D400-13-00 1 I56-555-09R DH400ACDCP Air Duct Smoke Detector INST ALLA TION AND MAINTENANCE INSTRUCTIONS 3825 Ohio A venue , St. Charles, Illinois 60 174 1-800-SENSOR2, F AX: 63 0-377-6495 www .
[3] Contents Of The Duct Detector Kit 1. Complete housing base and cov er assembly 2. T wo #1 0 sheet metal mounting scre ws 3. T wo sampling tube filter s 4. One test magnet 5. Drilling template 6. T wo 5/16 O-rings 7. T wo rubber tube bushing seals 8.
feet per minute . Be sur e to check engineering specifications to ensure that the air velocity in the duct falls within these parameter s . If necessary , use a velocity meter to check the air velocity in the duct. [5.2] Drill The Mounting Holes R emo ve the paper backing from the mounting template supplied.
[5.4.1] Installation For Ducts Less Than 8 Feet Wide 1. If the tube is longer than the width of the air duct, drill a 3/4-inch hole in the duct directly opposite the hole already cut for the inlet tube. If the tube is shorter than the width of the air duct, install the end plug into the inlet tube as shown in Figure 4.
Install the inlet tube as follow s: 1. Drill a 3/4-inch hole in the duct directly opposite the hole already drilled for the inlet tube . 2. Slide the inlet tube with the flange into the centermost housing bushing. Position the tube so that the arr ow s point into the air flow .
24V 120 VAC 220/240 VAC 1 2 1 2 13 14 AVAILABLE POWER INPUTS ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN, ETC. 15 16 17 18 19 20 N.C. C. N.O. N.O. C. N.C. ALARM AUXILIARY CONTACTS SHOWN IN STANDBY. CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS.
24V 120 VAC 220/240 VAC 1 2 12 13 14 AVAILABLE POWER INPUTS ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN, ETC. 15 16 17 18 19 20 N.C. C. N.O. N.O. C. N.C. ALARM AUXILIARY CONTACTS SHOWN IN STANDBY. CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS.
[5.6] Install The Filters T o install the sampling tube filters , simply push the filter adapter into the exhaust tube, and push the filter onto the adapter tube on the left, as shown in Figure 9. Install the other filter ov er the end of the inlet sampling tube .
[6.1] Smoke Entr y T ests [6.1.1] Air Flow T o verify sufficient sampling of ducted air , use a manometer to measure the differ ential pressure created from air flow across the sampling tubes . The pr essure should measure no less than 0.0 1 inches of water and no greater than 1.
the R T S45 1/R T S45 1KEY manual. The DH400A CDCP duct detector can be reset by the R T S45 1/R T S45 1KEY . If a sys- tem control panel is used, the panel itself may also requir e resetting. T o install the R T S45 1/R T S45 1KEY , connect the device as shown in Figur e 8; wir e runs must be limited to 25 ohms or less per interconnecting wire .
3. V acuum the photo chamber . Use clean compr essed air to blow it clean. 4. R eplace the screen by aligning the arro w on top with the field test port on the detector . Press the screen into place . It should fit tightly on the chamber . 5. R eplace the detector co v er and rotate it clockwise to lock it in place .
[8] Model DH400ACDCP Air Duct Smoke Detector Specifications Description HV A C air duct mounted ionization or photoelectronic smoke detector for separately power ed sy stems or stand alone sys- tems. A uxiliary alarm relay contacts pr ovide fan contactor shutdo wn to pr e vent HV A C circulation of smoke .
Electrical Specifications P o wer supply v oltage: 20-29 VDC 24 V A C 5 0-60-Hz 120 V A C 50-60 Hz 220/240 V A C 50-60 Hz Input capacitance: 27 0 µ F max. 27 0 µ F max. N/A N/A R eset v oltage: 3.0 VDC min. 2.0 V A C min. 1 0 V A C min. 20 V A C min.
NOTES D400-13-00 14 I56-555-09R.
NOTES D400-13-00 15 I56-555-09R.
D400-13-00 16 I56-555-09R © Sy stem Sensor 1997 DETECTOR TEST LOG Detector Identification Infor mation Manufacturer and Serial Date Detector Model: ______________________ Number: ___________________.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté System Sensor DH400ACDCP c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du System Sensor DH400ACDCP - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation System Sensor DH400ACDCP, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le System Sensor DH400ACDCP va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le System Sensor DH400ACDCP, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du System Sensor DH400ACDCP.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le System Sensor DH400ACDCP. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei System Sensor DH400ACDCP ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.