV10DK--* XDV10BKP-*; XDV10DKP-* XDV10BK-E*; XDV10DK-E* XDV10BKPE*; XDV10DKPE* XDV10BKR-*; XDV10BKR E* XDV10DKR-*; XDV10DK.
Specifications 73 T able 38 Liebert XDV8 dime nsions—domestic and export Model Shipping Dime nsions Length x Width x Height inches (mm) Unit Dimens ions Unpacked Length x Widt h x Height inches (mm).
Specifications 74 T able 41 Liebert XDH specifications Models XDH20DKP-0 XDH20DK--0 XDH20BKP-0 XDH20BK--0 XDH20DKPE0 XDH20DK-E0 XDH20BKPE0 XDH20BK-E0 (60Hz) XDH32DKP-0 XDH32DK--0 XDH32BKP-0 XDH32BK--0.
Specifications 75 Notes.
Specifications 76.
.
Ensuring The Hi gh Av ailab ilit y 0f Mission-Critic al Dat a And Applic ations. Emerson Net work P ow er , the global leader in enabling business-critical continuity , ensures network resiliency and .
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Emerson Liebert Xtreme Density c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Emerson Liebert Xtreme Density - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Emerson Liebert Xtreme Density, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Emerson Liebert Xtreme Density va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Emerson Liebert Xtreme Density, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Emerson Liebert Xtreme Density.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Emerson Liebert Xtreme Density. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Emerson Liebert Xtreme Density ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.