Manuel d'utilisation / d'entretien du produit SINGLE PACKAGED HEAT PUMP UNITS 657A du fabricant Bryant
Aller à la page of 32
NOTE: Read the entire instruction manual before starting the installation. This symbol → indicates a change since the last issue. TABLE OF CONTENTS SAFETY CONSIDERATIONS .....................................................1 Introduction ...........
severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
Forward claim papers directly to transportation company. Manu- facturer is not responsible for any damage incurred in transit. Check all items against shipping list. Immediately notify the nearest distributor if any item is missing. To prevent loss or damage, leave all parts in original packages until installation.
outdoor coil-air inlet to prevent obstruction of airflow by grass or shrubs. Do not secure the unit to the slab except when required by local codes. III. PROVIDE CLEARANCES The required minimum service clearances are shown in Fig. 2-5. Adequate ventilation and outdoor air must be provided.
should be at least 4 in. above the highest expected water and runoff levels. Do not use unit if it has been under water. IV. SELECT AND INSTALL DUCTWORK The design and installation of the duct system .
filter rack installed in the return-air side of the unit. Recommended sizes for filters are shown in Table 1. 2. Avoid abrupt duct size increases and reductions. Abrupt change in duct size adversely affects air performance. IMPORTANT: Use flexible connectors between ductwork and unit to prevent transmission of vibration.
to prevent damage when moving the unit. Unit must remain in an upright position during all rigging and moving operations. The unit must be level for proper condensate drainage; the ground-level pad or accessory roof curb must be level before setting the unit in place.
WARNING: Secure screws and paint protectors solidly against unit base to hold lifting brackets in position. Never use lifting brackets when the temperature is below -10 F (-23 C). Never exceed 200 lbs per bracket of lifting force. Never use lifting brackets for lifting other models of air conditioning units.
WARNING: Lifting point should be directly over the center of gravity for the unit. Failure to follow this warning could result in personal injury or death. VI. CONNECT CONDENSATE DRAIN NOTE: When installing condensate drain connection be sure to comply with local codes and restrictions.
Fig. 13—Removing Insulation and Vertical Duct Cover C95015 Fig. 14—Indoor Blower Access Panel C950016 INDOOR BLOWER ACCESS P ANEL (REMOVE SCREWS) Fig.
flexible duct is used, insert a sheet metal sleeve inside duct. Heat resistant duct connector (or sheet metal sleeve) must extend 24-in. from the unit discharge connection flange into the ductwork. ACCESSORY DUCT FLANGE KIT INSTALLATION- 1. Mark hole locations (See instructions included in Flange Kit).
WARNING: Before performing service or maintenance operations on the system, turn off main power to unit and install lockout tag or electrical shock could result. 1. Open all electrical disconnects and install lockout tag before starting any service work.
securing the cover to the unit base and slide out the cover. Discard the cover. Install filler bracket removed in Step 7. 10. If unit ductwork is to be attached to vertical opening flanges on the unit base (jackstand applications only), do so at this time.
WARNING: Before performing service or maintenance operations on the system, turn off main power to unit and install lockout tag or electrical shock could result. 1. Open all electrical disconnects and install lockout tag before starting any service work.
3. ROUTING CONTROL POWER WIRES - STD NON- ECM UNITS (24 v) -Form a drip-loop with the thermostat leads before routing them into the unit. Route the thermostat leads through grommeted hole provided in unit (see Fig. 21) into unit control power splice box.
b. Inspect for oil at all refrigerant tubing connections and on unit base. Detecting oil generally indicates a refrig- erant leak. Leak test all refrigerant tubing connections using electronic leak detector, halide torch, or liquid- soap solution. If a refrigerant leak is detected, see Check for Refrigerant Leaks section.
c. Inspect all field- and factory-wiring connections. Be sure that connections are completed and tight. d. Ensure electrical wiring does not contact refrigerant tubes or sharp metal edges. e. Inspect coil fins. If damaged during shipping and han- dling, carefully straighten fins with a fin comb.
B. START UP AND MAKE ADJUSTMENTS CAUTION: Complete the required procedures given in the Pre-Start- Up section before starting the unit. Do not jumper any safety devices when operating the unit. Do not operate the compressor when the outdoor temperature is below 40°F (unless accessory low-ambient kit is installed).
Fig. 26—Wiring Diagram–024 to 042 (208/230-60-1) C95037 —19—.
Fig. 27—Wiring Diagram–048 to 060 (208/230-60-1 with ECM Indoor) C95038 —20—.
NOTE: Allow system to operate in the cooling mode for a minimum of 10 minutes before checking or adjusting refrigerant charge. CAUTION: When evaluating the refrigerant charge, an indicated adjustment to the specified factory charge must always be very minimal.
5. AC/HP TIME DELAY (GRY) - Four motor operation delay options are provided to customize system operation. See listing below: Unit Controls— All compressors have the following internal- protection controls. 1. High-Pressure Relief Valve - This valve opens when the pressure differential between the low and high side becomes excessive.
remains energized for the delay timing. When the fan switch is in AUTO, the fan cycles with either the call for heating or cooling. Cooling- On a call for cooling, 24 v is supplied to the compressor contactor (C) and IFM simultaneously through the ’’Y’’ and ’’G’’ terminals of the thermostat.
1. Inspect air filter(s) each month. Clean or replace when necessary. 2. Inspect indoor coil, drain pan, and condensate drain at least each cooling season for cleanliness. Clean when necessary. 3. Inspect blower motor and wheel for cleanliness and check lubrication each heating and cooling season.
WARNING: Disconnect and tag electrical power to the unit before cleaning the blower motor and wheel. Failure to adhere to this warning could cause personal injury or death. To clean the blower motor and wheel: 1. Remove and disassemble blower assembly as follows: a.
c. On all units remove blower assembly from unit. Remove screws securing blower and slide assembly out. Be careful not to tear insulation in blower compartment. d. Ensure proper reassembly by marking blower wheel and motor in relation to blower housing before disassembly.
f. Reassemble motor into housing. Be sure setscrews are tightened on motor shaft flats and not on round part of shaft. g. Reinstall unit access panel. 4. Restore electrical power to unit. Start unit and check for proper blower rotation and motor speeds during heating and cooling cycles.
E. OUTDOOR FAN CAUTION: Keep the outdoor fan free from all obstruc- tions to ensure proper cooling operation. Never place articles on top of the unit. Damage to unit may result. 1. Remove 2 screws at bottom of outdoor air intake grille and remove plastic grille.
G. REFRIGERANT CIRCUIT Inspect all refrigerant tubing connections and the unit base for oil accumulations annually. Detecting oil generally indicates a refrig- erant leak. WARNING: System under pressure. Relieve pressure and recover all refrigerant before system repair or final unit disposal to avoid personal injury or death.
Fig. 32—Typical Heat Pump Operation-Heating Mode C95045 STRAINER ACCUMULA TOR COMPRESSOR STRAINER LCS OUTDOOR COIL INDOOR COIL A B D C Check V alves A Open B Closed C Open D Closed LEGEND LCS Loss of Charge Switch Acutrol Metering Device Check V alve (Arrow indicates direction of flow) HEA TING CYCLE 1.
TABLE 14—TROUBLESHOOTING CHART SYMPTOM CAUSE REMEDY Compressor and outdoor fan will not start Power Failure Call power company Fuse blown or circuit breaker tripped Replace fuse or reset circuit bre.
START-UP CHECKLIST (REMOVE AND STORE IN JOB FILE) I. PRELIMINARY INFORMATION Model No ............................................................................................................................................................. Serial No .
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Bryant SINGLE PACKAGED HEAT PUMP UNITS 657A c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Bryant SINGLE PACKAGED HEAT PUMP UNITS 657A - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Bryant SINGLE PACKAGED HEAT PUMP UNITS 657A, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Bryant SINGLE PACKAGED HEAT PUMP UNITS 657A va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Bryant SINGLE PACKAGED HEAT PUMP UNITS 657A, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Bryant SINGLE PACKAGED HEAT PUMP UNITS 657A.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Bryant SINGLE PACKAGED HEAT PUMP UNITS 657A. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Bryant SINGLE PACKAGED HEAT PUMP UNITS 657A ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.