Manuel d'utilisation / d'entretien du produit VFD-XXXM du fabricant Delta Electronics
Aller à la page of 22
English-1 Preface Thank you for choosing DELTA’s high-perform ance VFD-M Serie s. The VFD-M Series is manufactured with high-quali ty components and material s and incorporates the latest micro processor technology av ailable. Getting Started This quick start w ill be helpful in the installation and parameter setting of the AC motor driv es.
English-2 Specifications Voltage Class 1 15V Class Model Number VFD-XXXM 002 004 007 Max. Appli cable Motor Output ( kW) 0.2 0.4 0.75 Max. Applicable M otor Output ( hp) 0.25 0.5 1.0 Rated Output Capaci ty (kVA) 0.6 1.0 1.6 Rated Output Cur rent (A) 1.
English-3 Voltage Class 575V Class Model Number VFD-XX XM 007 015 022 037 055 075 Max. Applicable M otor Output ( kW) 0.75 1.5 2.2 3.7 5.5 7.5 Max. Applicable Motor Output (hp) 1.0 2.0 3.0 5.0 7.5 10 Rated Output Capacity (kVA) 1.7 3.0 4.2 6.6 9.9 12.
English-4 General Specifications Protection Functions Self-testi ng, over v oltage, ov er current, under voltage, ov erload, over heating, external fault , electronic ther mal, groun d fault.
English-5 Description of Digital Keypad The digital keypad i ncludes two parts: Display panel and key pad. The display panel pr ovides the parameter display and shows the operation stat us of the AC drive and the key pad provides programming and control interface .
English-6 Power Terminals Model Name Max. Current (input / output) Wire Gauge AWG (mm 2 ) Torque kgf-cm (in-lbf) VFD002M11A 6A/1.6A VFD004M11A 9A/2.5A 12-14 (3.3-2.1) VFD007M11A 16A/4.2A 12 (3.3) VFD004M21A/21B 6.3A/2.5A VFD004M23A 3.2A/2.5A VFD007M21A/21B 11.
English-7 Terminal Explanations Terminal Symbol Explanation of T ermi nal Function R/L1, S/L2, T/L3 AC line i nput terminals (thr ee phase) U/T1, V/T2, W/T 3 Motor connections B1 – B2 Connections fo.
English-8 Terminal Symbol Terminal Function Factory Settings (NPN mode) M0 Multi-function auxiliary input M1 Multi-function input 1 M2 Multi-function input 2 M3 Multi-function input 3 M4 Multi-function input 4 M5 Multi-function input 5 M0~M5-GND Refer to P38~P42 for prog ramming the multi-func tion inputs.
English-9 SUMMARY OF PARA METER SETTINGS a : The parameter can be set during operation Parameter Expl anation Settings Factory Setting Customer a Pr.00 Source of Frequency Command 00: Master frequen c.
English-10 Parameter Expl anation Settings Factory Setting Customer a Pr.16 Jog Frequency 0.00 to 400.0 H z 6.00 a Pr.17 1st Step Speed Freq. 0.00 to 400.0Hz 0.00 a Pr.18 2nd Step Speed Freq. 0.00 to 400.0Hz 0.00 a Pr.19 3rd Step Speed Freq. 0.00 to 400.
English-1 1 Parameter Expl anation Settings Factory Setting Customer Pr.38 Multi-function Input Terminal (M0,M1) 00: M0: FWD/STOP, M1: REV/STO P 01: M0: RUN/STOP, M1: REV/ FWD 02: M0, M1, M2: 3-wire operation control mode 00 Pr.
English-12 Parameter Expl anation Settings Factory Setting Customer Pr.45 Pr.46 Multi-Function Output Terminal 1 (Photocoupler outp ut) Multi-function Output Terminal 2 (Relay Output) 00: AC Drive Operational 01: Maximum Output Frequency Attained 02: Zero Speed 03: Over-Torque Detection 04: Base-Block (B.
English-13 Parameter Expl anation Settings Factory Setting Customer a Pr.59 Electronic Thermal Motor Overload 30 to 300 sec 60 Pr.60 Over-Torque Detection Mode 00: Over-Torque Detection Disable 01: Enabled during constant speed operation until th e allowable time for detection (Pr.
English-14 Parameter Expl anation Settings Factory Setting Customer Pr.73 Present Fault Record 00 Pr.74 Second Most Recent Fault Record 00 Pr.75 Third Most Rec ent Fault Record 00: No fault occurred 0.
English-15 Parameter Expl anation Settings Factory Setting Customer Pr.84 Time Duration of 4th Step Speed 00 to 9999 sec 00 Pr.85 Time Duration of 5th Step Speed 00 to 9999 sec 00 Pr.86 Time Duration of 6th Step Speed 00 to 9999 sec 00 Pr.87 Time Duration of 7th Step Speed 00 to 9999 sec 00 Pr.
English-16 Parameter Expl anation Settings Factory Setting Customer Pr.102 Auto Voltage Regulation (AVR) 00: AVR function enabled 01: AVR function disabled 02: AVR function di sabled when stops 03: AVR function di sabled when decel 00 Pr.103 Auto tune Motor Parameters 00: Disable 01: Auto tune for R1 02: Auto tune for R1 + No Load testing 00 Pr.
English-17 Parameter Expl anation Settings Factory Setting Customer Pr.119 Differential Time (D) 0.00 to 1.00 se c 0.00 Pr.120 Integration’s Upper Bound Frequency 00 to 100 % 100 % Pr.121 One-Time Delay 0.0 to 2.5 sec 0.0 Pr.122 PID Frequency Output Command Limit 00 to 110 % 100 Pr.
English-18 Parameter Expl anation Settings Factory Setting Customer Pr.142 Second Source of Frequency Command 00: Keypad Up/Down 01: AVI (0-10V) 02: ACI (4-20mA) 03: Communication 04: Keypad potentiometer 00 115V/230V 370-450 Vdc 380.0 460V 740-900 Vdc 760.
English-19 Fault Codes Fault Name Faul t Descriptions Corrective A ctions Over current Abnormal i ncrease in current. 1. Check whether the motors ho rsepower cor responds to th e AC drive output p ower. 2. Check the wiring connection s between the AC drive and motor for possible short circuits.
English-20 Fault Name Faul t Descriptions Corrective A ctions Over-current during acceleration 1. Short-circuit at motor ou tput: Check for possible poor insulation at the outp ut lines. 2. Torque boost too high: Decr ease the torque compensation setting in Pr.
English-21 Fault Name Faul t Descriptions Corrective A ctions CC (cur rent cl amp) OV hardware error GFF hard ware error OV or LV Current sensor error U-phase erro r W-phase error Return to the facto ry. Phase Loss Check input phase wiring for loose contacts.
English-22 D1 D H2 H H1 W W1 Unit: mm [inch] Model Name W W1 H H1 H2 D D1 VFD022M21A, VFD037M23A/43A/53A, VFD055M23A/43A/53A, VFD075M43A/53A 125.0 [4.92] 110.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Delta Electronics VFD-XXXM c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Delta Electronics VFD-XXXM - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Delta Electronics VFD-XXXM, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Delta Electronics VFD-XXXM va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Delta Electronics VFD-XXXM, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Delta Electronics VFD-XXXM.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Delta Electronics VFD-XXXM. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Delta Electronics VFD-XXXM ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.