IDEALLY I NSTALL IN T HE C ENTRE OF CEILIN G AT L EAST 3 00mm FROM L IGHT FITTINGS LOCATE IONISATION A LARMS AWAY FROM KITCHENS TO PREVENT NUISANCE ALARM S ENSURE L IVE MAINS IS CORRECTLY CONNECTED TO.
1.1 Installation Guide 2.
2. Alarm Removal SLIDE AL AR M OFF BA SE WI TH T HE S CREW DRIVER STILL IN SER TE D, PUSH TH E LO WE R HALF OF TH E ALARM AW AY F ROM THE SCRE WD RIVER, I N TH E DIRECTION OF THE ARROW ON THE COVER HO.
2. HOW MANY ALARMS TO INSTALL - CATEGORIES & GRADES - The advice here follows the guidance in British Standard BS 5839-Part 6: 2004 in general (for further information see the BS standard itself).
for dwellings where occupants may be at high risk (e.g. elderly) OPTIMUM PROTECTION LD1 Optimum Protection LD1: As LD2, but in addition Smoke or Heat Alarms should be located in all rooms and other areas of the dwelling. (apart from toilets or bathroom) Multi Storey Dwelling LD1 Heat Alarms located in: (Heat Alarms must be within 5.
for dwellings where occupants may be at high risk (e.g. elderly) OPTIMUM PROTECTION LD1 Optimum Protection LD1: As LD2, but in addition Smoke or Heat Alarms should be located in all rooms and other areas of the dwelling. (apart from toilets or bathroom) Multi Storey Dwelling LD1 Heat Alarms located in: (Heat Alarms must be within 5.
for dwellings where occupants may be at high risk (e.g. elderly) OPTIMUM PROTECTION LD1 Optimum Protection LD1: As LD2, but in addition Smoke or Heat Alarms should be located in all rooms and other areas of the dwelling. (apart from toilets or bathroom) Multi Storey Dwelling LD1 Heat Alarms located in: (Heat Alarms must be within 5.
2.2 Selecting Alarm Type 1 Optical Smoke Alarms are recommended due to their excellent response to smouldering fires. If there is likely to be problems with steam, contamination or dust build-up, or if there is significant risk of a fast burning clean fire an Ionisation Smoke Alarm should be fitted.
Improved Audibility The effectiveness of Category LD2 and LD3 systems can be significantly enhanced if an additional Smoke Alarm (interconnected) is installed in the master bedroom. This will help ensure that a responsible person will quickly be alerted to a fire and can arrange for an orderly evacuation of children and other vulnerable occupants.
Wall mounting of smoke alarms (only): If ceiling mounting is impractical, smoke alarms may be mounted on a wall, provided that: a) the top of the detection element is between 150mm and 300mm below the.
• Do not locate in insect infested areas . Small insects getting into the smoke detector chamber can cause intermittent alarms. Insects and contamination on the Heat Alarm sensor can increase its response time. 4. INSTALLATION The Alarm is designed to be permanently mounted, using it’s own built-in terminal block to connect it to the mains.
Note: BS 5839-6 2004 gives the folowing recommendations regarding the mains supply to be used in a Grade D system (The Ei141RC/146RC/161RC/166RC Smoke Alarms and Ei144RC/164RC Heat Alarms can be used in a Grade D system). The power supply for the Alarms should be derived from the public electricity supply to the dwelling.
We strongly recommend that you check for the following before connecting the alarm : • check for Live and Neutral using a two probe tester. • check for Live using a neon tester. • check that the Interconnect wire is NOT connected to Live, Neutral or Earth.
prevent air draughts affecting the smoke/heat entering the alarm. If the hole is too large or the alarm does not seal it, it should be sealed with silicone rubber or equivalent. 6. Replace the wiring cover. Check the alarm battery is connected (Ei141RC/144RC/146RC only).
In the UK it is recommended that the following coloured cores are used (for example with triple flat 6243Y cable). 230V supply Brown Neutral Grey - sleeved blue at terminations Interconnect Black The interconnect wire (minimum 0.75mm 2 cable) must be treated as if it was Live.
5. ACCESSORIES Alarm System Control Switch Ei1529RC: The Syst em Contr ol Switc h is recommended for systems with three or more Smoke / Heat Alarms. It a llo ws the user to perform the following functions from a remote location: LOCATE - If alarms sound press Locate to allow source of alarm to be identified.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Ei Electronics Ei146RC c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Ei Electronics Ei146RC - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Ei Electronics Ei146RC, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Ei Electronics Ei146RC va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Ei Electronics Ei146RC, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Ei Electronics Ei146RC.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Ei Electronics Ei146RC. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Ei Electronics Ei146RC ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.